CS Paper Radar

A Hybrid Two-Stage Machine Learning Pipeline for Fault Detection and Classification in Power Transmission Systems

Sahil Manikshete, Atharva Gujarathi, Thanh Long Vu, Akhtar Hussain, Van-Hai Bui

eess.SY cs.LG ·submitted 2026-08-24 18:11 UTC · v1
benchmarktheory

Abstract

Rapid and accurate fault detection in high-voltage transmission networks is essential for grid reliability and equipment protection. Transmission fault datasets are frequently imbalanced, and certain fault types produce electrical signatures that fall within the normal operating envelope, causing single-model classifiers to fail on safety-critical cases. This paper proposes a hybrid two-stage machine learning pipeline that decouples detection from classification. Stage 1 combines an Isolation Forest anomaly detector with an optional supervised binary detector through an OR-fusion rule; the supervised branch is allocated automatically during training for any fault class the anomaly detector cannot resolve, and is omitted when no such class exists. Stage 2 applies a Random Forest multiclass classifier only to samples flagged by Stage 1. Feature engineering is expressed as a per-measurement-point operator mapping six raw channels to eighteen features, including zero-sequence symmetrical components derived from Fortescue's theorem, yielding 18L features for L measurement points. On the TLFaultDataset, the pipeline raises Line-fault end-to-end accuracy from 31.3% to 95.8%. On an independent single-point dataset, the same framework attains 97.25% end-to-end accuracy across all classes including normal operation, exceeding the TLFed federated benchmark of 94.84% without GPU or federated infrastructure, at 0.05 ms per sample on CPU. Ablation on both datasets shows zero-sequence features resolving the three-phase versus three-phase-to-ground ambiguity, raising the F1-score of that class pair from 0.39 to 0.997. The direction of the zero-sequence signature is found to be system-dependent, motivating a learned decision boundary in place of a fixed relay threshold.

Comment
21 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Protection-Oriented Assessment of Machine Learning-Based Fault Detection in Power Systems

cs.LG eess.SP ·2026-11-13 ·Julian Oelhaf, Georg Kordowich, Changhun Kim, Christian Bergler, Andreas Maier +2 more
publishedhot direction similarity 0.68
Abstract · 9 pages, 3 figures, 5 tables. Accepted for oral presentation at the 21st International Conference on Developments in Power System Protection…

Machine learning (ML)-based fault detectors are increasingly proposed for power system protection, yet aggregate metrics can obscure the consequences of false and missed trips. We present a protection-oriented assessment of three ML detectors and a sequence-current reference on PROTECT-90, comprising 9,022 simulated fault episodes on a 90 kV double-circuit line. The assessment combines five window conditions, causal window-end labelling, episode-grouped cross-validation, and operating-point selection under a fixed security budget. It reports security, dependability, detection timing, decision margins, and episode-level nuisance assertions. Gradient-boosted trees, a convolutional neural network, and logistic regression achieve AUC-ROC values above 0.999, yet at a security budget of $10^{-3}$ their developed-fault missed-trip rates range from 0.007% to 1.99%. Post-clearing false-trip rates of approximately 0.12-0.16% per window coexist with nuisance assertions in 11.3-19.1% of episodes. Among the analysed physical descriptors, missed trips are most consistently associated with higher fault resistance within the sampled range. An analytical current proxy suggests a fault-current gradient only partly reproduced by waveform-derived current (rank correlation 0.62). No single topology state or faulted phase consistently dominates within the sampled domain. Because PROTECT-90 contains fault episodes only, security is assessed on pre-fault and post-clearing windows rather than independent non-fault disturbances.

0.27

EvEMTBench: An Open Benchmark for Machine Learning in Power System Protection

eess.SY cs.LG ·2026-09-23 ·Julian Oelhaf, Georg Kordowich, Christian Bergler, Andreas Maier, Johann Jäger +1 more
benchmarkcode/data similarity 0.65
Abstract · 15 pages, 3 figures. Supplementary information included. Code: https://github.com/EvEMTBench/evemtbench-benchmark

Studies of machine-learning-based power system protection are difficult to compare because task definitions, measurement access, data partitions, metrics, and generalization conditions often differ. EvEMTBench addresses this gap with an open, executable, and versioned benchmark that fixes these evaluation choices while leaving model design open. Across four grids spanning 20-345 kV, it defines 12 protection and event-analysis functions instantiated as 24 scored tasks and supports structured evaluation across observability conditions, predefined distribution shifts, and zero-shot and fine-tuned cross-grid transfer. Committed partitions, leakage controls, and reproducible reporting provide a common basis for comparing future methods. A reference evaluation spanning trivial, conventional, feature-based, and deep-learning baselines shows that wider observability is not uniformly beneficial, shifted conditions can reveal failures not apparent in-distribution, and cross-grid transfer is substantially stronger for fault detection than for fault localization. Protection-relevant diagnostics identify failure modes not apparent from primary metrics alone. EvEMTBench therefore makes generalization in machine-learning-based protection an explicit and reproducible evaluation problem.

