CS Paper Radar

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

Grigoris Michos, Christos K. Verginis

eess.SY ·submitted 2026-10-18 13:39 UTC · v1

Abstract

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

Comment
10 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Barrier Function Control for the Interconnection of DC Electronic Loads to Utility Grid

eess.SY ·2026-10-22 ·Grigoris Michos, Christos K. Verginis
similarity 0.70
Abstract · preprint for paper to appear in IEEE ISGT Europe conference 2026

This paper proposes a nonlinear control law that facilitates the safe integration of DC electronic loads to the utility grid. Specifically, by employing suitable reciprocal barrier functions, it is rigorously proven that the closed-loop system guarantees constrained operation within a desired operating region, despite the influence of fast converter dynamics and fluctuating constant power load demand. This way, the proposed controller guarantees safety of the electronic components from surges in power demand and high transients. The theoretic results are validated in simulation scenarios, where the performance of the proposed controller is compared against the conventional saturated-PI controller. Contrary to the latter, the proposed method guarantees stable and safe operation, enhancing the system robustness.

0.16

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.68
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.67
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.28

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.66
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.33

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

eess.SY ·2026-09-29 ·Wei Zhou, Yunjie Gu
similarity 0.66
Abstract · 10 pages, 6 figures

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

0.25

Relative-Degree Wall Restricts Passivity-Based Stability Analysis in Inverter-Dominant Grids

eess.SY ·2026-08-30 ·Xiaoyu Peng, Zhongze Li, Xi Ru, Xinghua Chen, Feng Liu
top venue similarity 0.62
Abstract

This letter reveals a fundamental limitation of passivity-based distributed stability analysis in power systems. Under the standard formulation, passivity certification inherently imposes a relative-degree compatibility constraint that excludes many high-fidelity inverter dynamic models (e.g., those that include electromagnetic transients). Potential extensions of passivity frameworks are discussed to break this limitation.

0.43

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.62
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.62
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23