CS Paper Radar

Decentralized Impedance Specifications for Grid-Connected Converters: a Sequence-Domain Gershgorin Method, and a Frequency-Wise Framework for Combining Different Criteria

Lazar Stojanović, Ružica Cvetanović, Paolo Mattavelli, Simone Buso

eess.SY ·submitted 2026-11-03 22:12 UTC · v1

Abstract

In complex grid scenarios, with many power electronics (PE) converters connected, having specifications for converters can ease the design process. A practical approach is to impose the specifications on the converter's small-signal impedance in the frequency domain. This is advantageous since impedance is a physical property that can be measured. This paper focuses on providing decentralized impedance specifications for each converter connected to an ac bus. With decentralized specifications, each converter has its own specifications, which are independent of other converters' impedance. This enables a competitive multi-vendor environment while guaranteeing system stability. Existing methods of imposing decentralized specifications, based on the small-gain, passivity and Gershgorin theorems, are formulated within a common frequency-domain framework. Building on this, two new solutions that reduce the conservativeness of the specifications are proposed. First, Gershgorin-based decentralized specifications are formulated in the modified sequence domain. Second, a framework for combining different specification types across frequency ranges is developed and mathematically proven. The methods are compared on examples covering sub-synchronous and harmonic-range interactions of grid-following converters, grid-forming converters, and a mixed grid-forming/grid-following system, using analytical models, black-box impedance measurements, and time-domain responses obtained from simulations and an experimental setup.

Closest papers

Nearest neighbours by meaning across the whole index.

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part I

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.68
Abstract · 15 pages, 10 figures

The rise of renewable generation in AC power systems calls for small-signal stability assessment methods that do not rely on centralised, system-wide models. In this two-part paper, we present a decentralised stability framework based on frequency-domain conditions imposed on local subsystems (many admitting equivalent graphical interpretations) which collectively imply the stability of the entire grid. The framework generalises many previously reported results, with added flexibility and plug-and-play compatibility provided by the additional degrees of freedom of the imposed conditions, the ability to mix conditions across frequency ranges, conditions on extended subsystems that couple buses to their connecting lines and loads, and a method to incorporate unstable subsystems. Detailed, heterogeneous device and line models are accommodated in the frequency domain using impedance, admittance, and power-flow models, making the framework suitable as a foundation for grid codes that enable plug-and-play functionality in inverter-dominated grids. Part I focuses on stable impedance and admittance representations and Part II extends the results to unstable subsystems, which are shown to be fundamentally present in many grid models. The results of Part I are validated on a modified 9-bus case study, demonstrating the reduced conservatism and significance of the proposed approach.

0.54

A New Index for Quantifying Stability Adaptation Effort in Power Electronics-Dominated Power Systems Based on Frequency-Domain Impedance Identification

eess.SY ·2026-10-02 ·Luis A. Garcia-Reyes, Macarena Martin-Almenta, Edgar Nuño-Martínez, Javier Renedo, Antonio Cordón-Rodríguez +2 more
published similarity 0.63
Abstract · Paper in Proceedings of CIGRE Paris Session, C4-PS1, Paper ID 11553

The increasing use of converter based resources has made stability assessment in modern power systems more challenging, particularly because many devices are available only as black box models. Conventional eigenvalue based methods require full dynamic representations, while frequency domain impedance techniques based on the Generalized Nyquist Criterion (GNC) provide stability insight but do not quantify how much a converter must be retuned to restore stability. This paper introduces the Adaptation Effort Index (AEI), a metric that measures the sensitivity of dominant modes to parameter variations and quantifies the effort required for a converter to reconfigure itself under unstable operating conditions. The AEI combines the Nyquist Stability Margin obtained from frequency domain screening with a modal sensitivity index derived from fitted state space models synthesized from black box impedance data. The method is applied to a system comprising a grid forming and a grid following converter. Results show that, although both units can be tuned to stabilize the system, the grid following converter requires significantly less adaptation effort. The AEI therefore provides a practical and model agnostic tool for identifying which converter should be reconfigured in converter dominated grids, offering valuable guidance for system operators and manufacturers.

0.30

Impedance-Based Sensitivity Analysis for Stability Enhancement of LCC-HVDC Links Connected to Weak Grids Using Grid-Forming Converters

eess.SY ·2026-09-09 ·Luis A. Garcia-Reyes, Anup Joshi, Javier Renedo, Macarena Martin-Almenta, Oriol Gomis-Bellmunt +3 more
benchmark similarity 0.62
Abstract · Best Paper Award in the 2026 5th IEEE International Conference on Power Systems and Electrical Technology

This paper presents a frequency-domain, impedance-based sensitivity methodology for stability assessment and enhancement of line-commutated converter HVDC (LCC-HVDC) links operating under weak-grid conditions. The methodology integrates frequency-domain identification tailored for black-box systems, the Generalized Nyquist Criterion (GNC) for multivariable stability assessment, and modal impedance decomposition with participation-factor analysis to locate and interpret interaction mechanisms. The approach is validated against a detailed linearized state-space model and nonlinear EMT simulations of an LCC-HVDC benchmark. A sensitivity study varying the grid short-circuit ratio (SCR) reveals a stability limit for the standalone LCC-HVDC link and demonstrates that the integration of a grid-forming voltage source converter (GFM-VSC) substantially increases the stability margin.

