CS Paper Radar

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

Wei Zhou, Yunjie Gu

eess.SY ·submitted 2026-09-29 08:15 UTC · v1

Abstract

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

Comment
10 pages, 6 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Comparison of Current-Limiting Strategies for Grid-Forming Converters Under Grid Faults

eess.SY ·2026-10-17 ·Maitraya Avadhut Desai, Ramona Stoll, Xiuqiang He, Florian Dörfler, Gabriela Hug
published similarity 0.71
Abstract · Presented at the 16th IEEE PowerTech Conference (Kiel 2025). 6 pages, 12 figures

This paper investigates the performance of three state-of-the-art current-limiting strategies for grid-forming (GFM) converters under grid faults. These highly effective strategies include virtual admittance control, virtual admittance control enhanced with virtual power feedback, and the recently developed cross-forming control. The performance comparison addresses two crucial requirements for GFM converters under grid faults, namely transient stability and reactive current injection. The comparison indicates that the virtual admittance control enhanced with virtual power feedback shows the most promising transient stability performance, while the cross-forming control exhibits superior reactive current injection performance. Thus, individual benefits of each strategy can be obtained by properly combining them.

0.32

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.67
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.66
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.64
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.63
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Local Energy Function-Based Power System Transient Stability Analysis with Grid Forming and Grid Following Inverters

eess.SY ·2026-09-06 ·Yingyi Tang, Junbo Zhao, Baosen Zhang
similarity 0.61
Abstract

The widespread deployment of inverter-based resources (IBRs) is reshaping power system dynamics by their control strategies. Grid-following (GFL) and grid-forming (GFM) inverters are expected to co-exist from now on. However, ensuring the transient stability of such systems remains a critical and underexplored challenge. In this paper, a comprehensive transient stability analysis of the mixed-GFM-GFL inverter system is conducted using a newly derived local energy function. The transient stability analysis model of the system is first derived to reveal the dynamic interactions between GFL and GFM inverters during transient responses. A local energy function is then proposed for analytical transient stability assessment. Instead of ignoring or making harsh assumptions on inverters' coupled damping effect, the proposed local energy function carefully addresses its impact on system transient stability by locally bounding the region where the system's energy dissipation property holds. Such a property fully considers the combined damping effect of GFL and GFM inverters. The derived critical energy and stability index provide a fast and quantitative transient stability assessment. Furthermore, the adverse impact of insufficient damping of GFM inverters on system transient stability is thoroughly investigated. The effectiveness of the proposed method is validated on the modified IEEE 14-bus system with mixed GFL and GFM inverters, and the numerical simulation results further demonstrate the small conservativeness of the proposed method.

0.24

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.61
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Quantifying the Unintentional Islanding Risk: A Comparative Study on Active Distribution Network

eess.SY ·2026-09-10 ·Harshit Nayak, Edoardo Daccò, Jose Luis Rueda Torres, Davide Falabretti
similarity 0.58
Abstract

The growing share of Inverter-Based Resources (IBRs) is changing the operation of modern Active Distribution Networks (ADNs), raising concerns for grid stability, protection, and reliability. In this paper, we investigate the dynamic behavior of a Medium-Voltage (MV) portion of an ADN during the transition from grid-connected to islanded operation. The study considers a Grid-Following (GFL) converter and Synchronous Generators (SGs) operated under two distinct regulation modes: a fixed-setpoint, non-regulating condition representative of present-day distribution networks, and an active frequency/voltage-regulating condition representative of SGs equipped with governor and AVR control. Detailed electromagnetic transient (EMT) models of both technologies have been developed in DIgSILENT PowerFactory that quantifies the sensitivity of island persistence to SG regulation mode and inertia. The results show that when DERs operate at a fixed power setpoint, the risk of forming a sustained, undetected electrical island is limited, since the isolated network drifts out of the protection thresholds within tens of seconds. Conversely, enabling frequency and voltage regulation on the SGs is sufficient to sustain an unintentional island indefinitely without triggering conventional protection, regardless of system inertia.

0.28