0.22

A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids

cs.LG eess.SP ·2026-09-15 ·Julian Oelhaf, Georg Kordowich, Paula Andrea Pérez-Toro, Tomás Arias-Vergara, Andreas Maier +2 more
publishedhighly cited similarity 0.65
Abstract · Accepted at ICASSP 2025. 5 pages, 4 figures. Published version: DOI 10.1109/ICASSP49660.2025.10890544

The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery mechanisms. Traditional relay protection systems, which operate based on static rules and predefined thresholds, are inadequate for addressing these challenges, particularly in detecting and isolating faults such as short circuits. Consequently, the conventional methodologies applied to electrical network protection frequently fail to achieve optimal performance in fault detection, especially in terms of adherence to safety standards and the selective limitation of damage. Recent research indicates that machine learning (ML)-based approaches can effectively tackle these issues; however, variations in grid configurations and analysis windows have impeded consistent comparative assessments. In this study, we assess the efficacy of various ML models in detecting electrical faults and pinpointing defective transmission lines within a 10 ms measurement interval - a critical time-frame for real-time operational viability, for the first time. The most effective model attained an F1 score of 0.991 +/- 0.018 and demonstrated a processing time of 0.342ms +/- 0.509ms.

0.52

Multi-Library Feature Engineering and Statistically Validated Classification for Power Swing Detection and Stability Assessment

eess.SP cs.LG ·2026-11-16 ·Pallav Kumar Bera, Samita Rani Pani, Ranjeeta Patel
published similarity 0.65
Abstract · Accepted at Annual Conference of the IEEE Industrial Electronics Society (IECON) 2026; 52nd Edition; Doha, Qatar

Faults occurring during power swings, and the evolution of a swing into an unstable condition, cause distance-relay maloperation and cascaded outages. This paper identifies faults, faults during power swings, and power swings, and distinguishes stable from unstable swings in a 9-bus WSCC system modeled in PSCAD/EMTDC. Three time-series feature libraries (tsfresh, TSFEL, and tsfeatures) are applied to the 3-phase relay voltages and currents, giving 3286 statistical, temporal, spectral, and fractal descriptors per event window. A two-step feature selection (Boruta all-relevant filtering followed by RFECV- and SHAP-guided minimal-optimal pruning) reduces the feature set to 18 compact, non-redundant features. 14 classifiers spanning linear, kernel/instance-based, probabilistic, neural, and tree-ensemble/boosting families are then benchmarked under repeated stratified cross-validation, with model differences assessed by a Friedman/Nemenyi omnibus-and-post-hoc test and a Nadeau--Bengio corrected paired t-test. Rotation Forest (ROF) identifies the three event types with 99.98% and SVM-RBF distinguishes stable from unstable swings with 97.97% balanced accuracy. The results show that automated, library-driven feature extraction combined with rigorous statistical model comparison achieves near-perfect discrimination while retaining feature-level interpretability through SHAP importance.

0.28

Data-Optimized Contingency Screening: A Machine Learning Approach to Power System Security

cs.AI cs.LG ·2026-09-03 ·Joshua Salako, Folajimi Osikomaiya, Olakorede Olamiju
published similarity 0.61
Abstract · Accepted for presentation at the 3rd EIE International Conference on Computing, Networking, Robotics and Telecommunication (EIECon), 2025. T…

Ensuring the security of the power system is essential for stability and reliability, especially in the event of disruption. Effective classification of contingency in power systems enables proactive decision-making and mitigates large-scale breakdowns and failures. This study explores the use of machine learning algorithms to classify security levels of contingencies in power systems into safe, moderate or severe classes. For this approach, Newton-Raphson load flow method extracts system data from contingency scenarios, using Overall Performance Index (OPI) as safety measure. For data pre-processing, Synthetic Minority Over-Sampling Technique (SMOTE) and Principal Component Analysis (PCA) is used to address class imbalance and reduce dimensionality, respectively. K-Nearest Neighbours (KNN), Random Forest (RF) and Support Vector Machines (SVM) is trained and evaluated on datasets generated through N-k contingency scenarios for k equal 1, 2, and 3 on IEEE-14 and IEEE-30 bus systems using four hybrid pre-processing configurations: normalized, SMOTE-balanced, PCA-transformed, and a combined SMOTE PCA-transformed. Performance is assessed by precision, recall and F1 score, with priority given to the severe contingency classes. The RF achieved the highest F1 scores of 0.97 in IEEE-30 and 0.86 in IEEE-14, SVM benefits significantly from PCA and improves the accuracy of the classification, while KNN is best suited for SMOTE and PCA conversion. The findings show that PCA contributes more than SMOTE to the overall performance of the model. However, SMOTE improves recall but can introduce false positives and is therefore a compromise of accuracy. This study highlights machine learning as a scalable and powerful alternative to traditional contingency analysis, which improves the assessment of security in real time.