0.20

Decentralised Plug-and-Play Stability Conditions for AC Grids-Part II: Unstable Subsystems

eess.SY ·2026-09-07 ·Liam Hallinan, Ioannis Lestas
similarity 0.61
Abstract · 15 pages, 13 figures

Part I of this paper presented a decentralised framework for certifying small-signal stability in AC grids using frequency-domain quadratic constraints on individual grid subsystems. Part II extends the framework to a broader class of networks that contain unstable subsystems. In particular, we show that such unstable subsystems arise in many common scenarios, even when the aggregate system is stable and well behaved. Such subsystems must be stabilised by the closed-loop network interconnection, which complicates decentralised stability analysis. A stable hybrid representation resembling the power (PQ) model at low frequencies and the impedance (IV) model at high frequencies is then defined, to which the stability framework of Part I can be applied, allowing plug-and-play compatible conditions to be formulated. Furthermore, we show that at low frequencies, the characteristic loci in the Nyquist plot of the return ratio in this hybrid representation decouple into unbounded and bounded branches along the classical $P$-$δ$ / $Q$-$V$ separation, and give sufficient conditions on each branch for ensuring system stability. The results are validated on the Kundur two-area system, where stability is certified, with a decentralised, plug-and-play compatible grid code covering the frequency ranges in which electromagnetic interactions arise.

0.30

Scalable Small-Signal Stability Assessment of Power Systems Based on Frequency-Domain Quadratic Constraints

eess.SY ·2026-09-28 ·Xiaoying Liu, Linbin Huang, Hangyu Chen, Huanhai Xin
similarity 0.59
Abstract

Small-signal stability analysis of power electronics-dominated power systems is becoming increasingly challenging due to the large-scale integration of heterogeneous grid-following (GFL) and grid-forming (GFM) converters. Classical centralized methods, such as eigenvalue analysis and the generalized Nyquist criterion, provide direct stability assessment tools but exhibit limited scalability as the system size increases. This motivates scalable analysis methods for stability assessment and device-level diagnosis, and calls for less conservative stability conditions. To this end, this paper proposes a scalable small-signal stability assessment method with quantitative stability indices for multi-converter systems based on frequency-domain quadratic constraints (FQCs). It is shown that several existing stability conditions, including geometric conditions based on the Davis-Wielandt (DW) shell, numerical range, $x$-$z$ graph, scaled relative graph (SRG), mixed gain-phase condition, and passivity condition, are special cases of the FQC-based stability condition. This FQC-based formulation also clarifies the requirements for decentralized verification of these existing stability conditions. To further reduce conservatism, a full-multiplier FQC-based stability condition is developed, based on which an optimization problem is formulated for scalable stability certification and device-level diagnosis using quantitative stability indices without relying on graphical inspection. Combined with the mixed gain-phase condition, this optimization problem forms a hierarchical screening-diagnosis procedure that improves efficiency. Case studies demonstrate that the proposed method is less conservative than existing criteria and can effectively identify problematic devices associated with potential instability risks.

0.40

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

eess.SY ·2026-11-05 ·Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten
code/data similarity 0.58
Abstract · Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z…

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

0.44

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.58
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32

Decentralized Stability Certificates for Interoperability in Power-Electronics-Dominated Power Systems

eess.SY ·2026-10-19 ·Linbin Huang, Verena Häberle, Ruohan Leng, Huanhai Xin, Hua Geng +2 more
similarity 0.58
Abstract

The rapid integration of power electronics converters has fundamentally altered the power grid's dynamic landscape, making modularity of operation and interoperability of heterogeneous devices two critical hurdles for power system reliability. In control language, these challenges can be paraphrased as decentralized certificates on the input/output behavior of every device, assured by local control, so that stability and guaranteed performance of the interconnected system emerge. For the power system application, such certificates should eventually be part of the rule book, the so-called grid code, and thus be generic and minimally restrictive for the control architecture of each device. Classical system-theoretic angles of attack to these questions go back to dissipativity concepts, which have historically been co-developed in automatic control, circuit theory, and power systems. Since standard dissipativity (e.g., passivity or small gain) criteria fall short in terms of conservatism, a range of more flexible and advanced tools have been developed to assure less conservative decentralized certificates guaranteeing stability under interconnection as well as dynamic performance following a disturbance. In this article, we review a range of methods that have been put forward to tackle these questions, compare and validate them, and point towards practically relevant research gaps which are amenable to control-theoretic approaches. Moreover, we provide a tutorial exposition of practically relevant power systems/electronics issues accessible to control engineers.

0.17