Evaluating Grid Strength with Rising Penetration of Inverter Based Resources

Mohammed N. Khamees, Gad Ilunga, Zhongxia Zhang, Richard E. Tuck

eess.SY ·submitted 2026-09-22 21:03 UTC · v1
published

Abstract

Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet been established. This paper presents methodologies for assessing system strength across the DEV network and identifying regions that may be vulnerable to such disturbances. To this end, three grid-strength metrics are evaluated: the Simple Short-Circuit Ratio (SSCR), the Weighted Short-Circuit Ratio (WSCR), and the Composite Short-Circuit Ratio (CSCR). Historical event data will be analyzed using steady-state snapshots from DEV's proprietary Analysis on Demand (ANODE) platform, which provides 10-minute interval load-flow data. These snapshots will be processed using a developed software tool to compute system strength metrics. The analysis will investigate potential correlations between system strength and observed disturbances. Where such correlations are identified, the study will further evaluate the impact of deploying synchronous condensers (SynCons) as a mitigation strategy.

Comment
Accepted for publication in 2026 CIGRE USNC Grid of the Future (GOTF) Symposium

Closest papers

Nearest neighbours by meaning across the whole index.

Quantifying Grid-Forming Requirements for System Strength: How Much and Where?

eess.SY ·2026-10-06 ·Ambuj Gupta, Balarko Chaudhuri, Mark O'Malley
similarity 0.63
Abstract · 25th Wind & Solar Integration Workshop, Porto, Portugal, 29 September - 02 October 2026

As power systems transition toward inverter-based resource (IBR)-dominated grids, Grid-ForMing (GFM) IBRs are increasingly expected to provide the voltage-source characteristics required to maintain adequate system strength. However, how many GFM IBRs are required, and where they should be located in the grid, remains unclear. This paper investigates the impact of the number and location of GFM IBRs on small-signal system strength. The Jacobian Voltage Stiffness Metric (JVSM), which quantifies the voltage-magnitude and voltage-phase stiffness from frequency-domain Jacobian characteristics, is used as a system-strength measure. The analysis demonstrates that increasing the number of GFM IBRs generally improves system strength; however, configurations with the same number of GFM IBRs can exhibit significantly different bus-wise system-strength characteristics depending on their locations. Thus, this paper provides a quantitative basis for specifying GFM requirements in terms of the resulting system strength, rather than solely in terms of penetration level or the number of GFM IBRs. Case studies on a modified IEEE 39-bus system demonstrate how JVSM can be used to quantify and compare the system-strength impact of different numbers and locations of GFM IBRs, with the resulting strength assessments validated against small-signal oscillatory stability.

0.20

Data Center Load Reductions: Attribution, Measurement Limits, and Estimation

eess.SY ·2026-10-28 ·Abdallah Alalem Albustami, Ahmad F. Taha, Mohammad Alwahdanee, Zuhaib Shakeel Muhammad
similarity 0.60
Abstract

Hundreds of gigawatts of data center loads are seeking interconnection in the United States given the massive growth of artificial intelligence and cloud computing. In recent years, several incidents of data centers reducing their loads by hundreds to thousands of megawatts have been documented, raising grid reliability concerns. U.S. regulators have since ordered reliability standards for the integration of computational loads, and the North American Electric Reliability Corporation (NERC) now calls on transmission owners to install disturbance recorders at these facilities to support root cause analysis. Such recorders usually observe only electrical quantities at the point of interconnection (POI). A sudden load reduction can be caused by a change in workload or a switch to backup supply. This work shows when POI measurements can distinguish the two mechanisms. It is established that they can produce identical POI voltage and current in a quasi-static constant power model, and during the transient their separation depends on the reduction relative to measurement noise, the clearing time, the dynamics through which workload reaches the POI, and the recorder bandwidth. When POI data are insufficient, an estimator that uses workload data is proposed to determine how much of the facility stayed connected. The results of this work identify the measurements and grid information utilities need to determine why data center load dropped.

0.31

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.59
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

eess.SY ·2026-09-10 ·Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti
similarity 0.59
Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

0.28

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.58
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.28

Cascading Contingency Analysis of Modern Power Systems Using a Stochastic Hybrid Systems Framework

eess.SY eess.SP ·2026-11-10 ·Masoud H. Nazari, Hamid Varmazyari
published similarity 0.57
Abstract · This paper was accepted at the 2026 North American Power Symposium (NAPS)

This paper presents a cascading contingency analysis and risk assessment framework that incorporates probabilistic mode transitions motivated by stochastic hybrid system (SHS) concepts together with power-flow-based stress evaluation. A two-stage modeling approach is adopted in which sensitivity-based analysis is first used to identify candidate cascading transitions, followed by DC power flow re-evaluation to accurately capture post-contingency stress redistribution, islanding behavior, and load shedding. A probabilistic propagation model is constructed using mode-dependent transition probabilities derived from line loading conditions. A Cascading Risk Index (CRI) is introduced to quantify the expected load shedding accumulated over cascade progression. Case studies on the IEEE 39-bus system demonstrate that the proposed framework captures diverse cascading routes under multiple initiating outages and identifies critical propagation patterns that are not revealed by N-1/N-2 screening. The results highlight the importance of SHS modeling in assessing cascading risk and providing a scalable framework for resilience evaluation in modern power systems.

0.34

Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

eess.SY ·2026-11-02 ·Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid +1 more
published similarity 0.57
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

0.49

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.57
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16