0.25

Characterizing Cross-Relay Generalization Failure in Machine Learning-Based Power System Protection

cs.LG ·2026-10-20 ·Nithin Pradeep Nadayil Kizhakkethil, Julian Oelhaf, Christian Bergler, Andreas Maier, Siming Bayer
published similarity 0.61
Abstract · 6 pages, 3 figures. Accepted for presentation at the IEEE Power & Energy Student Summit (PESS 2026), Karlsruhe, Germany

Machine learning-based fault detectors are often evaluated at the relay locations used for training, although local voltage and current measurements vary across power networks. This work investigates cross-relay generalization for binary detection of faults anywhere in the network using local measurements, rather than line-selective tripping. Using 50 ms windows from a simulated 110 kV transmission network, we evaluate a multilayer perceptron across all 64 source target combinations of eight relays and five random seeds. A shared simulation-level split and source-only threshold selection provide a controlled held-out evaluation without target-specific calibration. Despite nearly unchanged mean F1-scores (0.730 within-relay versus 0.734 cross-relay), the mean false-positive rate (FPR) increases from 0.088 to 0.341, while the mean false-negative rate decreases from 0.399 to 0.318. The change is strongly directional: models trained at Bus 2 relays yield a mean FPR of 0.670 at Bus 1 and Bus 3 relays, compared with 0.096 for cross-relay transfers within the same bus group. Linear probing indicates that learned representations retain coarse bus-group information, while exploratory class-conditional latent distribution analysis shows no consistent monotonic association with transfer errors. These findings demonstrate that aggregate metrics can conceal location-structured changes in false-alarm behavior, highlighting the importance of evaluating error types separately when assessing cross-relay generalization.

0.23

A simulation based dataset of faults and events for machine learning in power systems

eess.SY ·2026-08-20 ·Georg Kordowich, Jonathan Loebel, Julian Oelhaf, Andreas Maier, Siming Bayer +2 more
similarity 0.60
Abstract

The integration of inverter-based renewable energy sources into electric grids challenges conventional power system protection. Machine learning-based solutions can address these challenges by utilizing available data in modern smart grids. However, the lack of open datasets prevents reproducibility and fair comparisons between different approaches and their results, which hinders further progress. Therefore, this paper presents EvEMTBench, a synthetic dataset of faults and events generated using electromagnetic transient simulations. The physical plausibility of the power system simulation is ensured by validating the simulation parameters against established literature and providing comprehensive documentation of the simulation procedure. The dataset is designed for training, fine-tuning, and benchmarking machine learning models by providing synchronized point-on-wave voltage and current measurements at 9600 Hz across a diverse set of topologies and voltage levels. The inclusion of a wide range of fault and operating events allows the utilization of EvEMTBench for different tasks like incipient fault detection, fault localization, or event detection.

0.50

Interpretable statistical feature engineering for early disruption prediction in the short pulse ADITYA tokamak

cs.LG physics.plasm-phphysics.data-an ·2026-08-23 ·Jyoti Agarwal, Kavit Patel, Bhaskar Chaudhury, Abhishek Sharma, Shrichand Jakhar +1 more
similarity 0.60
Abstract · 27 pages

Reliable early disruption prediction is critical for the safe operation and real-time control of tokamaks. However, machine learning based prediction frameworks have predominantly targeted medium and long pulse devices, with comparatively limited attention given to short pulse tokamaks where available warning time is inherently constrained. In this work, an interpretable machine learning framework is developed for feature engineering and early prediction of disruptions in the ADITYA using the initial plasma evolution information, prior to the activation of the negative converter of the ohmic transformer power supply. Statistical descriptors comprising the mean, variance, skewness, kurtosis and wavelet energy entropy are extracted from routinely available plasma diagnostics over different operation time windows. Decision tree based feature selection is employed to identify physically meaningful disruption precursors and to reduce feature dimensionality. These selected features are used to train a random forest classifier. The proposed framework achieves stable predictive performance across different analysis windows, with a maximum ROC-AUC of 0.87 for 0-35 ms and 0-40 ms windows. Comparable and in some cases improved, performance is obtained using the reduced feature set, demonstrating that the selected statistical descriptors retain the essential information required for disruption prediction. The proposed methodology provides an interpretable and computationally efficient framework for real time disruption prediction in short pulse tokamaks and establishes that carefully engineered statistical descriptors can effectively replace raw time series inputs for early disruption prediction, thereby offering a practical pathway toward real time plasma control in short pulse tokamaks similar to ADITYA and ADITYA-U.

0.29