CS Paper Radar

A Novel Asymmetric Distributed Voltage Regulation Scheme to Enhance the Utilization of Distributed Energy Resources

Madhura Sondharangalla, Dan Moldovan, Raja Ayyanar

eess.SY ·submitted 2026-11-05 04:05 UTC · v1
published

Abstract

Passive voltage regulation in distribution grids using distributed energy resources (DERs) is becoming the standard for feeder voltage management in both under-voltage and over-voltage scenarios. Their simple control, ease of implementation, and fast response make them ideal for distribution feeders with high-DER penetration. This paper proposes a novel distributed voltage control for DERs based on the voltage at the point of common coupling, inverter rating, and operating active power. The proposed control is designed to utilize feeder inverters efficiently to reduce the burden on the inverters in both under-voltage and over-voltage operations and increase the fairness in reactive power ($Q$) support in over-voltage operations. The proposed control is implemented in static and dynamic simulations of a real feeder to validate the performance. Results for the under-voltage scenario are also presented in the paper.

DOI
10.1109/PVSC57443.2024.10748978

Closest papers

Nearest neighbours by meaning across the whole index.

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.66
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Optimal Coordination of Multiple Ancillary Service Provisions in Active Distribution Networks

eess.SY ·2026-11-14 ·Xinbao Jia, Yi Guo, Ognjen Stanojev, Zhen Chen, Yuning Jiang +1 more
similarity 0.61
Abstract · 16 pages

We propose a multi-rate model predictive control (MPC) framework for coordinating primary frequency control (PFC), automatic generation control (AGC), and voltage control (VC) in active distribution networks. The framework allocates distributed energy resource (DER) flexibility among these three ancillary services while retaining their different update rates. To account for the intertemporal flexibility of electric vehicle aggregations and aggregations of buildings with thermostatically controlled loads (TCLs), we incorporate time-varying power-energy envelopes into our multi-rate MPC formulation. These constraints couple the combined PFC and AGC response to the demand-side flexibility available later in the prediction horizon. Furthermore, the input-multirate structure enables coordinated ancillary service provision by DERs with different response dynamics. The controller optimizes the three services together, allowing fast regulation to be coordinated with the developing slow response within the available DER flexibility. We demonstrate the coordinated provision of the three ancillary services through closed-loop simulations on a modified IEEE 33-bus system using a nonlinear differential-algebraic model.

0.32

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.60
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

Fixed-Time Voltage Regulation in Distribution Networks with Impedance Awareness

eess.SY ·2026-10-01 ·Nilanjan Roy Chowdhury, Venkatesh Sarangan
similarity 0.60
Abstract · 8 pages, 6 figures

This letter introduces an optimization-based fixed time control algorithm for solving the voltage regulation problem of a radial and balanced power distribution network. The proposed algorithm requires no prior knowledge of the exact network impedance (resistance and reactance), yet guarantees voltage convergence to the predefined safe limit within a fixed time-window. We embrace results from Fixed-time stability (FxTs) and Control Lyapunov function (CLF) to analyze the stability and robustness of the underlying algorithm and then synthesize it leveraging the Quadratic Programming (QP) approach. We first analytically provide sufficient conditions on the control gains and the design parameters, that can ensure voltage regulation in fixed-time. Thereafter we transform the existing voltage regulation problem into an equivalent QP-based optimization framework and translate the aforesaid conditions to find feasible solutions for voltage stability. We empirically verify the efficacy of our proposed algorithm on the IEEE-33 bus distribution network and compare its performance against other existing robust control methods.

0.29

Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

eess.SY ·2026-09-10 ·Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti
similarity 0.60
Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

0.28

Emergency Control of Transmission Voltages by Coordinating DERs From Multiple Substations

eess.SY ·2026-09-28 ·Francisco Escobar, Gustavo Valverde
top venue similarity 0.58
Abstract · Accepted in IEEE Transactions on Power Systems

Voltage stability can be endangered in transmission networks that operate under high strain and exhibit a large separation between generators and loads. During emergencies associated to voltage instability, one promising supporting countermeasure is to control large populations of Distributed Energy Resources (DERs) connected to medium- and low-voltage networks, so that they locally reduce the net load by modifying their power generation or consumption. However, it is challenging to achieve this control while anticipating interactions with legacy voltage regulators, coordinating efforts across substations, and exchanging small amounts of information with DERs. In this paper, we propose a control scheme that coordinates DER aggregations with the load tap changers of substation transformers, asks them to contribute power depending on the substation they are connected to, and relies on lightweight communication. Our simulations show that the proposed control can successfully coordinate DERs and load tap changers to enhance long-term voltage stability.

0.46

Zero-Sum Power Factor Games

eess.SY math.OC ·2026-08-20 ·Cameron Khanpour, Samuel Talkington, Mathieu Dahan, Daniel K. Molzahn
similarity 0.58
Abstract

Variable active power injections arising from device behavior or compromised dispatch complicate voltage regulation in electric power networks with distributed energy resources (DERs). An operator can limit the resulting voltage deviations by remotely selecting DER reactive power parameters before observing the active power injections. IEEE Standard 1547-2018 specifies constant power factor as one such control mode, coupling each device's reactive power to its realized active power. Using a linear voltage model, we formulate the operator's decision as a robust minimax problem in which the operator minimizes the largest feasible aggregate voltage deviation. We solve this problem by expressing the power factor decisions through continuous reactive to active power ratios and exactly decomposing the payoff according to the signs of the voltage deviations. When every feasible voltage residual remains on its initial side of nominal, the resulting ratios cancel each injection's contribution and yield a closed form minimax strategy. We identify realistic DER ratings for which this strategy applies and quantify the regulation capacity lost under restricted power factor ranges. Numerical tests check the cancellation computation, solve the complete minimax problem directly at a representative DER rating, and compare the linear voltage predictions with nonlinear AC power flow.

0.23

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.58
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.29