UNION: A Unified AC-OPF Framework for Topology-Varying Real-Time Grid Operation

Kyungnam Park, Keunju Song, Yeji Lim, Suho Park, Kibaek Kim, Hongseok Kim

eess.SY ·submitted 2026-08-26 13:32 UTC · v1

Abstract

Secure real-time grid operation requires fast AC optimal power flow (AC-OPF) tools that stay accurate and feasible as operating conditions and topology change. Learning-based methods have advanced, but most are trained per system or per topology, and delivering an operating point that satisfies every operational limit remains challenging. This paper proposes UNION, a unified graph-based AC-OPF framework for heterogeneous systems and topology-varying operation. UNION proposes a shared graph encoder, a scalar-gated aggregation with explicit consensus correction, and a sparse-aware differentiable implicit layer embedding the AC power-flow equations. The remaining inequalities are handled by primal-dual training and the deterministic restoration layer. A single model trained jointly across seven systems, including a real-world 4,492-bus Korean transmission grid, attains a 1.23% mean objective gap and satisfies every operational limit on 99.56% of test instances. It sustains this under zero-shot $N-1$ contingencies, i.e., line and generator outages, and over five days of time-varying Korean topologies; it retains full snapshot coverage at a 2.51% gap under lightweight online fine-tuning. UNION pre-restoration inference takes 55$-$58 ms per instance on the three largest systems, and 108$-$114 ms including restoration. These results indicate that one jointly trained, physics-consistent model can support real-time AC-OPF across heterogeneous systems and evolving topologies.

Comment
10 pages, 2 figures

Closest papers

Nearest neighbours by meaning across the whole index.

GridSFM: A Foundation Model for Solving AC Optimal Power Flow

eess.SY cs.LGmath.OC ·2026-09-24 ·Luke Bhan, Weiwei Yang, Margaret Capetz, Baosen Zhang
theory similarity 0.66
Abstract · 19 pages

We introduce GridSFM, a framework that combines a pretrained foundation model across grid topologies with physics-informed fine-tuning for solving AC Optimal Power Flow (AC-OPF) at scale. It is a $15$ million parameter physics-inspired graph neural network pretrained across $54$ topologies of $500$ to $4{,}000$ buses. Our model attains a $2.45\%$ zero-shot generation-cost error on a $10{,}000$ bus case held-out operating conditions with no degradation as system size grows. Building on this, we pair the pretrained backbone with a physics-informed fine-tuning design based on Newton's method for power flow. With only $100$ solved instances, GridSFM adapts to unseen grids up to $10{,}000$ buses. We show it out performs single topology, dedicated neural network models that are trained more data, both in terms of cost and solver iterations when deployed as warm starting points. In designing this foundation model, we overcome the fact that the feasible set for AC-OPF can be disconnected. This is an obstruction that prevents any continuous neural network from approximating the solution map. To do so, we lift the problem and relax its constraints with logarithmically penalized slacks. We prove that the resulting elastic feasible set is contractible, that the AC-OPF minimizers remain minimizers of the elastic problem above an explicit penalty threshold, and that projecting an approximate solution back onto the AC-OPF feasible set is well posed. We release all models, data, and code so that the community can build on a shared starting point for AC-OPF.

0.40

Unified Heterogeneous Graph Neural Network solver for Power Flow, Optimal Power Flow and State Estimation

eess.SY cs.LG ·2026-09-15 ·Ferran Bohigas-Daranas, Hamid Latif-Martínez, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt, Pere Barlet-Ros
similarity 0.64
Abstract

Power Flow (PF), Optimal Power Flow (OPF), and State Estimation (SE) are fundamental problems in power system analysis, but solving them is computationally expensive. Graph Neural Networks (GNNs) have been proposed as fast surrogates, yet existing solvers are trained for a single problem at a time, producing narrow models that must be rebuilt for each new task. We propose a more general approach: a single Heterogeneous Residual Gated Graph Convolutional Network that solves all three problems with one shared backbone. Rather than learning one mapping, the model learns a reusable representation of how the network behaves, from which PF, OPF, and SE can each be estimated. Trained jointly on the three problems across diverse topologies and loading conditions, and evaluated on the IEEE 14-bus and 118-bus systems, the shared model matches the accuracy of task-specific GNN solvers and stays robust on unseen loading levels and topologies. These results show that a single model can capture the basic operation of a power network and serve several analysis tasks at once, a first step toward a foundation model for power systems.

