Abstract

The concept of grid-forming (GFM) converters has gained great attention in the past years. However, it remains challenging to analyze and quantify the impacts of heterogeneous GFM devices (e.g., GFM energy storage systems, GFM wind turbines, GFM HVDC stations) on power system dynamics, especially when taking into account the complex interaction between GFM converters and grid-following (GFL) converters. To this end, this paper focuses on the decentralized and scalable stability analysis of power systems containing both GFM and GFL converters, where we use Davis-Wielandt (DW) shells to characterize the dynamics of the converters and the power grid. In particular, we analytically derive how integrating heterogeneous GFM converters affects the DW shell of the power grid and therefore the system stability. Our approach does not require the detailed parameters or control schemes of the GFM converters; instead, we define the local passivity and imaginary-axis indices of GFM converters to compactly describe their characteristics. These two indices can be conveniently obtained by testing a GFM converter and greatly simplify the stability analysis and computation when handling large-scale power systems.

Closest papers

Nearest neighbours by meaning across the whole index.

Scalable Small-Signal Stability Assessment of Power Systems Based on Frequency-Domain Quadratic Constraints

eess.SY ·2026-09-28 ·Xiaoying Liu, Linbin Huang, Hangyu Chen, Huanhai Xin
similarity 0.70
Abstract

Small-signal stability analysis of power electronics-dominated power systems is becoming increasingly challenging due to the large-scale integration of heterogeneous grid-following (GFL) and grid-forming (GFM) converters. Classical centralized methods, such as eigenvalue analysis and the generalized Nyquist criterion, provide direct stability assessment tools but exhibit limited scalability as the system size increases. This motivates scalable analysis methods for stability assessment and device-level diagnosis, and calls for less conservative stability conditions. To this end, this paper proposes a scalable small-signal stability assessment method with quantitative stability indices for multi-converter systems based on frequency-domain quadratic constraints (FQCs). It is shown that several existing stability conditions, including geometric conditions based on the Davis-Wielandt (DW) shell, numerical range, $x$-$z$ graph, scaled relative graph (SRG), mixed gain-phase condition, and passivity condition, are special cases of the FQC-based stability condition. This FQC-based formulation also clarifies the requirements for decentralized verification of these existing stability conditions. To further reduce conservatism, a full-multiplier FQC-based stability condition is developed, based on which an optimization problem is formulated for scalable stability certification and device-level diagnosis using quantitative stability indices without relying on graphical inspection. Combined with the mixed gain-phase condition, this optimization problem forms a hierarchical screening-diagnosis procedure that improves efficiency. Case studies demonstrate that the proposed method is less conservative than existing criteria and can effectively identify problematic devices associated with potential instability risks.

0.39

Local Energy Function-Based Power System Transient Stability Analysis with Grid Forming and Grid Following Inverters

eess.SY ·2026-09-06 ·Yingyi Tang, Junbo Zhao, Baosen Zhang
similarity 0.59
Abstract

The widespread deployment of inverter-based resources (IBRs) is reshaping power system dynamics by their control strategies. Grid-following (GFL) and grid-forming (GFM) inverters are expected to co-exist from now on. However, ensuring the transient stability of such systems remains a critical and underexplored challenge. In this paper, a comprehensive transient stability analysis of the mixed-GFM-GFL inverter system is conducted using a newly derived local energy function. The transient stability analysis model of the system is first derived to reveal the dynamic interactions between GFL and GFM inverters during transient responses. A local energy function is then proposed for analytical transient stability assessment. Instead of ignoring or making harsh assumptions on inverters' coupled damping effect, the proposed local energy function carefully addresses its impact on system transient stability by locally bounding the region where the system's energy dissipation property holds. Such a property fully considers the combined damping effect of GFL and GFM inverters. The derived critical energy and stability index provide a fast and quantitative transient stability assessment. Furthermore, the adverse impact of insufficient damping of GFM inverters on system transient stability is thoroughly investigated. The effectiveness of the proposed method is validated on the modified IEEE 14-bus system with mixed GFL and GFM inverters, and the numerical simulation results further demonstrate the small conservativeness of the proposed method.

0.24

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

eess.SY ·2026-11-05 ·Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten
code/data similarity 0.59
Abstract · Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z…

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

0.44

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.56
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Impact of Reduced-Order Modelling on Sum-of-Squares Region-of-Attraction Certification for Grid-Forming and Grid-Following Converters

eess.SY math.OC ·2026-11-10 ·Chenxi Yuan, Jeremy D. Watson, Neville R. Watson
similarity 0.56
Abstract · 13 pages, 5 figures, 3 tables

With the increasing penetration of power-electronic equipment, the transient stability of grid-forming (GFM) and grid-following (GFL) converters is increasingly characterized through the region of attraction (ROA) of the post-fault equilibrium. Sum-of-squares (SOS) programming yields certified inner approximations of the ROA, yet its computational cost grows rapidly with system order. Reduced-order models are therefore widely used to reduce computational cost and, more importantly, to enable analytical investigation. However, ROA analyses based on these models often assume that reproducing the converter's transient response, or retaining more dynamics in the correct time-frame, is sufficient to preserve the ROA of the full-order system. Using time-domain ODE simulations as a reference, the SOS-based ROA of each reduced-order GFM and GFL model is assessed against both its own simulated ROA and that of the corresponding full-order model, thereby separating SOS-induced conservativeness from model-order-induced ROA distortion. The results indicate that increasing reduced-order model complexity does not necessarily improve SOS-based ROA fidelity. In the cases examined, more complex reduced-order models yield lower SOS coverage of the full-order reference ROA, despite closer ODE-boundary agreement in some regions. Model selection should therefore consider both full-order ROA fidelity and certified coverage of the practical operating range, rather than model complexity alone.

0.27

Relative-Degree Wall Restricts Passivity-Based Stability Analysis in Inverter-Dominant Grids

eess.SY ·2026-08-30 ·Xiaoyu Peng, Zhongze Li, Xi Ru, Xinghua Chen, Feng Liu
top venue similarity 0.56
Abstract

This letter reveals a fundamental limitation of passivity-based distributed stability analysis in power systems. Under the standard formulation, passivity certification inherently imposes a relative-degree compatibility constraint that excludes many high-fidelity inverter dynamic models (e.g., those that include electromagnetic transients). Potential extensions of passivity frameworks are discussed to break this limitation.

0.43

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part I

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.56
Abstract · 15 pages, 10 figures

The rise of renewable generation in AC power systems calls for small-signal stability assessment methods that do not rely on centralised, system-wide models. In this two-part paper, we present a decentralised stability framework based on frequency-domain conditions imposed on local subsystems (many admitting equivalent graphical interpretations) which collectively imply the stability of the entire grid. The framework generalises many previously reported results, with added flexibility and plug-and-play compatibility provided by the additional degrees of freedom of the imposed conditions, the ability to mix conditions across frequency ranges, conditions on extended subsystems that couple buses to their connecting lines and loads, and a method to incorporate unstable subsystems. Detailed, heterogeneous device and line models are accommodated in the frequency domain using impedance, admittance, and power-flow models, making the framework suitable as a foundation for grid codes that enable plug-and-play functionality in inverter-dominated grids. Part I focuses on stable impedance and admittance representations and Part II extends the results to unstable subsystems, which are shown to be fundamentally present in many grid models. The results of Part I are validated on a modified 9-bus case study, demonstrating the reduced conservatism and significance of the proposed approach.

0.53

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.56
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.