Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao, F. Milano

eess.SY ·submitted 2026-11-13 10:00 UTC · v1

Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

Closest papers

Nearest neighbours by meaning across the whole index.

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.69
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.69
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Guidelines for the implementation of power oscillation damping controllers in power converters

eess.SY ·2026-09-02 ·Javier Renedo, Macarena Martín Almenta, Sergio Martínez Villanueva, Agustín Díaz-García, Antonio Cordón +1 more
similarity 0.67
Abstract

One of the most effective ways to damp electromechanical oscillations in power systems is by means of supplementary controllers attached to the different devices in the power system is by means of power system stabilizers (PSS) in synchronous machines or by means of power oscillation damping (POD) controllers in facilities with power converters. In the recent years, the use of POD controllers in voltage source converters (VSCs) with grid-following (GFL) control has been investigated. Although the potential of POD controllers to help to damp inter-area oscillations in power systems is enormous, their correct implementation is not trivial, because their effectiveness is strongly linked to their settings. This paper provides guidelines for the implementation of POD controllers in power converters for application in real-world power systems. The paper proposes compliance criteria for POD controllers using a synthetic test system and a systematic methodology used in Spanish technical standard for monitoring compliance (NTS), considering practical considerations. The paper also includes numerical examples to illustrate compliance criteria for POD controllers in a synthetic test system. A generic power converter with grid-following (GFL) control is used for the analysis by simulation and POD controllers using modulation of active-power injection (POD-P), reactive-power injection (POD-Q) or both simultaneously (POD-PQ) will be analysed. Results were validated in a large-scale power system. The paper concludes that by using appropriate synthetic systems, methodologies and compliance criteria, POD controllers in power converters could be effective to damp electromechanical oscillation in large-scale power systems.

0.33

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.66
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.27

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.66
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.64
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.64
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.64
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.28