Local Energy Function-Based Power System Transient Stability Analysis with Grid Forming and Grid Following Inverters

Yingyi Tang, Junbo Zhao, Baosen Zhang

eess.SY ·submitted 2026-09-06 16:36 UTC · v1

Abstract

The widespread deployment of inverter-based resources (IBRs) is reshaping power system dynamics by their control strategies. Grid-following (GFL) and grid-forming (GFM) inverters are expected to co-exist from now on. However, ensuring the transient stability of such systems remains a critical and underexplored challenge. In this paper, a comprehensive transient stability analysis of the mixed-GFM-GFL inverter system is conducted using a newly derived local energy function. The transient stability analysis model of the system is first derived to reveal the dynamic interactions between GFL and GFM inverters during transient responses. A local energy function is then proposed for analytical transient stability assessment. Instead of ignoring or making harsh assumptions on inverters' coupled damping effect, the proposed local energy function carefully addresses its impact on system transient stability by locally bounding the region where the system's energy dissipation property holds. Such a property fully considers the combined damping effect of GFL and GFM inverters. The derived critical energy and stability index provide a fast and quantitative transient stability assessment. Furthermore, the adverse impact of insufficient damping of GFM inverters on system transient stability is thoroughly investigated. The effectiveness of the proposed method is validated on the modified IEEE 14-bus system with mixed GFL and GFM inverters, and the numerical simulation results further demonstrate the small conservativeness of the proposed method.

Closest papers

Nearest neighbours by meaning across the whole index.

Quantitative Stability Region Estimation of Grid-Forming Inverters with Current Limiting via a State-Dependent Switched Energy Function

eess.SY ·2026-11-11 ·Yifan Zhang, Yang Wu
similarity 0.73
Abstract

With increasing renewable energy integration, grid-forming (GFM) inverters are becoming key components of future power systems. Compared with synchronous generators (SGs), GFM inverters have limited overcurrent capability and require current limiting. This can lead to switching between normal and current-limited operating modes under large disturbances, complicating synchronization dynamics and posing a longstanding challenge to existing transient-stability analysis methods. In this paper, a state-dependent switched (SdS) energy function theory is proposed for transient-stability analysis of GFM inverters with current limiting, whose dynamics can be abstracted as SdS nonlinear systems. Regional energy functions are constructed for individual operating modes and continuously matched at switching interfaces, yielding a continuous piecewise energy function. Hence, the derived conservative estimate of the stability region (region of attraction, ROA) spans different operating regions without prescribing subsequent current limiting activations and releases, a fundamental distinction from conventional methods using signal-mode energy functions. Techniques for incorporating damping energy are extended to the proposed framework to capture damping effects and further reduce the conservatism of the ROA estimates. The methodology applies to GFM inverters with different synchronization control loops and current-limiting strategies. Experiments on a physical GFM inverter under various grid contingencies validate the proposed quantitative transient stability assessment.

0.22

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.61
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

eess.SY ·2026-09-29 ·Wei Zhou, Yunjie Gu
similarity 0.61
Abstract · 10 pages, 6 figures

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

0.25

Impact of Grid-Forming Inverter Placement and Penetration on Local and Aggregate Frequency

eess.SY ·2026-11-13 ·Fatma Alfailkawi, Marena Trujillo, Bri-Mathias Hodge
similarity 0.61
Abstract

Modern power systems are undergoing a huge shift in generation mix, including inverter-based resources that are fundamentally changing the stability dynamics of the grid. Thus, synchronous Generators (SG) are gradually being displaced by Grid-forming inverters (GFM) that are proposed as a solution to continue supporting grid stability. However, the effect of GFM placement in the network on frequency performance and how well aggregate-frequency assessment captures placement sensitivity observed in local frequency metrics remains unclear. This paper evaluates all SG and droop-controlled GFM assignments in the IEEE 39-bus system. A reduced-order model is used for the exhaustive search with load disturbances applied separately at every eligible load bus while considering nadir and Rate of Change of Frequency (RoCoF) derived from both device rating weighted aggregate frequency and local bus frequencies. Results reveal that at fixed GFM penetration, placement produced up to 104 mHz variation in worst-case local nadir and 0.21 Hz/s in maximum local RoCoF. Aggregate-frequency assessment reduced the apparent across placements by 89\% for nadir and 88\% for RoCoF at 50\% GFM penetration. These results indicate that aggregate-frequency assessment alone may obscure favorable or adverse placement effects on local frequency performance.

0.28

Distributed Droop-Free Control of Grid-Forming Inverters with Dynamic Line and Load Modeling

eess.SY ·2026-09-07 ·Hiya Akhil Gada, Marija Ilic
similarity 0.61
Abstract

Droop-free distributed control has emerged as a promising alternative to conventional linear droop control for coordinating inverter-based resources in AC microgrids. However, existing droop-free methods typically rely on quasi-steady state network models that neglect fast electromagnetic transients and assume a decoupled dependence of active and reactive power on frequency and voltage, respectively. In this paper, we propose a transient-aware droop-free distributed primary/secondary control framework for grid-forming (GFM) inverters. The control objective is to achieve proportional active and reactive power sharing, frequency regulation, and voltage regulation within prescribed bounds. The proposed approach incorporates dynamic models of network lines and loads into the control design, enabling accurate representation of transient behavior while capturing the coupled nature of power flow interactions. A gradient-based distributed control update is derived from an optimization formulation, in which voltage magnitude constraints are enforced through a projection operator. To validate the performance of the proposed control, real-time simulation studies are conducted on a four-inverter microgrid under load changes in both strong and weak grid conditions. The results demonstrate that the proposed method improves transient performance, particularly in weak grids, while preserving the same steady state operating conditions as existing QSS-based droop-free approaches.

0.21

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.60
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.59
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

Impacts of Heterogeneous Grid-Forming Devices on Power System Dynamics Quantified by DW Shells

eess.SY ·2026-08-22 ·Liangxiao Luo, Linbin Huang, Hangyu Chen, Ruohan Leng, Zhixian Hou +2 more
similarity 0.59
Abstract

The concept of grid-forming (GFM) converters has gained great attention in the past years. However, it remains challenging to analyze and quantify the impacts of heterogeneous GFM devices (e.g., GFM energy storage systems, GFM wind turbines, GFM HVDC stations) on power system dynamics, especially when taking into account the complex interaction between GFM converters and grid-following (GFL) converters. To this end, this paper focuses on the decentralized and scalable stability analysis of power systems containing both GFM and GFL converters, where we use Davis-Wielandt (DW) shells to characterize the dynamics of the converters and the power grid. In particular, we analytically derive how integrating heterogeneous GFM converters affects the DW shell of the power grid and therefore the system stability. Our approach does not require the detailed parameters or control schemes of the GFM converters; instead, we define the local passivity and imaginary-axis indices of GFM converters to compactly describe their characteristics. These two indices can be conveniently obtained by testing a GFM converter and greatly simplify the stability analysis and computation when handling large-scale power systems.

0.29