0.11

GENCO - A Unified Neural Solver Embedded in a Development Framework for Steady-State Grid Analysis

cs.AI ·2026-08-10 ·Alban Puech, Matteo Mazzonelli, Tamara R. Govindasamy, Mangaliso Mngomezulu, Héctor Maeso-García +17 more
code/datahighly cited similarity 0.61
Abstract

Foundation models are transforming business workflows and boosting productivity, yet they remain largely absent from engineering domains such as power system analysis, where strict physical consistency must be enforced. We present GENCO (GEometric Neural Corrective Optimizer), a unified neural solver for steady-state transmission grid analysis that handles power flow (PF), optimal power flow (OPF), and state estimation (SE) within a single architecture and shared grid representation. To support advances in neural power system solvers, we introduce the open-source GridFM Development Framework, which standardizes synthetic data generation and training in a low-code environment. We also release large-scale datasets with millions of PF and OPF scenarios across diverse grid topologies to support reproducible benchmarking. We evaluate GENCO on the PFDelta and OPFData benchmarks against state-of-the-art neural solvers and classical solvers, including Newton-Raphson and IPOPT, as well as on real-world Hydro-Québec SCADA data. For large-scale PF, GENCO recovers the full AC operating state, including voltage magnitudes and reactive power that DC-PF cannot provide, while matching DC-PF-level active power-balance residuals. It achieves up to 30x speedups over Newton-Raphson at only 2x the runtime of DC-PF. For OPF, it achieves up to 85x speedups over IPOPT while improving feasibility, optimality, and runtime over DC-OPF. For SE, GENCO is more robust than classical weighted least squares to noisy measurements and grid parameter errors, and always returns a high-quality estimate even when weighted least squares fails to converge. Together, the unified architecture and development framework provide a new approach to large-scale steady-state grid analysis, lowering the barrier to entry for power system engineers and marking a step toward Grid Foundation Models.

0.60

Benchmarking a Grid Foundation Model for AC Optimal Power Flow: Feasibility and Warm-Start Results on Synthetic Texas and South Carolina Grids

eess.SY ·2026-11-17 ·Tam Kemabonta, Brighton Ombuki, Vladimir Abdelnour
similarity 0.61
Abstract · 5 pages, 3 figures, 2 tables. Submitted to the 2027 IEEE PES General Meeting

Learning-based surrogates for alternating-current optimal power flow (AC-OPF) are often judged by the gap between their objective value and that of a nonlinear solver, which does not show that a prediction satisfies power balance and network limits. This paper tests whether predictions from the pretrained foundation model GridSFM-Open 1.1.0, recently released by Microsoft, are feasible AC-OPF operating points and whether they are useful initial values for a nonlinear solver. The model was evaluated zero-shot and after fine-tuning on 10, 100, and 1,000 labeled scenarios (FT10, FT100, and FT1000) on 500 scenarios for each of two synthetic grids, ACTIVSg2000 (Texas) and ACTIVSg500 (South Carolina), with Ipopt, MATPOWER MIPS, and pandapower PIPS as solver references. The lowest Texas median cost gap, 0.44\% for FT100, coincided with thermal violations in 24.1\% of cases and a median maximum bus power mismatch of 89 MW and 197 Mvar. Texas zero-shot predictions had a median maximum mismatch of 648 MW and 1,641 Mvar, and every South Carolina case violated a thermal limit for every model variant. Seeding Ipopt with FT1000 predictions gave geometric-mean solve-time speedups of 1.55x on South Carolina and 1.12x on Texas (p = 0.06, not significant at the 5\% level), while zero-shot seeds slowed South Carolina solves (0.26x). A small objective gap therefore did not indicate feasibility: although median zero-shot inference took only 1.32 s on Texas and 0.157 s on South Carolina on a shared host, every prediction still required a nonlinear solver, and fine-tuned predictions gave modest, grid-dependent warm-start speedups while zero-shot predictions slowed convergence on one grid. GridSFM may therefore be useful for initializing a nonlinear solver, but obtaining feasible AC-OPF solutions still required the solver.

0.36

Graph Machine Learning: An Opportunity for Power Systems

cs.LG cs.AIcs.CEeess.SY ·2026-08-17 ·Martin Sadric, Sebastian Pütz, Christian Nauck, Veit Hagenmeyer, Frank Hellmann +2 more
surveybenchmark similarity 0.61
Abstract

Modern power systems face growing operational complexity driven by the integration of renewable energy sources, decentralization, and the need for real-time decision-making across a wide range of timescales. Addressing these challenges traditionally relies on model-based methods that, while accurate, can be too slow for operational demands. Machine learning (ML) has therefore emerged as a faster, data-driven alternative. As grid topology plays a central role in power system operation, graph machine learning (GML) methods offer a natural framework for incorporating topological dependencies as an inductive bias. We survey nearly 800 papers at the intersection of GML and power systems, covering forecasting, state estimation, optimization, control, fault diagnosis, and cybersecurity. Power systems constitute an unusually rich benchmark setting for GML, as they combine hard physical constraints, multi-scale dynamics, safety-critical requirements, and scarce labeled data within a single, well-defined domain. Conversely, power systems can benefit from utilizing GML to complement classical solvers, as GML provide scalable, topology-aware approximations with promising generalization and computational efficiency. We identify open challenges, including limited real-world deployment and the need for interpretable models in safety-critical settings. Despite the rapidly growing number of publications, standardized benchmarks and open datasets remain scarce, leaving many results difficult to reproduce and undermining the long-term scientific credibility of the field. We further derive a structured requirements catalog for ML-ready power grid benchmarks, intended to guide future dataset development and improve reproducibility across studies. We call on the community to prioritize dedicated benchmark studies and the release of open datasets and models.

