CS Paper Radar

DynaSeek: Large Language Model-Driven Hybrid Dynamic Model Discovery for Grid-Tied Inverters from Limited Measurements

Hongwei Zhen, Chao Shen, Jianfeng Niu, Xin Xiang, Wuhua Li, Mingyang Sun

eess.SY ·submitted 2026-11-25 02:25 UTC · v1

Abstract

Discovering the unknown governing equations of grid-tied inverters from limited measurements is essential for the stability analysis of modern inverter-dominated power systems. However, existing identification methods struggle to jointly resolve unmeasured internal control memory and saturation-induced mode transitions from accessible terminal waveforms. To address this challenge, this paper proposes DynaSeek, a large language model (LLM)-driven framework for discovering explicit hybrid differential-algebraic equations (DAEs) of current-limited inverters. The framework integrates physics-constrained symbolic skeleton synthesis with the joint numerical estimation of shared model parameters and record-specific latent initial states across multi-island experience archives. Furthermore, two complementary structural diagnostics evaluating cross-record state closure and cross-window consistency are established to detect structural deficiencies across distinct input histories and transient stages. Guided by diagnostic feedback, DynaSeek directs variable-dimensional latent-state expansion and current-limiting and anti-windup refinement to yield self-contained hybrid DAEs unifying unsaturated regulation, current limiting, and post-fault recovery. Controller-hardware-in-the-loop (CHIL) experiments and closed-loop system-level simulations demonstrate that DynaSeek reduces transient trajectory reconstruction errors by one to two orders of magnitude compared with symbolic and neural baselines while accurately preserving reference critical clearing times, enabling reliable large-signal stability assessment of inverters with inaccessible internal controls.

Closest papers

Nearest neighbours by meaning across the whole index.

Recursive Self-Improvement LLM Agents for Inverter Dynamic Model Identification

eess.SY ·2026-09-13 ·Jie Feng, Xiaoyang Wang, Xin Chen, Yuanyuan Shi
publishedbenchmarkpositioncode/data similarity 0.65
Abstract · Presented at the 2026 IEEE Power & Energy Society General Meeting, Agentic AI for Empowering Future Grid Operations panel

This is a position paper. We demonstrate that recursive self-improvement (RSI) large language model (LLM) agents are a natural search engine for dynamic model identification of inverter-based resources (IBRs) whose internal controls are often proprietary and hidden from grid operators. White-box models provide physical transparency but require vendor disclosure; black-box models avoid this requirement but sacrifice interpretability; and existing grey-box approaches, including sparse and symbolic regression, are poorly suited to discovering feedback control architectures or incorporating control-engineering priors. Our position is that this gap can be alleviated by (1) restricting the search space to a typed vocabulary of standard control modules, including PI controllers, phase-locked loops (PLLs), low-pass filters, etc., composed under block-diagram grammar rules, and (2) using an RSI LLM agent to perform program search over candidate block-diagram models, guided by measured frequency-domain admittance data at the point of common coupling (PCC), while fitting the free parameters of each candidate by nonlinear least squares. We instantiate this position by adapting ThetaEvolve, an open-source program-evolution framework supporting in-context evolution and test-time learning, to inverter model discovery. In a proof-of-concept study on a grid-following (GFL) inverter benchmark, the RSI loop reduces the normalized root mean square error (NRMSE) of a naive open-loop model from 0.470 to 0.0435 and identifies a 15-module closed-loop structure that closely resembles the hidden ground-truth GFL controller.

0.43

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.60
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

Expanding the Transient Stability Region of Attraction of Networked Grid-Interactive Inverters: A Probabilistic Active Learning Framework

eess.SY ·2026-08-23 ·Zhong Liu, Jialin Zheng, Junjie Qin, Xiaonan Lu
benchmark similarity 0.58
Abstract

The continuous integration of inverter-based resources makes transient stability analysis increasingly important for power system modernization, in light of the intricate dynamics arising from large-scale inverter deployment. However, analytical transient stability analysis methods consistently yield overly conservative stability boundary estimates, which constrain grid dispatch and operational flexibility. Although recent neural Lyapunov methods attempt to enlarge these stability boundaries to obtain less conservative estimates, they remain trapped within restricted domains due to the out-of-distribution problem. To break this bottleneck, this paper proposes a probabilistic active learning framework. Starting from a deterministic inner stability region certified by neural Lyapunov functions, the framework constructs a Gaussian process surrogate and deploys an uncertainty-guided frontier search. By intelligently coupling electromagnetic transient simulations with active boundary exploration, the algorithm systematically drives the estimated stability boundary outward. Comprehensive evaluations across multi-machine grid-forming benchmarks demonstrate that the proposed framework substantially reduces estimation conservatism. Across test systems ranging up to four interconnected grid-forming inverters, the methodology achieves up to a $20$-fold volumetric enlargement of the certified stability region over classical baselines, while requiring at most 220 time-domain simulation queries per system, far fewer than the 1,600 queries that exhaustive EMT evaluation demands even for the simplest single-inverter benchmark.

