CS Paper Radar

Optimal Coordination of Multiple Ancillary Service Provisions in Active Distribution Networks

Xinbao Jia, Yi Guo, Ognjen Stanojev, Zhen Chen, Yuning Jiang, Jian Sun

eess.SY ·submitted 2026-11-14 13:26 UTC · v1

Abstract

We propose a multi-rate model predictive control (MPC) framework for coordinating primary frequency control (PFC), automatic generation control (AGC), and voltage control (VC) in active distribution networks. The framework allocates distributed energy resource (DER) flexibility among these three ancillary services while retaining their different update rates. To account for the intertemporal flexibility of electric vehicle aggregations and aggregations of buildings with thermostatically controlled loads (TCLs), we incorporate time-varying power-energy envelopes into our multi-rate MPC formulation. These constraints couple the combined PFC and AGC response to the demand-side flexibility available later in the prediction horizon. Furthermore, the input-multirate structure enables coordinated ancillary service provision by DERs with different response dynamics. The controller optimizes the three services together, allowing fast regulation to be coordinated with the developing slow response within the available DER flexibility. We demonstrate the coordinated provision of the three ancillary services through closed-loop simulations on a modified IEEE 33-bus system using a nonlinear differential-algebraic model.

Comment
16 pages

Closest papers

Nearest neighbours by meaning across the whole index.

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.73
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12

Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

eess.SY ·2026-10-12 ·Rida Fatima, Hassan Zahid Butt, Xingpeng Li
similarity 0.66
Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

0.29

Approximating Energy-Regulation Feasible Region of Virtual Power Plants: A Data-driven Inverse Optimization Approach

eess.SY math.OC ·2026-08-26 ·Ruike Lyu, Hongye Guo, Qixin Chen
publishedhighly cited similarity 0.63
Abstract · Published in: 2024 IEEE Power & Energy Society General Meeting (PESGM)

System operators will probably allow virtual power plants (VPPs) to submit their feasible region (FR) for market clearing and dispatch. A VPP needs to determine its FR to submit as a whole based on the individual operation model of its internal distributed energy resources (DERs), which is an FR aggregation problem. Existing FR aggregation approaches rely on analytical methods, which have issues with generality and adaptability. In this paper, we propose a data-driven approach to approximate the energy-regulation FR of VPPs. It adopts the virtual battery model to approximate the aggregate FR of a VPP and determines the model parameters through inverse optimization based on generated multi-scenario operation data using the original operation model. Numerical tests verified the accuracy of the proposed method. We believe that our work helps to better leverage the flexibility of DERs.

0.63

Real-Time Operation Strategy of Virtual Power Plants With Optimal Power Disaggregation Among Heterogeneous Resources

eess.SY ·2026-08-27 ·Qixin Chen, Ruike Lyu, Hongye Guo, Xiangbo Su
publishedhot directionhighly cited similarity 0.61
Abstract · Accepted by Applied Energy

The virtual power plant (VPP) can aggregate flexible resources on the demand side to provide frequency regulation for the grid, helping address the supply-demand balance challenges. When deploying regulation, the VPP disaggregates the requested power adjustment in real time among its internal heterogeneous resources. Achieving optimal power disaggregation in this process is challenging due to the temporal coupling characteristics of the resources, the uncertain regulation signals, and the requirement for fast response. Therefore, existing research relies on heuristic methods, such as proportional disaggregation, and fails to leverage the heterogeneity of multiple resources. Here, we propose an optimal operation strategy for VPPs to provide regulation, exploiting the complementary characteristics of heterogeneous resources by prioritizing the use of low-cost resources while considering temporal coupling. To reduce the computational overhead of online deployment, we further propose a fast disaggregation algorithm to eliminate the reliance on optimisation solvers. We conducted case studies on the operation of a VPP composed of resources including thermostatically controlled loads and industrial production processes. The results verified the reduced operation cost and increased profit of the VPP under the proposed strategy, with only milliseconds of online computation time. We believe that our work can help better exploit demand-side flexibility.

0.62

Grid-Responsive Pricing of Dynamic Wireless Charging with Coupled Residential Demand

eess.SY math.OC ·2026-11-17 ·Zhiheng Wang, Dipanjan Ghose, S. Sivaranjani, Junjie Qin, Qin Lv
similarity 0.61
Abstract · 5 pages, 2 figures. Submitted to the IEEE Power & Energy Society General Meeting (PESGM) 2027

Dynamic wireless charging (DWC) is an emerging technology that enables electric vehicles (EVs) to recharge while traveling. Its unique operational model creates two revenue streams for DWC operators through lane access tolls and electricity sales. However, these prices influence not only traffic flow and roadway energy delivery but also how much EV charging moves to homes instead, potentially within the same distribution network. Neglecting this coupling can underestimate grid loading and compromise pricing decisions. We develop a coupled traffic, EV energy, driver-response, and AC distribution network model with a model predictive control (MPC) framework that jointly optimizes DWC tolls and charging prices while explicitly accounting for displaced residential charging and network losses. Using 78 days of I-210 West traffic data, we show that conventional MPC exceeds feeder loading limits on 52 days, whereas the proposed residential load aware controller eliminates these violations with only 0.6% lower operator revenue. Under a more constrained feeder configuration, it eliminates 50 overloaded days with a 0.9% revenue reduction. Sensitivity analyses highlight the importance of accurate residential demand estimation and feeder loss modeling, while peak-aware pricing further reduces daily peak loading by 3.7% relative to the base load. These results demonstrate the value of coordinated pricing that captures the interaction between roadway and residential charging.