0.23

Benchmarking Graph Neural Networks for AC Power Flow: The Role of Inductive Biases and Physical Constraints

cs.LG cs.AI ·2026-10-28 ·Federico Clerici, Ferran Bohigas-Daranas, Hamid Latif-Martínez, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt +1 more
benchmark similarity 0.61
Abstract

Fast and accurate models for AC power flow (ACPF) are increasingly important as modern electrical grids require more frequent system analyses. Graph neural networks (GNNs) naturally exploit electrical grid topology, yet the effects of architectural design choices on predictive performance remain poorly understood given differences in graph representations and evaluation settings across studies. We present a unified benchmark of representative GNN architectures for ACPF prediction under a common experimental framework. All models use identical preprocessing and training procedures and comparable parameter budgets, isolating the impact of message-passing mechanisms and inductive biases. We also analyze errors by distance from the slack bus and systematically ablate key design components. We evaluate predictive accuracy and physical consistency on the IEEE 14-bus and IEEE 118-bus systems. Results indicate that anisotropic message-passing architectures offer the most favorable trade-off between predictive accuracy and physical consistency under the studied parameter and topology constraints. Explicit edge features encoding line impedances and global context aggregation are particularly important for representing electrical interactions and system-wide dependencies, especially for voltage-angle predictions on the topologically bottlenecked IEEE-118 grid. Under a budget with approximately fixed parameters, two or three message-passing layers generally provide the best balance between depth and representation width, while additional depth offers no consistent improvement. Ablations also show that standard residual and root connections are not necessarily beneficial in shallow models, and that aggregation operators involve trade-offs between statistical accuracy and physical consistency. These results provide practical guidelines for designing graph-based power system models.

0.17

Scalable Self-Supervised Learning for Multiphase AC-OPF in Distribution Systems with Topology Reconfiguration

eess.SY cs.LGmath.OC ·2026-08-25 ·Hoang T. Nguyen, Shaohui Liu, Reetam Sen Biswas, Varsha Pendyala, Nurali Virani +2 more
similarity 0.60
Abstract · Source code will be published following the review process

The proliferation of distributed energy resources (DERs) in distribution grids enables the active coordination of these assets to reduce costs and enable cleaner operations. Realizing this potential requires solving multiphase AC optimal power flow (AC-OPF) quickly across varying loads, DER availabilities, and topology reconfigurations, at much greater speed and scale than conventional nonlinear solvers. Learning-based surrogates can offer millisecond inference, yet existing methods target largely balanced transmission systems and do not scale to the multiphase, unbalanced, and reconfigurable nature of distribution feeders at utility scale. We present the Penalty + Sequential Linearized Feasibility Seeking (SLFS) algorithm, a self-supervised learning framework for multiphase distribution AC-OPF under switch-induced topology changes. Penalty+SLFS requires no labeled optimal solutions and trains directly from the AC-OPF objective and constraints through a differentiable fixed-point power flow solver, avoiding expensive label generation and admitting robust training procedures. Topology changes are handled efficiently using Sherman-Morrison-Woodbury updates of the admittance-matrix inverse, while an M-step Jacobian approximation accelerates differentiation through the power flow solver. At inference, SLFS repairs any infeasible predictions, providing feasibility guarantees with low computational overhead. On IEEE feeders ranging from 13 to 8,500 nodes, Penalty+SLFS achieves negligible optimality gaps and near-zero constraint violations, delivers up to three orders of magnitude speedups over IPOPT, and remains robust under large distributional shifts, demonstrating a viable path toward real-time, topology-aware AC-OPF for large-scale distribution grids.

0.23

Improving Learned AC-OPF Feasibility under Distribution Shift with PF-in-the-Loop Correction

eess.SY ·2026-10-26 ·Afia Afrin, Omid Ardakanian
similarity 0.60
Abstract

Learning-based AC-OPF enables fast dispatch, yet its feasibility can degrade under distribution shift. We analyze three state-of-the-art methods and identify a shared deployment-time limitation: none use feedback from the power-flow (PF)-realized state to ensure feasibility of the predicted control. Using a simple PF-in-the-loop feasibility restoration filter, we empirically show that such feedback substantially improves hard feasibility across four out-of-distribution scenarios with modest runtime overhead.

0.25