Comparative Assessment of Frequency Scans using EMT and RMS Models

Clea Bürgel, Gustavo Valverde, Gabriela Hug

eess.SY ·submitted 2026-08-27 09:16 UTC · v1

Abstract

Frequency scans of inverter and grid impedances are crucial for assessing small-signal stability and system strength in inverter-dominated power systems. This paper compares frequency-scan results for several generating units, including a synchronous generator, grid-following, and grid-forming inverters, using fully dq electromagnetic transient and root-mean-square (RMS) models in Simulink. The scans are performed for the same device rating and operating point. Frequency scans and time-domain simulations show that the RMS models are valid only at low frequencies. We find that the current-controlled grid-forming inverter is more difficult to represent in RMS than the voltage-controlled grid-forming inverter. However, including the inner voltage-control loops improves the accuracy of the RMS representation. The paper also investigates the influence of generator and grid impedance on the total system impedance seen from the point of common coupling and relates the oscillatory modes and zeros of the system to peaks and dips in the first and second singular values of the system impedance, respectively.

Closest papers

Nearest neighbours by meaning across the whole index.

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.72
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Spatial Differences Analysis of Nodal Frequency Considering Frequency-Voltage Coupling

eess.SY ·2026-11-04 ·Xiaodan Li, Donghai Zhu, Zining Liu, Zhu Guo, Jiabing Hu +1 more
similarity 0.66
Abstract

The rising penetration of inverter-based resources (IBRs) brings rich control dynamics that can amplify spatial differences in nodal frequency through frequency-voltage (F-V) coupling. Existing analyses often neglect voltage dynamics or only examine the aggregate frequency, leading to overoptimistic evaluation of frequency security. To address these drawbacks, this paper develops a unified model of synchronous generators (SGs), grid-following (GFL)-IBRs, and grid-forming (GFM)-IBRs based on the magnitude and phase dynamics of equivalent internal electromotive force (EMF). Integrating these source models with network equations yields a sparse implicit closed-loop model, which fully captures the device-network F-V coupling without transfer-matrix inversion. Then, the obtained nodal responses are decomposed into common and differential modes. Using this decomposition, coupling indices and pole-residue analysis reveal how F-V coupling can amplify spatial differences in nodal frequency and how source configuration and parameters modify this effect. Finally, case studies on the modified IEEE 39-bus and 118-bus test systems validate the proposed model and demonstrate its computational efficiency.

0.19

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.64
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.63
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.63
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.63
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.28

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.63
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Development of an EMT model of the Balearic power system

eess.SY ·2026-09-02 ·Yousef Pipelzadeh, Dharshana Muthumuni, Farid Mosallat, Javier Renedo, Silvia Sanz Verdugo +3 more
similarity 0.61
Abstract

The Balearic Islands are striving to achieve 100% renewable energy, which poses new challenges in operating the power system securely and reliably. With a higher integration of inverter-based resources (IBRs) and a reduced presence of conventional synchronous generators, the system strength, particularly short circuit levels, becomes weaker and more susceptible to disturbances; and the total inertia of the system becomes lower. Technology enablers are planned to achieve energy transition in the Balearic power system: a new 2x200 MW VSC-HVDC link (bipole with metallic return), Synchronous Compensators (SC) and Battery Energy Storage Systems (BESS), as fully-integrated network components. Detailed ElectroMagnetic Transient (EMT) simulation studies may be needed to analyse stability of the system, due to the high amounts of power-electronics devices in the system. This paper describes the implementation of an EMT model of the Balearic power system.