Quantifying Grid-Forming Requirements for System Strength: How Much and Where?

Ambuj Gupta, Balarko Chaudhuri, Mark O'Malley

eess.SY ·submitted 2026-10-06 18:14 UTC · v1

Abstract

As power systems transition toward inverter-based resource (IBR)-dominated grids, Grid-ForMing (GFM) IBRs are increasingly expected to provide the voltage-source characteristics required to maintain adequate system strength. However, how many GFM IBRs are required, and where they should be located in the grid, remains unclear. This paper investigates the impact of the number and location of GFM IBRs on small-signal system strength. The Jacobian Voltage Stiffness Metric (JVSM), which quantifies the voltage-magnitude and voltage-phase stiffness from frequency-domain Jacobian characteristics, is used as a system-strength measure. The analysis demonstrates that increasing the number of GFM IBRs generally improves system strength; however, configurations with the same number of GFM IBRs can exhibit significantly different bus-wise system-strength characteristics depending on their locations. Thus, this paper provides a quantitative basis for specifying GFM requirements in terms of the resulting system strength, rather than solely in terms of penetration level or the number of GFM IBRs. Case studies on a modified IEEE 39-bus system demonstrate how JVSM can be used to quantify and compare the system-strength impact of different numbers and locations of GFM IBRs, with the resulting strength assessments validated against small-signal oscillatory stability.

Comment
25th Wind & Solar Integration Workshop, Porto, Portugal, 29 September - 02 October 2026

Closest papers

Nearest neighbours by meaning across the whole index.

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.65
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.29

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.63
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.36

Evaluating Grid Strength with Rising Penetration of Inverter Based Resources

eess.SY ·2026-09-22 ·Mohammed N. Khamees, Gad Ilunga, Zhongxia Zhang, Richard E. Tuck
published similarity 0.63
Abstract · Accepted for publication in 2026 CIGRE USNC Grid of the Future (GOTF) Symposium

Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet been established. This paper presents methodologies for assessing system strength across the DEV network and identifying regions that may be vulnerable to such disturbances. To this end, three grid-strength metrics are evaluated: the Simple Short-Circuit Ratio (SSCR), the Weighted Short-Circuit Ratio (WSCR), and the Composite Short-Circuit Ratio (CSCR). Historical event data will be analyzed using steady-state snapshots from DEV's proprietary Analysis on Demand (ANODE) platform, which provides 10-minute interval load-flow data. These snapshots will be processed using a developed software tool to compute system strength metrics. The analysis will investigate potential correlations between system strength and observed disturbances. Where such correlations are identified, the study will further evaluate the impact of deploying synchronous condensers (SynCons) as a mitigation strategy.

0.31

Dynamic droop specifications for Grid-Forming Inverter-Based Resources

eess.SY ·2026-08-26 ·Jennifer T. Bui, Dominic Groß, Deepak Ramasubramanian
similarity 0.62
Abstract

The large-scale retirement of synchronous generators requires additional capabilities from inverter-based resources (IBRs) to ensure the stability and reliability of power grids. With the heterogeneous controls of IBRs, it is especially important to understand their behavior on the grid. This work proposes a simple data-enabled dynamic model to capture the small-signal dynamics of IBRs and formulate specifications for grid-forming (GFM) IBRs. The dynamic droop model is complementary to well-studied impedance models and extends the common definition of steady-state droop coefficients to dynamic droop coefficients that fully characterize the IBR small-signal response below the nominal line frequency (e.g., subsynchronous oscillations). We propose bounds on the gain and phase of the dynamic droop coefficients to encode minimum requirements for GFM IBRs to promote interoperability and minimize adverse interactions. The resulting specifications also provide some insights into the much-debated question of how to certify an IBR as GFM. Moreover, we also provide dynamic droop specifications for frequency control ancillary services that, e.g., clarify and generalize the notion of an IBR inertia response. Finally, common grid-following (GFL) and GFM controls as well as original equipment manufacturer (OEM) models are used to illustrate the results and showcase the use of dynamic droop coefficients as a tool to screen IBR dynamics for potential adverse interactions.

0.26

Spatial Differences Analysis of Nodal Frequency Considering Frequency-Voltage Coupling

eess.SY ·2026-11-04 ·Xiaodan Li, Donghai Zhu, Zining Liu, Zhu Guo, Jiabing Hu +1 more
similarity 0.60
Abstract

The rising penetration of inverter-based resources (IBRs) brings rich control dynamics that can amplify spatial differences in nodal frequency through frequency-voltage (F-V) coupling. Existing analyses often neglect voltage dynamics or only examine the aggregate frequency, leading to overoptimistic evaluation of frequency security. To address these drawbacks, this paper develops a unified model of synchronous generators (SGs), grid-following (GFL)-IBRs, and grid-forming (GFM)-IBRs based on the magnitude and phase dynamics of equivalent internal electromotive force (EMF). Integrating these source models with network equations yields a sparse implicit closed-loop model, which fully captures the device-network F-V coupling without transfer-matrix inversion. Then, the obtained nodal responses are decomposed into common and differential modes. Using this decomposition, coupling indices and pole-residue analysis reveal how F-V coupling can amplify spatial differences in nodal frequency and how source configuration and parameters modify this effect. Finally, case studies on the modified IEEE 39-bus and 118-bus test systems validate the proposed model and demonstrate its computational efficiency.

0.19

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.57
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.56
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.55
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16