Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti

eess.SY ·submitted 2026-09-10 11:33 UTC · v1

Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

Closest papers

Nearest neighbours by meaning across the whole index.

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.71
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.62
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.28

Spatial Differences Analysis of Nodal Frequency Considering Frequency-Voltage Coupling

eess.SY ·2026-11-04 ·Xiaodan Li, Donghai Zhu, Zining Liu, Zhu Guo, Jiabing Hu +1 more
similarity 0.62
Abstract

The rising penetration of inverter-based resources (IBRs) brings rich control dynamics that can amplify spatial differences in nodal frequency through frequency-voltage (F-V) coupling. Existing analyses often neglect voltage dynamics or only examine the aggregate frequency, leading to overoptimistic evaluation of frequency security. To address these drawbacks, this paper develops a unified model of synchronous generators (SGs), grid-following (GFL)-IBRs, and grid-forming (GFM)-IBRs based on the magnitude and phase dynamics of equivalent internal electromotive force (EMF). Integrating these source models with network equations yields a sparse implicit closed-loop model, which fully captures the device-network F-V coupling without transfer-matrix inversion. Then, the obtained nodal responses are decomposed into common and differential modes. Using this decomposition, coupling indices and pole-residue analysis reveal how F-V coupling can amplify spatial differences in nodal frequency and how source configuration and parameters modify this effect. Finally, case studies on the modified IEEE 39-bus and 118-bus test systems validate the proposed model and demonstrate its computational efficiency.

0.19

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.61
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.60
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.60
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Transferable Neuromorphic Protection for Distribution Networks

eess.SP ·2026-11-12 ·Saurabh Prabhakar, Yubo Song, Pascal Schirmer, Bijaya Ketan Panigrahi, Subham Sahoo
benchmark similarity 0.60
Abstract · Submitted to IEEE Transactions on Smart Grid

Protection of converter-dominated distribution networks is challenging due to limited fault currents, operating-mode transitions, bidirectional power flow, and heterogeneous network configurations. This paper proposes a scale-invariant neuromorphic protection framework to enable transferable protection decisions across such networks. The framework integrates asset-based normalization, multi-domain disturbance representation, event-driven spike encoding, leaky integrate-and-fire (LIF) dynamics, adaptive threshold regulation, and directional supervision within a unified mathematical formulation. Local voltage, current, active power, and reactive power measurements are transformed into dimensionless disturbance representations, while latency encoding and membrane integration capture disturbance intensity and temporal evolution. The framework is evaluated across four heterogeneous network configurations: a two-DER inverter-interfaced microgrid, an islanded ring microgrid, the IEEE 13-node feeder, and the CIGRE European medium-voltage benchmark. Across 480 cases, it achieves a median operating time of 7.6 ms, with 94.2 % of cases operating within one power cycle. The results demonstrate selective protection across different electrical ratings and network topologies using a common parameterization without network-specific retuning, highlighting the potential of neuromorphic processing for physically interpretable, communication-free protection of converter-dominated distribution networks.

0.30

A Novel Asymmetric Distributed Voltage Regulation Scheme to Enhance the Utilization of Distributed Energy Resources

eess.SY ·2026-11-05 ·Madhura Sondharangalla, Dan Moldovan, Raja Ayyanar
published similarity 0.60
Abstract

Passive voltage regulation in distribution grids using distributed energy resources (DERs) is becoming the standard for feeder voltage management in both under-voltage and over-voltage scenarios. Their simple control, ease of implementation, and fast response make them ideal for distribution feeders with high-DER penetration. This paper proposes a novel distributed voltage control for DERs based on the voltage at the point of common coupling, inverter rating, and operating active power. The proposed control is designed to utilize feeder inverters efficiently to reduce the burden on the inverters in both under-voltage and over-voltage operations and increase the fairness in reactive power ($Q$) support in over-voltage operations. The proposed control is implemented in static and dynamic simulations of a real feeder to validate the performance. Results for the under-voltage scenario are also presented in the paper.

0.36