CS Paper Radar

Disturbance-Observer-Based Grid-Forming Control for Unbalanced Grids

Juho Määttä, Marko Hinkkanen, Tuure Nurminen, Orcun Karaca, Rayane Mourouvin, Jarno Kukkola, Lennart Harnefors

eess.SY ·submitted 2026-08-12 09:45 UTC · v1

Abstract

This article proposes a grid-forming control method for operation under unbalanced grid-voltage conditions. The method regulates the positive-sequence active power delivered to the grid and actively suppresses the negative-sequence converter voltage, controlling the voltage magnitude to be constant also during unbalanced faults when within the physical limits of the converter. Only the converter current is measured on the AC side, and a disturbance observer is used for synchronization as well as providing integral and resonant action. Estimates for the positive- and negative-sequence grid voltage are obtained from the disturbance observer. A current-limitation scheme for both balanced and unbalanced faults is integrated. Comprehensive stability analysis and tuning guidelines are provided. Experimental results using a 12.5-kVA converter demonstrate that the proposed method can operate during severe balanced and unbalanced faults.

Closest papers

Nearest neighbours by meaning across the whole index.

Comparison of Current-Limiting Strategies for Grid-Forming Converters Under Grid Faults

eess.SY ·2026-10-17 ·Maitraya Avadhut Desai, Ramona Stoll, Xiuqiang He, Florian Dörfler, Gabriela Hug
published similarity 0.63
Abstract · Presented at the 16th IEEE PowerTech Conference (Kiel 2025). 6 pages, 12 figures

This paper investigates the performance of three state-of-the-art current-limiting strategies for grid-forming (GFM) converters under grid faults. These highly effective strategies include virtual admittance control, virtual admittance control enhanced with virtual power feedback, and the recently developed cross-forming control. The performance comparison addresses two crucial requirements for GFM converters under grid faults, namely transient stability and reactive current injection. The comparison indicates that the virtual admittance control enhanced with virtual power feedback shows the most promising transient stability performance, while the cross-forming control exhibits superior reactive current injection performance. Thus, individual benefits of each strategy can be obtained by properly combining them.

0.32

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.61
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

Transient Triggering Grid-Forming Synchronization Control Under Voltage and Frequency Dips

eess.SY ·2026-09-30 ·Dewan Mahnaaz Mahmud, Vinu Thomas, Bogdan Marinescu, Mickaël Hilairet
benchmark similarity 0.59
Abstract

Grid-forming (GFM) inverters are gaining attention as a promising alternative for conventional synchronous generators in the modern power systems. Unlike conventional synchronous generators, GFM inverters have limited overcurrent capability that makes them vulnerable during large disturbances. During disturbances i.e., voltage and frequency dips, GFM inverters are pushed into current-limited operation to protect the semiconductor switches. This causes the internal angle of the GFM inverters to accelerate and lose synchronism with the rest of the grid. To address this limitation, this article proposes a transient triggering grid-forming (TTGFM) synchronization control to enhance the synchronization stability performance under voltage and frequency dips. This method uses two feedback signals; terminal voltage and the difference between unsaturated and saturated power to adjust the internal angle which is generated by power synchronization loop (PSL) of the GFM inverters. These two signals manipulates the internal reference angle generation that act as a virtual braking mechanism. This mechanism limits the angle acceleration during voltage and frequency dips without requiring an extra supervisory signal or parameters to tune. The proposed method is benchmarked against two state-of-the-art synchronization enhancement schemes and validated through high-fidelity electromagnetic transient (EMT) simulations with a grid dynamic equivalent (GDE) model in MATLAB/Simulink\textsuperscript{\textregistered}. An analytical framework is developed to derive the synchronization instability mechanism and the critical limits of the stability margins. Generalization of the GDE model further shows that the TTGFM control is not restricted to a single configuration but is applicable to any standard benchmark system.

0.23

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.59
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.56
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.56
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Model-Free Output-Admittance Reshaping for Stability Enhancement of Grid-Connected Inverters

eess.SY ·2026-10-23 ·Runnan Wang, Wanrong Li, Huawei Yuan, Sinan Li
published similarity 0.55
Abstract · Accepted at the 2026 IEEE PES Australasian Universities Power Engineering Conference (AUPEC)

Grid-connected inverters can be unstable when their current-control loops interact with an uncertain external network. Returning the existing controller to improve damping also alters current tracking because tracking dynamics and output admittance are coupled. This paper adds a local model-free control (MFC) loop around the existing current controller to reduce output admittance while closely preserving nominal current-tracking dynamics. The added loop uses local inverter parameters without an external grid or neighbouring converter model. A Norton formulation separates reference tracking from the current response to terminal-voltage disturbances and establishes a tracking-preservation condition for admittance reshaping. Reducing the disturbance response makes the inverter behave more like an ideal controlled current source. Averaged-model simulations show reductions exceeding 65% in the magnitudes of all four dq output-admittance elements over 10-200 Hz, with closely preserved current-tracking dynamics. Generalised Nyquist analysis predicts small-signal stability for all sampled grid-impedance cases with MFC, compared with 90.0% without MFC.

0.28

Internal-Model-Control-Based Virtual Admittance Emulation for Enhanced Grid-Forming Performance

eess.SY ·2026-09-18 ·Ruzica Cvetanovic, Lazar Stojanovic, Paolo Sbabo, Paolo Mattavelli, Massimo Bongiorno
similarity 0.54
Abstract

The large-scale integration of renewable energy into electrical power systems places a growing reliance on grid-forming converters (GFMs) to overcome critical stability and control hurdles. By emulating a slowly varying voltage source behind a tunable resistive?inductive impedance, GFMs enable precise setpoint tracking and vital grid support. In this regard, virtual admittance (VA)-based inner-loop control provides exceptional flexibility in shaping the converter's small-signal immittance at connection terminals, allowing for advanced GFM functionalities. This article addresses a novel internal-model-control-based VA approach, which inherently accounts for the effects of the inner current-control loop and the voltage feedforward. Unlike the state-of-the-art VA control, the proposed VA control ensures that, at frequencies outside the influence of outer loops, the converter's terminal admittance closely matches the target admittance, which is shown to be relevant for stability. It is revealed how, with the state-of-the art VA control, a small-signal instability in the harmonic range may arise if a low-pass filter with a high cut-off frequency is used for the voltage feedforward. However, the proposed VA control ensures stable operation regardless of this cut-off frequency. The methodology is experimentally validated using a laboratory prototype that features three-phase voltage-source converters.

0.21