0.20

A Novel Asymmetric Distributed Voltage Regulation Scheme to Enhance the Utilization of Distributed Energy Resources

eess.SY ·2026-11-05 ·Madhura Sondharangalla, Dan Moldovan, Raja Ayyanar
published similarity 0.61
Abstract

Passive voltage regulation in distribution grids using distributed energy resources (DERs) is becoming the standard for feeder voltage management in both under-voltage and over-voltage scenarios. Their simple control, ease of implementation, and fast response make them ideal for distribution feeders with high-DER penetration. This paper proposes a novel distributed voltage control for DERs based on the voltage at the point of common coupling, inverter rating, and operating active power. The proposed control is designed to utilize feeder inverters efficiently to reduce the burden on the inverters in both under-voltage and over-voltage operations and increase the fairness in reactive power ($Q$) support in over-voltage operations. The proposed control is implemented in static and dynamic simulations of a real feeder to validate the performance. Results for the under-voltage scenario are also presented in the paper.

0.36

Headroom-Aware Stochastic Adaptive Model Predictive Control for Load Frequency Control in Microgrids

eess.SY ·2026-09-04 ·Erfan Mehdipour Abadi, Shuo Yuan, Le Yi Wang, Caisheng Wang, Feng Lin
similarity 0.61
Abstract

As the penetration of inverter-based resources (IBRs) increases in microgrids, they are increasingly expected to play a greater role in load frequency control (LFC). Model predictive control (MPC) is attractive for LFC because it incorporates system dynamics and operational constraints. However, most MPC-based LFC formulations rely on fixed reserve headroom based on forecasted renewable availability or storage systems. Under short-term renewable intermittency, IBR headroom is stochastic and time-varying, causing optimal control commands to exceed the physically deliverable regulation capability and cause stochastic saturation. This control-actuator mismatch degrades LFC performance. Accordingly, this study develops two headroom-aware strategies for PV-dominated microgrids. First, stochastic headroom constrained MPC (SHCMPC) incorporates headroom predictions through time-varying input constraints to enforce control feasibility. Second, stochastic adaptive MPC (SAMPC) embeds headroom awareness into the MPC objective function by adaptively penalizing control actions based on predicted headroom, reducing reliance on units with limited headroom without hard time-varying constraints. Simulation results show that stochastic saturation degrades conventional MPC-based LFC, particularly under tight reserve margins. Both strategies improve regulation performance. SHCMPC eliminates saturation events, while SAMPC achieves substantial saturation mitigation with lower computational effort, offering a computationally efficient alternative for real-time LFC under stochastic renewable availability.

0.22

Feeder-Aware Service-Conditioned Flexibility of Grid-Interactive Buildings

eess.SY ·2026-10-22 ·Dafang Zhao, Ittetsu Taniguchi, Takao Onoye
similarity 0.61
Abstract

Grid-interactive buildings can adjust demand, but building-feasible power budgets may differ from accepted feeder-head offers. This study addresses a practical question: to what extent can the adjustable electricity consumption of buildings be translated into deliverable flexibility services while satisfying feeder-head operating requirements? To enable a fair comparison, we adopt the same baseline operating schedule, equipment conditions, and post-service recovery requirements for indoor temperature and battery state of charge (SOC). Flexibility is then evaluated under two settings: one considering only building-level constraints, and the other additionally accounting for feeder-head constraints. We first use a simplified network model with explicit security margins to determine a preliminary amount of flexibility that can be committed. The resulting schedule is then validated using a more detailed network simulation via Modelica. If network losses cause the actual response to deviate from the committed response, the electricity consumption of individual buildings is rescheduled. If the required response still cannot be achieved, the committed flexibility level is reduced. The experiments cover multiple service activation times, regulation directions, and service durations. For comparative purposes, we retain the initial optimization result as the reference estimate of the maximum potentially available flexibility, rather than interpreting the failure of a particular subsequent realization attempt as evidence that a larger flexibility level is inherently infeasible. The results demonstrated that 24.51\% of nonzero flexibility contracts were rejected due to feeder-head constraints, 67.04\% of contracts were accepted with some rescheduling and building redispatch, and only 8.09\% of contracts were accepted without any changes.