CS Paper Radar

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten

eess.SY ·submitted 2026-11-05 10:01 UTC · v1
code/data

Abstract

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

Comment
Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z-tool

Closest papers

Nearest neighbours by meaning across the whole index.

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.67
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Scalable Small-Signal Stability Assessment of Power Systems Based on Frequency-Domain Quadratic Constraints

eess.SY ·2026-09-28 ·Xiaoying Liu, Linbin Huang, Hangyu Chen, Huanhai Xin
similarity 0.61
Abstract

Small-signal stability analysis of power electronics-dominated power systems is becoming increasingly challenging due to the large-scale integration of heterogeneous grid-following (GFL) and grid-forming (GFM) converters. Classical centralized methods, such as eigenvalue analysis and the generalized Nyquist criterion, provide direct stability assessment tools but exhibit limited scalability as the system size increases. This motivates scalable analysis methods for stability assessment and device-level diagnosis, and calls for less conservative stability conditions. To this end, this paper proposes a scalable small-signal stability assessment method with quantitative stability indices for multi-converter systems based on frequency-domain quadratic constraints (FQCs). It is shown that several existing stability conditions, including geometric conditions based on the Davis-Wielandt (DW) shell, numerical range, $x$-$z$ graph, scaled relative graph (SRG), mixed gain-phase condition, and passivity condition, are special cases of the FQC-based stability condition. This FQC-based formulation also clarifies the requirements for decentralized verification of these existing stability conditions. To further reduce conservatism, a full-multiplier FQC-based stability condition is developed, based on which an optimization problem is formulated for scalable stability certification and device-level diagnosis using quantitative stability indices without relying on graphical inspection. Combined with the mixed gain-phase condition, this optimization problem forms a hierarchical screening-diagnosis procedure that improves efficiency. Case studies demonstrate that the proposed method is less conservative than existing criteria and can effectively identify problematic devices associated with potential instability risks.

0.40

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.59
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36

Impacts of Heterogeneous Grid-Forming Devices on Power System Dynamics Quantified by DW Shells

eess.SY ·2026-08-22 ·Liangxiao Luo, Linbin Huang, Hangyu Chen, Ruohan Leng, Zhixian Hou +2 more
similarity 0.59
Abstract

The concept of grid-forming (GFM) converters has gained great attention in the past years. However, it remains challenging to analyze and quantify the impacts of heterogeneous GFM devices (e.g., GFM energy storage systems, GFM wind turbines, GFM HVDC stations) on power system dynamics, especially when taking into account the complex interaction between GFM converters and grid-following (GFL) converters. To this end, this paper focuses on the decentralized and scalable stability analysis of power systems containing both GFM and GFL converters, where we use Davis-Wielandt (DW) shells to characterize the dynamics of the converters and the power grid. In particular, we analytically derive how integrating heterogeneous GFM converters affects the DW shell of the power grid and therefore the system stability. Our approach does not require the detailed parameters or control schemes of the GFM converters; instead, we define the local passivity and imaginary-axis indices of GFM converters to compactly describe their characteristics. These two indices can be conveniently obtained by testing a GFM converter and greatly simplify the stability analysis and computation when handling large-scale power systems.

0.29

Decentralized Impedance Specifications for Grid-Connected Converters: a Sequence-Domain Gershgorin Method, and a Frequency-Wise Framework for Combining Different Criteria

eess.SY ·2026-11-03 ·Lazar Stojanović, Ružica Cvetanović, Paolo Mattavelli, Simone Buso
similarity 0.58
Abstract

In complex grid scenarios, with many power electronics (PE) converters connected, having specifications for converters can ease the design process. A practical approach is to impose the specifications on the converter's small-signal impedance in the frequency domain. This is advantageous since impedance is a physical property that can be measured. This paper focuses on providing decentralized impedance specifications for each converter connected to an ac bus. With decentralized specifications, each converter has its own specifications, which are independent of other converters' impedance. This enables a competitive multi-vendor environment while guaranteeing system stability. Existing methods of imposing decentralized specifications, based on the small-gain, passivity and Gershgorin theorems, are formulated within a common frequency-domain framework. Building on this, two new solutions that reduce the conservativeness of the specifications are proposed. First, Gershgorin-based decentralized specifications are formulated in the modified sequence domain. Second, a framework for combining different specification types across frequency ranges is developed and mathematically proven. The methods are compared on examples covering sub-synchronous and harmonic-range interactions of grid-following converters, grid-forming converters, and a mixed grid-forming/grid-following system, using analytical models, black-box impedance measurements, and time-domain responses obtained from simulations and an experimental setup.

0.24

Blackbox Small-Signal Modeling of Grid-Connected Inverters in Asymmetrical Power Grids

eess.SY ·2026-09-01 ·Airan Frances, Dionisio Ramirez, Javier Uceda
top venuehighly cited similarity 0.58
Abstract · 11 pages, 14 figures, IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 38, NO. 10, OCTOBER 2023

Power electronic converters are envisaged to be key enablers of modern electric power distribution systems. Grid-connected three-phase inverters are widely used in Smart Grids and microgrids, but also in standard grids. They provide controllability and dynamic decoupling capabilities, which are fundamental in the integration of renewable sources and storage systems and in specialized applications such as FACTS. Nevertheless, power electronics-based systems can exhibit dynamic interactions, which may lead to power quality issues. Although the electrical model of each element of these systems is important for their system-level analysis, they are rarely available. Blackbox modeling strategies are useful for obtaining behavioral models of commercial electronic converters. Most blackbox modeling strategies are focused on dc-dc electronic converters; however, some works have extended these concepts to three-phase converters by means of the dq framework, under the assumption of symmetrical and balanced conditions. This work proposes a new structure in the sequence domain to represent the dynamic behavior of grid-connected commercial converters in asymmetrical conditions. Experimental tests have been performed on a three-phase inverter to identify its blackbox model and its performance has been validated during an asymmetric voltage sag.

0.82

Unifying Heterogeneous Dissipativity for Distributed Power-System Stability Analysis

eess.SY ·2026-11-11 ·Xi Ru, Xiaoyu Peng, Feng Liu
similarity 0.57
Abstract · 11 pages, 9 figures

Compositional dissipativity is attractive for large-scale interconnected systems, but its application to modern heterogeneous power systems is limited by conservative descriptions of nodal dissipativity and inefficient distributed implementation. This paper introduces a common first-order dynamic lifting of the physical voltage-current port, providing an enriched dissipativity representation that captures complementary frequency-dependent energy behavior while preserving network composability. The resulting representation accommodates heterogeneous power system buses within a unified dissipativity description and enables less conservative compositional stability analysis. A centralized stability-certification problem is then formulated and solved through a dual-guided column-generation scheme. Its matrix dual reveals the network-critical dissipation direction, which guides parallel local certificate generation toward the current system bottleneck. This leads to a distributed Network-Critical Margin Exchange (NCME) method with early stability certification. Case studies demonstrate substantially reduced conservatism of the dynamic-port formulation and improved computational and communication scalability of NCME for heterogeneous power systems.

0.26

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.57
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32