CS Paper Radar

Security-Constrained Operation of IBR-Dominated Power Systems: Static and Dynamic Security Across Preventive and Corrective Decisions

Buxin She

eess.SY ·submitted 2026-08-12 21:47 UTC · v1

Abstract

Inverter-based resources (IBRs) couple power system operation to fast dynamics and controller-dependent responses. Their configurable capabilities are reshaping the formulation and coordination of security-constrained operation. This paper presents a two-axis view: static versus dynamic security and preventive versus corrective decision timing. Preventive scheduling is extending from static post-contingency feasibility toward dynamic security, while corrective operation spans equilibrium-based corrective actions and trajectory-based control. A generic formulation represents this change and makes the preventive--corrective tradeoff explicit. Existing formulations, methods, and capability representations are reviewed and synthesized within this framework. The surveyed work yields two findings. First, IBR capability can expand the feasible set or relieve security constraints, reducing operating cost or improving security performance. Second, shared capability and constraints across formulations determine whether that capability remains operationally deliverable. These findings motivate future research in IBR capability characterization and quantification, joint scheduling, and scalable solution frameworks.

Comment
12 pages, 4 figures

Closest papers

Nearest neighbours by meaning across the whole index.

System Strength-Constrained Scheduling with Switchable Grid-Forming and Grid-Following Generation Resources

eess.SY ·2026-09-24 ·Jiaxin Wang, Fei Teng, Huanhai Xin, Jing Dai, Tomislav Capuder +1 more
similarity 0.61
Abstract · 15 pages, 15 figures

Inverter-based resources (IBRs) are increasingly dominating modern power systems, posing significant challenges to cost-effectively maintain system strength for stability. At the same time, the operating behaviors of IBRs are software-defined, including both their steady-state power outputs and control modes, e.g. grid-forming (GFM) and grid-following (GFL). Such flexibility has not been fully explored to efficiently operate future power systems. This paper develops a novel framework that simultaneously optimizes IBR operating behaviors and ensures adequate system strength. A comprehensive solution is provided to integrate system strength constraints into scheduling models, despite their inherent strong non-convexities. We derive a rigorous linear-matrix-inequality (LMI) reformulation of the system strength constraint, effectively addressing non-explicit formulations and dimension variation issues caused by GFM/GFL mode switching of IBRs. Then, we equivalently convert the original non-convex implicit system strength-constrained scheduling problem into an explicit mixed-integer semi-definite programming (MISDP) problem by incorporating the reformulated system strength constraint along with other operational constraints. We further provide a Rayleigh Cut method, which is compatible with standard mixed-integer linear programming (MILP) solvers, to solve this system strength-constrained scheduling problem. Case studies on a modified IEEE 118-bus system and a practical Jiangsu power system demonstrate the performance of the proposed methods.

0.21

Targeted Power System Frequency Attack via the Selection of Maliciously Controlled Inverters

eess.SY ·2026-08-28 ·Xiangyu Zou, Betelihem Ashebo, Daniel K. Molzahn
similarity 0.58
Abstract

This paper studies how an adversary can execute a power system frequency attack by choosing the most effective subset of inverter-based resources (IBRs) as malicious control nodes. During the attack, the adversary controls the attacking devices to destabilize a group of designated target generators. The attack is designed by introducing an unstable oscillatory mode whose eigenvector has large components at the target generators and small components at the compromised IBRs. We formalize the optimal attacker selection problem and present an equivalent mixed-integer quadratically constrained program (MIQCP). To address this combinatorial nonconvex problem, we develop two heuristic algorithms by introducing a ranking metric. The attack process is demonstrated on a modified WSCC 179-bus system, with results verified through nonlinear dynamic simulations. We show that the proposed heuristics find optimal attacking sets in a majority of evaluated scenarios while significantly reducing the required computational time. Scenarios from the ACTIVSg500 system are used to further support our results. Finally, we discuss how selecting different eigenvalues, targets, and numbers of compromised devices impact the attack's severity.

