Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

Rida Fatima, Hassan Zahid Butt, Xingpeng Li

eess.SY ·submitted 2026-10-12 17:14 UTC · v1

Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

Closest papers

Nearest neighbours by meaning across the whole index.

Unlocking AI Data Center Interconnection Capacity Through Coordinated Grid and Data Center Flexibility

eess.SY ·2026-10-04 ·Rida Fatima, Xingpeng Li
similarity 0.74
Abstract

The rapid growth of AI data centers is creating concentrated electricity demands that can exceed available distribution network headroom and delay interconnection. This paper investigates whether capacity can be used effectively by coordinating flexibility on both sides of the interconnection. A day-ahead mixed integer second order cone programming framework maximizes feasible AI data center IT capacity using utility side conservation voltage reduction and network topology reconfiguration, together with data center workload shifting and reserve constrained uninterruptible power supply storage. Background feeder demand uses voltage dependent ZIP models, while the data center is modeled as constant power demand using Training, Inference, and Mixed workload profiles. A two-stage solution first maximizes interconnection capacity and then minimizes feeder losses for the retained capacity, with numerical relaxation screening. Studies on a 116-bus model derived from the IEEE 123-node feeder show that, at the constrained bus-60 connection point, grid side flexibility, driven almost entirely by network reconfiguration, increases feasible IT capacity by approximately 42.5-45.0%, while data center flexibility alone provides approximately 2.1-5.4% gains. Coordinated operation increases feasible IT capacity from approximately 10.5-10.6 MW under BASE operation to 15.3-16.0 MW, corresponding to gains of approximately 45.9-50.8%; the 16.0 MW Inference result is limited by the adopted UPS reserve requirement. Benefits are strongly location dependent and influenced by workload flexibility, deferral duration, PUE, UPS energy and reserve requirements, and feeder loading. Under a combined adverse operating condition, FULL capacity decreases by only 3.4% relative to the nominal Mixed case while retaining substantial additional capacity over BASE.

0.08

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.70
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12

Optimal Coordination of Multiple Ancillary Service Provisions in Active Distribution Networks

eess.SY ·2026-11-14 ·Xinbao Jia, Yi Guo, Ognjen Stanojev, Zhen Chen, Yuning Jiang +1 more
similarity 0.66
Abstract · 16 pages

We propose a multi-rate model predictive control (MPC) framework for coordinating primary frequency control (PFC), automatic generation control (AGC), and voltage control (VC) in active distribution networks. The framework allocates distributed energy resource (DER) flexibility among these three ancillary services while retaining their different update rates. To account for the intertemporal flexibility of electric vehicle aggregations and aggregations of buildings with thermostatically controlled loads (TCLs), we incorporate time-varying power-energy envelopes into our multi-rate MPC formulation. These constraints couple the combined PFC and AGC response to the demand-side flexibility available later in the prediction horizon. Furthermore, the input-multirate structure enables coordinated ancillary service provision by DERs with different response dynamics. The controller optimizes the three services together, allowing fast regulation to be coordinated with the developing slow response within the available DER flexibility. We demonstrate the coordinated provision of the three ancillary services through closed-loop simulations on a modified IEEE 33-bus system using a nonlinear differential-algebraic model.

0.32

Harmonic-Constrained Hosting Capacity of Active Distribution Networks Using ESS Compensation and Certified Adaptive Decision-Tree Envelopes

eess.SY ·2026-11-16 ·Pengyu Ren, Wei Sun, Fei Teng, Gareth Harrison
similarity 0.65
Abstract

Active distribution networks increasingly rely on coordinated inverter-based resources to accommodate renewable generation, while harmonic limits constrain the capacity that can be connected. This paper proposes a harmonic optimal power flow (HOPF) method with active energy-storage-system (ESS) support. ESS charging, discharging and harmonic-current compensation are jointly scheduled under state-of-charge dynamics and a shared converter-current rating. An adaptive decision tree learns voltage-current partitions from OPF operating points. Within each leaf, an affine plane is fitted on an analytic grid and certified as a lower envelope. A disaggregated mixed-integer formulation embeds these envelopes in a second-order-cone-relaxed network model. Annual hourly data are assessed through daily capacity optimization, followed by componentwise capacity aggregation and chronological full-year feasibility validation. In the case study, the OPF reference of 65.572 MW exceeds the adopted harmonic bounds, whereas HOPF without harmonic support yields an annually validated capacity of 56.892 MW. With each generator capacity bounded by its OPF reference, the proposed method recovers the complete reference allocation. Coordinated energy dispatch and harmonic compensation thus recover generation capacity within the installed ESS converter ratings.

