CS Paper Radar

Guidelines for the implementation of power oscillation damping controllers in power converters

Javier Renedo, Macarena Martín Almenta, Sergio Martínez Villanueva, Agustín Díaz-García, Antonio Cordón, Davide Gotti

eess.SY ·submitted 2026-09-02 16:52 UTC · v1

Abstract

One of the most effective ways to damp electromechanical oscillations in power systems is by means of supplementary controllers attached to the different devices in the power system is by means of power system stabilizers (PSS) in synchronous machines or by means of power oscillation damping (POD) controllers in facilities with power converters. In the recent years, the use of POD controllers in voltage source converters (VSCs) with grid-following (GFL) control has been investigated. Although the potential of POD controllers to help to damp inter-area oscillations in power systems is enormous, their correct implementation is not trivial, because their effectiveness is strongly linked to their settings. This paper provides guidelines for the implementation of POD controllers in power converters for application in real-world power systems. The paper proposes compliance criteria for POD controllers using a synthetic test system and a systematic methodology used in Spanish technical standard for monitoring compliance (NTS), considering practical considerations. The paper also includes numerical examples to illustrate compliance criteria for POD controllers in a synthetic test system. A generic power converter with grid-following (GFL) control is used for the analysis by simulation and POD controllers using modulation of active-power injection (POD-P), reactive-power injection (POD-Q) or both simultaneously (POD-PQ) will be analysed. Results were validated in a large-scale power system. The paper concludes that by using appropriate synthetic systems, methodologies and compliance criteria, POD controllers in power converters could be effective to damp electromechanical oscillation in large-scale power systems.

Closest papers

Nearest neighbours by meaning across the whole index.

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.67
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.33

GFM Control Automatic Compliance Toolbox

eess.SY ·2026-11-08 ·Tejas Kunbi, Rahul Rane, Dan Wu, Aleksandra Lekić
similarity 0.63
Abstract

The increasing penetration of converter-interfaced generation reduces system inertia, short-circuit strength, and voltage support. European grid codes, including the ENTSO-E Network Code on Requirements for Generators and the ACER Demand Connection Code, now define disturbance-based validation procedures for grid-forming (GFM) generation and converter-based demand. Commercial RMS tools, however, lack an integrated workflow aligned with these recent requirements. This paper presents an automated Python-PowerFactory compliance toolbox and an RMS test bench for a co-located system comprising a 1 MW GFM photovoltaic (PV) plant, a 0.3 MW GFM battery energy storage system (BESS), and a 1 MW converter-interfaced dynamic load at a 20 kV point of common coupling fed from a 110 kV grid. Extended virtual synchronous machine models and a DCC-oriented load model are tested in batch, with results automatically extracted and plotted for assessment. Results show compliant RMS performance for the slower, electromechanical tests, while the paper identifies which tests require complementary electromagnetic transient (EMT) verification.

0.34

Tests on the POD-P controller of INELFE Spain-France VSC-HVDC interconnector

eess.SY ·2026-09-02 ·Javier Renedo, Agustín Diaz-García, Gilles Torresan, Eduardo Lorenzo Cabrera, Antonio Cordón +9 more
unusual similarity 0.61
Abstract

INELFE interconnector consists of a 2x1000 MW high voltage direct current system based on voltage source converters (VSC-HVDC) interconnecting France and Spain. INELFE VSC-HVDC link is embedded into the high voltage alternating current (HVAC) system. Electromechanical oscillations, also known as power oscillations, are a major concern worldwide. INELFE VSC-HVDC link has specific controllers to damp power oscillations by modulating active (P)- and reactive (Q)-power injections of the VSC converters (POD-P and POD-Q controllers, respectively). The Spanish and French Transmission System Operators (TSOs) carried out a join task force to - Increase the gain of POD-P controller of INELFE VSC-HVDC link. - Make it possible to use the POD-P controller together with angle difference control (ADC) of INELFE VSC-HVDC interconnector. The objective of these modifications is to improve the effectiveness of POD-P controller and, therefore, to increase its contribution to the damping of inter-area oscillations in the Continental Europe (CE) power system. Such changes require (a) extensive simulation studies and (b) extensive tests in different operation modes, in order to ensure the correct behavior of the system. This paper presents simulation studies and field tests on the POD-P controller of INELFE VSC-HVDC interconnector in different modes of operation.

0.62

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.59
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.57
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

eess.SY ·2026-11-02 ·Alan Valadez, George Weiss, Chunjiang Jia, Chong Ng
published similarity 0.55
Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

0.62

DC Voltage Control Dominated Oscillations in Electromechanical Frequency Range - Insights from Synchronous Coefficient Reduction Effect of IBR Plants and Network Interactions

eess.SY ·2026-11-09 ·Qiang Fu, Siqi Bu
top venue similarity 0.55
Abstract

Large-scale integration of inverter-based resources (IBRs) is widely known to cause subsynchronous oscillations. This paper investigates a distinct class of oscillations that occur in the electromechanical frequency range (EFR), referred to as EFOs, and are dominated by the DC voltage control (DVC) loops of grid-following IBRs rather than synchronous generator-like controls or phase-locked loops (PLLs). Although open-loop oscillation modes of DVC loops are subsynchronous, the corresponding closed-loop dominant oscillation mode related to DVC can shift downward into the EFR without retuning the control parameters. This frequency shift is caused by network-mediated interactions among the IBRs, which introduce a negative synchronous coefficient into the DVC oscillation loop. This synchronous coefficient reduction effect (SCRE) becomes stronger as the IBR plant scale increases and/or as the minimum eigenvalue of the network admittance matrix decreases. Furthermore, a complex vector-based stability analysis method is proposed, and a stability criterion for DVC-EFOs is derived. Finally, the analytical conclusions are validated using a practical power system configuration implemented in Simulink. The SCRE differs from traditional explanations, in which the open-loop oscillation modes are already located in the EFR, and provides new insight into DVC-dominated oscillations in the EFR for integration of IBR plants.

0.54

Stability Analysis in IBR-Dominated Grids: Model-Based and Data-Driven Methodologies

eess.SY ·2026-10-15 ·Federico Cecati, Yang Wu, Florian Dörfler, Marco Liserre, Xiongfei Wang +1 more
similarity 0.55
Abstract · Submitted to IEEE Transactions on Power Electronics

Stability issues in converter-dominated grids have a multifold nature, where static, small-signal and large-signal phenomena can influence each other. Capturing the interplay among these different stability aspects requires a rethinking of conventional modeling and analysis tools for power systems. As a further complication, Intellectual Property protection among manufacturers and system operators makes detailed converters and grid models unattainable. This motivates the use of data-driven approaches for stability analysis and control, nevertheless achieving an insightful representation of static, small-signal and large-signal phenomena from data still leaves many open questions. This paper discusses model-based and data-driven methodologies for stability analysis of converter-dominated grids. The instability mechanisms of static, small-signal and large-signal phenomena are conceptually explained, and the capability of different modeling and analysis tools to investigate them is examined. The effectiveness of data-driven methodologies to analyze instability phenomena in their multifold nature is debated, and the challenges on data completeness, model generalization under untrained conditions, physical interpretability, and uncertainty awareness are discussed.

0.16