0.21

Convex Inner Approximations for Safe AC Dispatch With Device Dynamics

eess.SY ·2026-10-19 ·Ziqing Zhu
similarity 0.55
Abstract

Safe AC dispatch requires both feasible operating points and enough ramping capability to reach the next target. This paper constructs convex inner approximations that connect nonlinear network feasibility, constrained device response, and dispatch-interval tracking. A fixed-point certificate enforces AC operating limits under bounded load uncertainty. Componentwise response envelopes convert heterogeneous device dynamics into affine conditions on measured states and power references. A command governor then combines these conditions with available ramping capability and a hard terminal-error bound. It selects an admissible target through a minimum-deviation objective and holds the corresponding reference while reserved fast regulation remains active. The resulting quadratic program optimizes controllable references and auxiliary variables. Tests on the IEEE 39- and 118-bus systems include 96 single-target executions and 64 transitions in continuous dispatch sequences at five- and fifteen-minute intervals. All 160 transitions satisfy the AC constraints, independent balancing-generator capability checks, and the prescribed regulation-adjusted terminal accuracy. Complete admission-cycle medians are 3.45 and 8.79 ms. A connected synthetic system with 3,200 buses and 1,000 generating units extends the computational assessment to 999 independent references, with a median cycle time of \LargeMedian{} s. The construction provides a tractable link between available ramping capability and safe, timely execution of AC dispatch.

0.19

Duration-Aware Ramp Adequacy Screening

eess.SY ·2026-09-30 ·Qian Zhang, Aidan Looney, Chao Tian, Xu Andy Sun, Le Xie
benchmark similarity 0.55
Abstract

Ramp products are widely used in regional electricity markets to procure intertemporal flexibility in anticipation of net demand changes. However, the design of such ramp products often lacks a clear specification of ramping duration, potentially leading to infeasible dispatch solutions. This paper develops a duration-aware ramp adequacy screening method that evaluates whether the currently committed and dispatched fleet can meet the anticipated net-demand ramp requirement across different durations. A negative ramp adequacy margin identifies an insufficient-duration set in which the fleet lacks adequate ramp capability. Evaluating this margin across duration supports product-duration selection, while tracking it over time provides a metric for assessing ramp adequacy under different products and dispatch policies. We further formulate rolling-window ramp-reserve procurement with horizon-dependent forecast uncertainty and show that a product can affect ramp capability beyond its designated duration through changes in dispatch positioning. Building on this framework, we develop a forecast-free ramp-reserve scarcity dispatch policy that prioritizes resources according to their remaining ramp-up durations and, in the transmission-unconstrained setting, achieves the same minimum operational security loss as a perfect-foresight benchmark. Studies on a 10-generator system and a 2751-bus synthetic Texas grid demonstrate the value of the proposed framework for early detection of ramp scarcity, product design and evaluation, and screening-guided emergency dispatch.

0.20

AIDC Microgrid Vulnerability Assessment Under Computing-Power Coordinated Attacks

eess.SY ·2026-08-11 ·Ze Yu, Hongwei Zhen, Chao Shen, Mingyang Sun
similarity 0.53
Abstract

The rapid growth of large language model (LLM) services is expanding AI data centers (AIDCs), increasing electricity demand and associated carbon emissions. Renewable energy integration can mitigate these impacts but also strengthens the coupling between AIDC loads and inverter-interfaced generation, creating cross-domain cyber-physical vulnerabilities. Specifically, adversarial AI requests alter AIDC power demand, whereas inverter control tampering modifies source-side dynamics, and their combined impact on system stability varies with generation forecast and demand response uncertainties. To this end, we propose an uncertainty-aware AIDC microgrid vulnerability assessment framework under computing-power coordinated attacks. First, the framework maps adversarial AI requests to AIDC power variations and represents uncertainties in attack-induced demand responses and photovoltaic (PV) forecasts through confidence-weighted realizations. Then, impedance based stability analysis combines these realizations with bounded inverter parameter tampering to construct attack reachable domains and identify critical attack time windows. Furthermore, a separate criterion identifies fixed coordinated attack vectors that retain destabilizing capability throughout each selected window. Case studies demonstrate that, unlike either attack component applied alone, coordinated attacks within identified critical windows induce sustained inverter frequency oscillations with peak absolute deviations exceeding 20% of nominal frequency, whereas the evaluated out-of-window response remains bounded. The proposed method further identifies critical attack windows and the associated coordinated attack vectors.