0.20

Supporting Data Center Grid Integration via Co-Optimized Battery Energy Storage Sizing and Capacity Allocation

eess.SY math.OC ·2026-11-06 ·Wei Wang, Himanshu Sharma, Thiagarajan Ramachandran
similarity 0.65
Abstract

Interconnecting large data centers can be delayed by grid requirements on demand flexibility, ramping limits, and ride-through performance. This paper proposes an optimization-based framework to size a Battery Energy Storage System (BESS) that accelerates data center grid integration by providing BESS capacity required to meet selected flexibility and grid-support requirements. The model co-optimizes BESS power rating and energy capacity while allocating capability across three services: (i) demand response over a specified duration, (ii) mitigation of high-magnitude, high-frequency load fluctuations through reserved active power with zero net state-of-charge change, and (iii) voltage support via reactive power capability at the point of common coupling. Minute-level operational scheduling enforces state-of-charge feasibility and load ramp constraints, and incorporates a controllable queue of delay-insensitive computing tasks to enhance flexibility. A case study using a real data center load profile demonstrates the proposed method and quantifies the BESS power-energy requirements and operational trade-offs needed to satisfy the multi-service constraints, providing practical guidance for interconnection planning and deployment.

0.05

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.64
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.29

Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage Control

eess.SY ·2026-11-05 ·Siyu Lu, Yang Weng
similarity 0.63
Abstract · 10 pages, 5 figures

Fault-induced transfers of large data centers to backup supply can cause abrupt reductions in grid-served demand. Coordinating reactive-power support to mitigate these transfers requires consideration of facility-specific voltage--duration ride-through characteristics, particularly when support capacity is limited. This paper develops a ride-through-aware extension of quadratic voltage control that assesses voltage deviations relative to the admissible margins specified by these characteristics. We establish four design requirements that jointly express envelope-based severity, duration dependence, and preventive voltage-restoration incentives. Within a multiplicatively gated quadratic class, we derive necessary and sufficient conditions for satisfying these requirements and construct an explicit family of envelope-normalized objectives. We apply the proposed objectives to reactive-power coordination and evaluate their performance on the IEEE 14-bus, New England 39-bus, and NPCC 140-bus systems. Comparisons with Volt/VAR control, conventional nominal-voltage tracking, and recent data-center voltage-control methods demonstrate improved data-center retention under matched reactive-power support constraints. In the IEEE 14-bus study, the proposed controller reduces the mean data-center disconnection rate by 44.8\% and grid-demand loss by 27.4\% compared with the best-performing baseline. These results highlight the benefit of incorporating data-center ride-through requirements into reactive-power allocation.

0.50

Fair Dynamic Operating Envelopes using Distributed Multi-Period Optimal Power Flow and Jain Index for Active Distribution Networks

eess.SY cs.CE ·2026-08-24 ·Pedro Salomão Quessongo, Daniel Gebbran, Clodomiro Unsihuay-Vila
similarity 0.63
Abstract · 10 pages, submitted to CLAGTEE 2026 Conference

Dynamic operating envelopes (DOEs) are increasingly used to publish time-varying export limits that keep distribution networks within operational limits. Purely technical DOE allocation, however, can systematically privilege electrically favorable prosumers, while embedding fairness directly into a single-period optimal power flow (OPF) objective mixes network feasibility, equity and efficiency in a way that obscures the cost of fairness. This paper proposes a two-stage, multi-period framework that addresses both of these. Initially, a technical distributed OPF computes network-feasible export envelopes. The subsequent stage then applies a dynamic aggregate export budget and redistributes capacity through cumulative proportional fairness, limiting the additional curtailment by an admissible efficiency budget. The resulting fair DOEs are treated as first-stage decisions, while battery storage provides scenario-dependent recourse under demand and renewable uncertainty. The operational problem is solved by a calibrated regional alternating direction method of multipliers (ADMM) on a lossless LinDistFlow model and independently validated using AC power flow. We observe a trade-off between increases in curtailment \emph{versus} improvements on fairness, as expected, reaching Jain fairness indices close to unity. Results show that considering both storage (which alleviates curtailment impact) and multi-period fairness (which increases curtailment) is an interesting approach for modern DOE design, which in turn requires a multi-period, co-designed approach.

0.51