CS Paper Radar

DC Voltage Control Dominated Oscillations in Electromechanical Frequency Range - Insights from Synchronous Coefficient Reduction Effect of IBR Plants and Network Interactions

Qiang Fu, Siqi Bu

eess.SY ·submitted 2026-11-09 10:48 UTC · v1
top venue

Abstract

Large-scale integration of inverter-based resources (IBRs) is widely known to cause subsynchronous oscillations. This paper investigates a distinct class of oscillations that occur in the electromechanical frequency range (EFR), referred to as EFOs, and are dominated by the DC voltage control (DVC) loops of grid-following IBRs rather than synchronous generator-like controls or phase-locked loops (PLLs). Although open-loop oscillation modes of DVC loops are subsynchronous, the corresponding closed-loop dominant oscillation mode related to DVC can shift downward into the EFR without retuning the control parameters. This frequency shift is caused by network-mediated interactions among the IBRs, which introduce a negative synchronous coefficient into the DVC oscillation loop. This synchronous coefficient reduction effect (SCRE) becomes stronger as the IBR plant scale increases and/or as the minimum eigenvalue of the network admittance matrix decreases. Furthermore, a complex vector-based stability analysis method is proposed, and a stability criterion for DVC-EFOs is derived. Finally, the analytical conclusions are validated using a practical power system configuration implemented in Simulink. The SCRE differs from traditional explanations, in which the open-loop oscillation modes are already located in the EFR, and provides new insight into DVC-dominated oscillations in the EFR for integration of IBR plants.

Journal ref
IEEE TRANS.POWER SYSTEMS, 2026
DOI
10.1109/TPWRS.2026.3748529

Closest papers

Nearest neighbours by meaning across the whole index.

Spatial Differences Analysis of Nodal Frequency Considering Frequency-Voltage Coupling

eess.SY ·2026-11-04 ·Xiaodan Li, Donghai Zhu, Zining Liu, Zhu Guo, Jiabing Hu +1 more
similarity 0.71
Abstract

The rising penetration of inverter-based resources (IBRs) brings rich control dynamics that can amplify spatial differences in nodal frequency through frequency-voltage (F-V) coupling. Existing analyses often neglect voltage dynamics or only examine the aggregate frequency, leading to overoptimistic evaluation of frequency security. To address these drawbacks, this paper develops a unified model of synchronous generators (SGs), grid-following (GFL)-IBRs, and grid-forming (GFM)-IBRs based on the magnitude and phase dynamics of equivalent internal electromotive force (EMF). Integrating these source models with network equations yields a sparse implicit closed-loop model, which fully captures the device-network F-V coupling without transfer-matrix inversion. Then, the obtained nodal responses are decomposed into common and differential modes. Using this decomposition, coupling indices and pole-residue analysis reveal how F-V coupling can amplify spatial differences in nodal frequency and how source configuration and parameters modify this effect. Finally, case studies on the modified IEEE 39-bus and 118-bus test systems validate the proposed model and demonstrate its computational efficiency.

0.19

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.64
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.29

Report on Stability Analysis of Islanded Power Systems with Grid-Forming Converters

eess.SY ·2026-10-30 ·Anup Joshi, Luis A. Garcia-Reyes, Qingyuan Gong, Xavier Guillaud, Javier Renedo +1 more
published similarity 0.63
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

Islanded power systems are inherently challenging to operate due to limited interconnection, low inertia, and weak short-circuit strength. As renewable and inverter-based resources replace synchronous machines, these challenges worsen, causing faster frequency deviations, greater voltage volatility, and higher risk of instability. This report summarizes the differences between islanded and interconnected systems and reviews key stability issues in islanded grids: frequency stability, converter-driven interactions, voltage stability, large-disturbance behavior, and small-signal dynamics. Grid-forming (GFM) voltage source converters are a promising solution because they can establish voltage and frequency, emulate synchronous machine behavior, and provide grid strength, virtual inertia, fast frequency response, voltage regulation, and black-start capability. The report examines relevant GFM control strategies and evaluates their capabilities in weak, low-inertia islanded grids. Challenges remain, particularly interoperability, control coordination among multiple inverter-based resources, lack of standardized grid code requirements, and coordination of protection devices. Successful deployment requires advances in interoperability, harmonized grid codes, and grid planning that considers the unique features of islanded systems, along with clear GFM functionality requirements. Finally, a case study illustrates the stability-enhancing capability of GFM converters in weak grids through small-signal stability analysis. Overall, GFM technology is a key enabler of reliable, renewable-dominant island power systems, but broader adoption depends on continued technical and regulatory development.

0.36

Enhancing Transient Stability of VSG-Controlled Converters Under Grid Frequency Disturbances

eess.SY ·2026-11-13 ·B. Li, Y. Zhang, X. Wang, S. Yang, Z. Hao +1 more
similarity 0.63
Abstract

Strong damping feedback can substantially improve the transient synchronization stability of renewable energy converters employing virtual synchronous generator (VSG) control. However, conventional damping feedback uses the nominal frequency as its reference. When the frequency of a weak grid deviates from nominal, strong damping tends to keep the VSG frequency near nominal. This can sustain a frequency difference between the VSG and the grid and compromise transient synchronization. To address this problem, this paper proposes a complex-frequency-based method to estimate the grid reference frequency from local terminal measurements. The estimated frequency replaces the nominal reference in the VSG synchronization loop, so that damping acts on the frequency difference between the VSG and the real grid. Controller hardware-in-the-loop tests validate the effectiveness of the proposed method under grid frequency disturbances and its robustness to grid parameter uncertainty and adverse grid conditions.

