Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

Amir H. Abolmasoumi, Hamed Mohsenian-Rad

eess.SY ·submitted 2026-10-20 19:11 UTC · v1
published

Abstract

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

Comment
Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.66
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.36

Comparative Assessment of Frequency Scans using EMT and RMS Models

eess.SY ·2026-08-27 ·Clea Bürgel, Gustavo Valverde, Gabriela Hug
similarity 0.64
Abstract

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

0.22

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.63
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.33

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.63
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Spatial Differences Analysis of Nodal Frequency Considering Frequency-Voltage Coupling

eess.SY ·2026-11-04 ·Xiaodan Li, Donghai Zhu, Zining Liu, Zhu Guo, Jiabing Hu +1 more
similarity 0.62
Abstract

The rising penetration of inverter-based resources (IBRs) brings rich control dynamics that can amplify spatial differences in nodal frequency through frequency-voltage (F-V) coupling. Existing analyses often neglect voltage dynamics or only examine the aggregate frequency, leading to overoptimistic evaluation of frequency security. To address these drawbacks, this paper develops a unified model of synchronous generators (SGs), grid-following (GFL)-IBRs, and grid-forming (GFM)-IBRs based on the magnitude and phase dynamics of equivalent internal electromotive force (EMF). Integrating these source models with network equations yields a sparse implicit closed-loop model, which fully captures the device-network F-V coupling without transfer-matrix inversion. Then, the obtained nodal responses are decomposed into common and differential modes. Using this decomposition, coupling indices and pole-residue analysis reveal how F-V coupling can amplify spatial differences in nodal frequency and how source configuration and parameters modify this effect. Finally, case studies on the modified IEEE 39-bus and 118-bus test systems validate the proposed model and demonstrate its computational efficiency.

0.19

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.62
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.61
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.29

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.61
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36