0.30

Learning-Based Augmentation and Adaptation for Grid Sim-to-Real Model Discrepancy

eess.SY ·2026-09-18 ·Sayak Mukherjee, Kyung-Bin Kwon, Ramij R. Hossain, Marcelo Elizondo
benchmark similarity 0.57
Abstract · 12 pages, 5 figures, 3 tables

Modern power systems can encounter increased discrepancy between the operators' simulation model and the actual true dynamics of the grid, driven by uncertainties caused by integration of new inverter-based resources (IBRs), large loads, unmodeled dynamics, parameter drifts, etc., to name a few. All of these impact the control room operations, where some critical oscillations may not be captured during the transient studies. To circumvent these issues, we propose a learning-augmented hybrid approach where the operator simulation model is supplemented with artificial intelligence (AI)-learned residual models using the phasor measurement unit (PMU)/ point-on-wave (PoW) based sensed trajectory data. The physics-based operator model provides interpretability and structural consistency, while the learned residual captures discrepancies caused by non-idealities. The learned model employs advanced neural architectures and consists of a backbone encoder and multi-head decoder layers for heterogeneous grid channels. Subsequently, we formulated a continual learning-motivated adaptation framework such that the baseline residual AI model can also be updated when the underlying real grid model changes in future conditions. Extensive numerical simulations are performed on the IEEE 68-bus benchmark model with a diverse set of disturbances, and different state-of-the-art predictive architectures involving recurrent learners, latent neural ODEs, and transformers are explored to demonstrate both residual learning and adaptation capabilities.

0.28

Lyapunov Exponents in Power Systems: A Survey of Theory and Applications in Stability, Control, Forecasting, and Protection

eess.SY ·2026-10-16 ·Mohammad Almomani, Venkataramana Ajjarapu
survey similarity 0.57
Abstract

Lyapunov exponents (LEs) are fundamental metrics from nonlinear dynamical systems theory that quantify the average exponential rate of divergence or convergence of nearby trajectories in phase space. Over the past three decades, LEs have emerged as powerful tools across a wide range of power system problems, including transient and voltage stability assessment, chaos detection and mitigation, short-term load and renewable energy forecasting, and fault diagnosis. This paper presents a comprehensive review of these applications, covering more than 165 publications spanning from the early demonstrations of chaos in simplified machine models (1990s) to the most recent data-driven and machine-learning-augmented approaches applied to inverter-based resource (IBR)-dominated grids (2024--2026). The review is organized into four principal application domains: (i) stability analysis and real-time monitoring, (ii) chaos characterization and control, (iii) forecasting and predictability analysis, and (iv) protection, fault diagnosis, and condition monitoring. For each domain, we trace the evolution of methods, compare model-based and data-driven LE estimation strategies, identify key benchmarks and validation gaps, and outline the most pressing open research problems.

0.25

Adaptive Model Predictive Control for Damping IBR-Induced SSOs

eess.SY ·2026-11-11 ·Fiaz Hossain, Nilanjan Ray Chaudhuri, Constantino M. Lagoa
similarity 0.56
Abstract

We propose an adaptive model predictive control (MPC) approach to damp sub-synchronous oscillations (SSOs) induced by grid-following (GFL) inverter-based resources (IBRs). Unlike traditional model predictive controller designed considering the nominal plant that may not perform well in other conditions, we use plants that alter with changing operating point. To capture the plant dynamics, we use recursive least squares (RLS) based system identification with variable forgetting factor. This approach allows us to discount past data and avoid bias caused by large transient outliers while performing system identification. We present a proof of the convergence of the model parameters in the presence of finite outliers. We propose to update the model inside the MPC optimization problem periodically after a predetermined time interval instead of each sampling instant since the operating point changes slowly in a practical power system. The MPC design allows us to directly impose constraints on control inputs so that the IBR current limits are respected. Our approach also addresses the issue of unavailability of IBR models. We show the accuracy of the system identification and the superior performance of the proposed controller on the modified IEEE $4$-machine system and the modified IEEE $68$-bus system as compared with the traditional MPC.

0.29

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.55
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16

Blackbox Small-Signal Modeling of Grid-Connected Inverters in Asymmetrical Power Grids

eess.SY ·2026-09-01 ·Airan Frances, Dionisio Ramirez, Javier Uceda
top venuehighly cited similarity 0.55
Abstract · 11 pages, 14 figures, IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 10, OCTOBER 2023

Power electronic converters are envisaged to be key enablers of modern electric power distribution systems. Grid-connected three-phase inverters are widely used in Smart Grids and microgrids, but also in standard grids. They provide controllability and dynamic decoupling capabilities, which are fundamental in the integration of renewable sources and storage systems and in specialized applications such as FACTS. Nevertheless, power electronics-based systems can exhibit dynamic interactions, which may lead to power quality issues. Although the electrical model of each element of these systems is important for their system-level analysis, they are rarely available. Blackbox modeling strategies are useful for obtaining behavioral models of commercial electronic converters. Most blackbox modeling strategies are focused on dc-dc electronic converters; however, some works have extended these concepts to three-phase converters by means of the dq framework, under the assumption of symmetrical and balanced conditions. This work proposes a new structure in the sequence domain to represent the dynamic behavior of grid-connected commercial converters in asymmetrical conditions. Experimental tests have been performed on a three-phase inverter to identify its blackbox model and its performance has been validated during an asymmetric voltage sag.

0.82