0.26

Beyond Scalar Inertia: Frequency-Response-Based Assessment of Finite-Duration Inertial Support in Grid-Forming Converters

eess.SY ·2026-11-13 ·Ziqi Zhou, Mahdieh S. Sadabadi, Sante Pugliese, Xiaoqiang Li, Xiaojie Wu +1 more
hot direction similarity 0.61
Abstract · This paper has 6 pages with 5 figures. The target journal will be determined at a later stage

Conventional scalar inertia characterizes only the low-frequency terminal behavior of grid-forming converters (GFMs) and cannot fully predict inertial energy delivery during short-duration frequency disturbances. This letter proposes a frequency-response-based method to assess finite-duration inertial support using complex terminal power--frequency responses, such as those provided by Network Frequency Perturbation (NFP) plots. For GFMs with nonzero steady-state droop, a duration-dependent energy-equivalent inertia is defined after subtracting the ideal static-droop contribution. An exact spectral relationship is established, expressing this metric as a duration-weighted integral of frequency-dependent inertia, without requiring knowledge of the internal controller structure and parameters. The duration dependence of the metric is further shown to encode observable oscillation frequencies and damping ratios. A coefficient-decoupling GFM control with identical scalar inertia and droop across different settings is used for verification.

0.27

Spatial-Frequency Control Authority of Grid-Forming Inverters over Voltage Waveforms in Distribution Feeders

eess.SY ·2026-10-20 ·Amir H. Abolmasoumi, Hamed Mohsenian-Rad
published similarity 0.61
Abstract · Accepted at the 2027 IEEE PES Grid Edge Technologies Conference & Exposition, Salt Lake City, Utah, April 19-22, 2027. 5 pages

This paper develops a spatial-frequency framework to quantify the impact of distributed energy resources with grid-forming inverters (GFMs) on voltage waveforms at different locations along a feeder. An analytical authority function is formulated to characterize how controllability varies with both electrical distance from the point of common coupling (PCC) and frequency. It is shown that the GFM control authority generally decays with both distance and frequency, reflecting the limited ability of inverter actions to influence voltage waveforms at distant points. To better capture controllability near resonance, a relative dominance metric is introduced to compare the influence of inverter-induced and grid-induced voltages at a given location and frequency. These results highlight that waveform controllability is fundamentally a spatial-frequency phenomenon along the feeder. Simulation studies validate the analytical findings by demonstrating both the spatial decay of control effectiveness along the feeder and the frequency-dependent trends in control authority in a realistic electromagnetic transient setting. The proposed framework provides insights into the placement and coordination of GFMs to enable effective waveform-level voltage control across electrical distance along the feeder.

0.29

An Integrated EMT Small-Signal Stability Analysis Tool for Power Systems with High Inverter-Based Resource Penetration

eess.SY ·2026-09-14 ·Zihao Qin, Xiaonan Lu, Shuan Dong, Jin Tan
published similarity 0.60
Abstract · 6 pages, 4 figures, 2 tables. Accepted for presentation at the 2026 IEEE Industry Applications Society (IAS) Annual Meeting

The ongoing replacement of synchronous generation by inverter-based resources (IBRs) introduces fast converter control dynamics whose characteristic frequencies extend beyond the classical electromechanical band. Conventional small-signal stability tools are commonly formulated in the phasor domain, representing electrical quantities as slowly varying phasors at the fundamental frequency, and therefore cannot resolve the sub-synchronous and converter-driven dynamics that increasingly arise in operation. Electromagnetic Transient (EMT) modeling captures these dynamics, but established EMT simulators produce time-domain waveforms rather than the modal indicators (eigenvalues, damping ratios, and participation factors) needed to assess stability risk. This paper presents EMT-SSA, an integrated tool suite for EMT-level small-signal analysis of IBR-rich power systems. From a standard PSS/E system snapshot (.raw/.dyr), it converts the model into an EMT representation with enhanced fidelity, solves an extended power flow for the steady-state equilibrium points of both the network and the device controllers, and linearizes a full-order EMT model to form the system state matrix, from which it produces eigenvalues, oscillation modes, and participation factor analysis results over a device library spanning synchronous generators, grid-following and grid-forming inverters, transmission lines, and loads. The EMT-SSA tool suite identifies poorly damped or unstable modes and attributes them to specific devices. The tool is demonstrated on the Kundur two-area system, with its modal results benchmarked against PSS/E NEVA.

0.16

Limitations of RMS-based Stability Assessment of Converter-based Grids: A Case Study

eess.SY ·2026-08-19 ·Pol Jane-Soneira, Ognjen Stanojev, Francisco Canales Perez, Qian Long, Mario Schweizer +1 more
similarity 0.58
Abstract

The increasing penetration of power electronic converters in industrial grids introduces stability challenges at frequencies well above the electromechanical range of traditional power systems. Commercial software tools typically perform eigenvalue-based stability analysis using root-mean-square (RMS) models that assume a quasi-stationary network, thereby neglecting electromagnetic dynamics of assets --- which is standard practice in power system analysis. This paper presents a case study of an industrial grid where the conventional RMS-based eigenvalue analysis predicts stable operation, while a detailed electromagnetic transient (EMT) simulation reveals growing oscillations, indicating instability. To bridge this gap, we introduce an alternative modeling approach that formulates the network dynamics in the rotating $dq$ reference frame, retaining the differential equations of electromagnetic dynamics. The resulting model enables eigenvalue analysis that correctly identifies the unstable modes, consistent with the EMT simulation results. Our findings highlight a fundamental limitation of RMS-based stability assessment for converter-dominated grids and demonstrate that dynamic impedance models in the dq frame provide a viable path toward accurate small-signal analysis encompassing high-frequency converter-network interactions.

0.32