CS Paper Radar

Comparison of Current-Limiting Strategies for Grid-Forming Converters Under Grid Faults

Maitraya Avadhut Desai, Ramona Stoll, Xiuqiang He, Florian Dörfler, Gabriela Hug

eess.SY ·submitted 2026-10-17 14:36 UTC · v1
published

Abstract

This paper investigates the performance of three state-of-the-art current-limiting strategies for grid-forming (GFM) converters under grid faults. These highly effective strategies include virtual admittance control, virtual admittance control enhanced with virtual power feedback, and the recently developed cross-forming control. The performance comparison addresses two crucial requirements for GFM converters under grid faults, namely transient stability and reactive current injection. The comparison indicates that the virtual admittance control enhanced with virtual power feedback shows the most promising transient stability performance, while the cross-forming control exhibits superior reactive current injection performance. Thus, individual benefits of each strategy can be obtained by properly combining them.

Comment
Presented at the 16th IEEE PowerTech Conference (Kiel 2025). 6 pages, 12 figures
Journal ref
2025 IEEE Kiel PowerTech, Kiel, Germany, 2025, pp. 1-6
DOI
10.1109/PowerTech59965.2025.11180244

Closest papers

Nearest neighbours by meaning across the whole index.

An Energy-Based Framework for Transient Stability of Grid-Forming Converter Networks With Current Limiting

eess.SY ·2026-09-29 ·Wei Zhou, Yunjie Gu
similarity 0.71
Abstract · 10 pages, 6 figures

Existing analyses for the transient stability of grid-forming (GFM) converters under current limiting mainly address single-converter systems, while network-level transient stability analysis remains challenging. This paper develops a network energy construction that incorporates current limiting while retaining a provable dissipation property. This structure enables Lyapunov-based analysis consistent with classical direct method for synchronous-machine based systems, without switching between mode-dependent energy functions. A two-GFM example using a reactive circular current limiter and impedance insertion illustrates the proposed framework. Electromagnetic transient simulations support the theoretical results.

0.25

Internal-Model-Control-Based Virtual Admittance Emulation for Enhanced Grid-Forming Performance

eess.SY ·2026-09-18 ·Ruzica Cvetanovic, Lazar Stojanovic, Paolo Sbabo, Paolo Mattavelli, Massimo Bongiorno
similarity 0.68
Abstract

The large-scale integration of renewable energy into electrical power systems places a growing reliance on grid-forming converters (GFMs) to overcome critical stability and control hurdles. By emulating a slowly varying voltage source behind a tunable resistive?inductive impedance, GFMs enable precise setpoint tracking and vital grid support. In this regard, virtual admittance (VA)-based inner-loop control provides exceptional flexibility in shaping the converter's small-signal immittance at connection terminals, allowing for advanced GFM functionalities. This article addresses a novel internal-model-control-based VA approach, which inherently accounts for the effects of the inner current-control loop and the voltage feedforward. Unlike the state-of-the-art VA control, the proposed VA control ensures that, at frequencies outside the influence of outer loops, the converter's terminal admittance closely matches the target admittance, which is shown to be relevant for stability. It is revealed how, with the state-of-the art VA control, a small-signal instability in the harmonic range may arise if a low-pass filter with a high cut-off frequency is used for the voltage feedforward. However, the proposed VA control ensures stable operation regardless of this cut-off frequency. The methodology is experimentally validated using a laboratory prototype that features three-phase voltage-source converters.

0.21

Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids

eess.SY ·2026-08-12 ·Juho Määttä, Marko Hinkkanen, Tuure Nurminen, Orcun Karaca, Rayane Mourouvin +2 more
similarity 0.63
Abstract

This article proposes a grid-forming control method for operation under unbalanced grid-voltage conditions. The method regulates the positive-sequence active power delivered to the grid and actively suppresses the negative-sequence converter voltage, controlling the voltage magnitude to be constant also during unbalanced faults when within the physical limits of the converter. Only the converter current is measured on the AC side, and a disturbance observer is used for synchronization as well as providing integral and resonant action. Estimates for the positive- and negative-sequence grid voltage are obtained from the disturbance observer. A current-limitation scheme for both balanced and unbalanced faults is integrated. Comprehensive stability analysis and tuning guidelines are provided. Experimental results using a 12.5-kVA converter demonstrate that the proposed method can operate during severe balanced and unbalanced faults.

0.04

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.61
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.60
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Impact of Reduced-Order Modelling on Sum-of-Squares Region-of-Attraction Certification for Grid-Forming and Grid-Following Converters

eess.SY math.OC ·2026-11-10 ·Chenxi Yuan, Jeremy D. Watson, Neville R. Watson
similarity 0.55
Abstract · 13 pages, 5 figures, 3 tables

With the increasing penetration of power-electronic equipment, the transient stability of grid-forming (GFM) and grid-following (GFL) converters is increasingly characterized through the region of attraction (ROA) of the post-fault equilibrium. Sum-of-squares (SOS) programming yields certified inner approximations of the ROA, yet its computational cost grows rapidly with system order. Reduced-order models are therefore widely used to reduce computational cost and, more importantly, to enable analytical investigation. However, ROA analyses based on these models often assume that reproducing the converter's transient response, or retaining more dynamics in the correct time-frame, is sufficient to preserve the ROA of the full-order system. Using time-domain ODE simulations as a reference, the SOS-based ROA of each reduced-order GFM and GFL model is assessed against both its own simulated ROA and that of the corresponding full-order model, thereby separating SOS-induced conservativeness from model-order-induced ROA distortion. The results indicate that increasing reduced-order model complexity does not necessarily improve SOS-based ROA fidelity. In the cases examined, more complex reduced-order models yield lower SOS coverage of the full-order reference ROA, despite closer ODE-boundary agreement in some regions. Model selection should therefore consider both full-order ROA fidelity and certified coverage of the practical operating range, rather than model complexity alone.

0.27

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.55
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Constrained Grid-Forming Control for Photovoltaic Systems: A Control Barrier Function Approach

eess.SY ·2026-10-13 ·Amir Afshari, Dominic Groß
similarity 0.54
Abstract

This paper leverages control barrier functions (CBFs) to systematically account for constraints of voltage source converters (VSCs) and photovoltaic (PV) resources in grid-forming (GFM) control. The proposed control combines (unconstrained) dual-port GFM control with control barrier functions (CBFs) to ensure reliable and safe operation of a GFM PV system under grid faults, sudden changes in irradiance, and load perturbations. First, CBFs are used to encode physical and operational limits of the PV system, namely current and voltage limits at its ac and dc terminals. Then, CBFs are used to restrict the dynamics of dual-port GFM control to within the VSC and PV limits during both transient and steady states. To this end, a cost function is defined that encodes trade-offs between forming the ac voltage phase angle/frequency and voltage magnitude under constraints. Then, real-time optimization is used to make the least modification, as measured by the cost function, to the (unconstrained) dual-port GFM control state to remain within the safe set encoded by the CBFs. Finally, the performance of the developed constrained GFM control is evaluated through EMT simulations in MATLAB/Simulink.

0.28