0.04

Safeguarding Intelligent Power Dispatch:A Performance-Equivalent-Model-Based Safety-Critical Control Method for DC Microgrids

eess.SY ·2026-10-12 ·Shaoliang Zhou, Ziqing Zhu
similarity 0.53
Abstract

Intelligent power dispatch is enabling fast and self-adaptive decision-making in microgrids, yet its deployment in real-world industry remains limited due to unresolved safety concerns. Existing safety-preserving approaches typically rely on an accurate characterization of the feasible operating region, which is impossible to obtain under uncertain and heterogeneous system dynamics. Moreover, even a dispatch command verified as feasible at a discrete setpoint may become unsafe during its continuous physical execution. To address these challenges, this paper proposes a safety-aware dispatch adjustment framework that uses performance-equivalent modeling of closed-loop systems (PEM-CLS) and embeds high-order control barrier functions and control Lyapunov functions within a quadratic programming formulation (HOCBF-CLF-QP). PEM-CLS captures EMS-required power-regulation dynamics solely from port-level responses, without requiring internal subsystem models, parameters, or controller information. Its modeling error is analytically characterized and explicitly bounded, enabling requirement-oriented dynamic abstraction for safety-critical control. Based on these PEMs, the HOCBF-CLF-QP safety controller coordinates heterogeneous transient power responses and corrects unsafe EMS commands to maintain dynamic safety during command execution. Four deliberately constructed extreme stress-test scenarios are used to expose conflicts between nominal EMS commands and physical safety. Without intervention, the DC-bus voltage violates its safety limit in all four cases, whereas the proposed framework maintains QP feasibility and limits the voltage deviation. The results demonstrate that the proposed framework provides an algorithm-agnostic safety execution layer for intelligent power dispatch without requiring an exact feasible-region model or detailed internal information of lower-level devices.

0.51

Decentralized Stability Certificates for Interoperability in Power-Electronics-Dominated Power Systems

eess.SY ·2026-10-19 ·Linbin Huang, Verena Häberle, Ruohan Leng, Huanhai Xin, Hua Geng +2 more
similarity 0.51
Abstract

The rapid integration of power electronics converters has fundamentally altered the power grid's dynamic landscape, making modularity of operation and interoperability of heterogeneous devices two critical hurdles for power system reliability. In control language, these challenges can be paraphrased as decentralized certificates on the input/output behavior of every device, assured by local control, so that stability and guaranteed performance of the interconnected system emerge. For the power system application, such certificates should eventually be part of the rule book, the so-called grid code, and thus be generic and minimally restrictive for the control architecture of each device. Classical system-theoretic angles of attack to these questions go back to dissipativity concepts, which have historically been co-developed in automatic control, circuit theory, and power systems. Since standard dissipativity (e.g., passivity or small gain) criteria fall short in terms of conservatism, a range of more flexible and advanced tools have been developed to assure less conservative decentralized certificates guaranteeing stability under interconnection as well as dynamic performance following a disturbance. In this article, we review a range of methods that have been put forward to tackle these questions, compare and validate them, and point towards practically relevant research gaps which are amenable to control-theoretic approaches. Moreover, we provide a tutorial exposition of practically relevant power systems/electronics issues accessible to control engineers.

0.17

Frequency-Security-Aware Real-Time Economic Dispatch with Data Center UPS Flexibility for Inertia and Primary Frequency Response Services

eess.SY ·2026-11-13 ·Shengyi Wang, Liang Du
hot direction similarity 0.51
Abstract

The increasing penetration of renewable energy and the rapid growth of AI data centers are introducing significant challenges to power system frequency security. There is an urgent need to identify grid-compatible resources capable of providing fast frequency support. This paper proposes a frequency-security-aware real-time economic dispatch (RTED) model that enables data center (DC) uninterruptible power supply (UPS) systems to provide steady-state power balancing, inertia response, and primary frequency response (PFR) services. Specifically, tractable analytical frequency-security constraints are derived and incorporated into the RTED framework through second-order cone programming (SOCP) formulation. The proposed model jointly optimizes energy, reserve, and inertia to minimize system operation cost while preventing under-frequency load shedding (UFLS). Numerical validation on a modified IEEE 39-bus system demonstrates that the proposed RTED model with UPS flexibility can economically support system operation and significantly improve frequency security under active-power deficit disturbances.

0.30