CS Paper Radar

Harmonic-Constrained Hosting Capacity of Active Distribution Networks Using ESS Compensation and Certified Adaptive Decision-Tree Envelopes

Pengyu Ren, Wei Sun, Fei Teng, Gareth Harrison

eess.SY ·submitted 2026-11-16 16:25 UTC · v1

Abstract

Active distribution networks increasingly rely on coordinated inverter-based resources to accommodate renewable generation, while harmonic limits constrain the capacity that can be connected. This paper proposes a harmonic optimal power flow (HOPF) method with active energy-storage-system (ESS) support. ESS charging, discharging and harmonic-current compensation are jointly scheduled under state-of-charge dynamics and a shared converter-current rating. An adaptive decision tree learns voltage-current partitions from OPF operating points. Within each leaf, an affine plane is fitted on an analytic grid and certified as a lower envelope. A disaggregated mixed-integer formulation embeds these envelopes in a second-order-cone-relaxed network model. Annual hourly data are assessed through daily capacity optimization, followed by componentwise capacity aggregation and chronological full-year feasibility validation. In the case study, the OPF reference of 65.572 MW exceeds the adopted harmonic bounds, whereas HOPF without harmonic support yields an annually validated capacity of 56.892 MW. With each generator capacity bounded by its OPF reference, the proposed method recovers the complete reference allocation. Coordinated energy dispatch and harmonic compensation thus recover generation capacity within the installed ESS converter ratings.

Closest papers

Nearest neighbours by meaning across the whole index.

Fair Dynamic Operating Envelopes using Distributed Multi-Period Optimal Power Flow and Jain Index for Active Distribution Networks

eess.SY cs.CE ·2026-08-24 ·Pedro Salomão Quessongo, Daniel Gebbran, Clodomiro Unsihuay-Vila
similarity 0.67
Abstract · 10 pages, submitted to CLAGTEE 2026 Conference

Dynamic operating envelopes (DOEs) are increasingly used to publish time-varying export limits that keep distribution networks within operational limits. Purely technical DOE allocation, however, can systematically privilege electrically favorable prosumers, while embedding fairness directly into a single-period optimal power flow (OPF) objective mixes network feasibility, equity and efficiency in a way that obscures the cost of fairness. This paper proposes a two-stage, multi-period framework that addresses both of these. Initially, a technical distributed OPF computes network-feasible export envelopes. The subsequent stage then applies a dynamic aggregate export budget and redistributes capacity through cumulative proportional fairness, limiting the additional curtailment by an admissible efficiency budget. The resulting fair DOEs are treated as first-stage decisions, while battery storage provides scenario-dependent recourse under demand and renewable uncertainty. The operational problem is solved by a calibrated regional alternating direction method of multipliers (ADMM) on a lossless LinDistFlow model and independently validated using AC power flow. We observe a trade-off between increases in curtailment \emph{versus} improvements on fairness, as expected, reaching Jain fairness indices close to unity. Results show that considering both storage (which alleviates curtailment impact) and multi-period fairness (which increases curtailment) is an interesting approach for modern DOE design, which in turn requires a multi-period, co-designed approach.

0.51

Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

eess.SY ·2026-10-12 ·Rida Fatima, Hassan Zahid Butt, Xingpeng Li
similarity 0.65
Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

0.29

Risk Assessment of Fair Multi-Period Dynamic Operating Envelopes under Uncertainty

eess.SY cs.CE ·2026-10-30 ·Pedro Salomão Quessongo, Daniel Gebbran, Wilhiam de Carvalho, Clodomiro Unsihuay-Vila
published similarity 0.65
Abstract

Dynamic operating envelopes (DOEs) can allocate time-varying export capacity to distributed energy resources (DERs), and while they are not intended to make operations immune to voltage violations, they should guide operations to mostly remain inside expected values under changing regimes and residual forecast errors. However, although recent literature proposed many different techniques for implementing DOEs, there is sparse discussion of analyzing and quantifying the risk of using more or less conservative DOEs under uncertain operating regimes. Having this gap in mind, this paper develops a risk-oriented extension of a previously established fair distributed multi-period optimal power flow (OPF) framework, where fair or technical DOEs are fixed as first-stage decisions and the OPF leverages battery energy storage and renewable curtailment as recourse under regime uncertainties. An independent nonlinear AC power flow then computes a resulting ensemble, which is summarized by (i) voltage-violation probability, severity, and a persistence metric for consecutive out-of-band hours, (ii) curtailment and Jain and Gini indices, and (iii) model deviations. Different probability situations are assessed, ranging from uniform, sunny-heavy, night-peak-heavy, and adversarial, which separate the envelope design from the assumed operating distribution. An optional outer loop allows for fine-tuning a fairness--efficiency parameter under explicit violation and persistence budgets. The combination of the outer loop and the overall framework, which quantifies how often and how severely operating limits are exceeded, creates an auditable methodology mixing equitable export allocation, distributed recourse, and AC risk assessment for active distribution network operators, and this framework is assessed using up to 1000 Monte Carlo scenarios per mixture and DOE design.

0.35

Day-ahead Coordination of Virtual Power Plants within Active Distribution Networks using Deterministic Bi-Level Optimization

cs.CE math.OCeess.SY ·2026-09-15 ·Laura M. Barajas-Arguello, Rafael A. Núñez-Rodríguez, Daniel Gebbran, Clodomiro Unsihuay-Vila
theory similarity 0.61
Abstract

This paper proposes a deterministic bilevel optimization framework for the coordinated operation of Virtual Power Plants (VPPs) embedded in an active distribution network. The Distribution System Operator (DSO) acts as the upper-level leader, minimizing a weighted combination of expenditure, active losses and voltage deviation subject to nonlinear AC power flow constraints, while each VPP operates as a lower-level follower that maximizes its profit under the uniform price signal issued by the DSO. Unlike most existing formulations, which linearize the lower-level subproblem to obtain a Mixed-Integer Linear Program (MILP), the proposed model retains the full AC Optimal Power Flow (AC-OPF) equations, producing a bilevel Mixed-Integer Nonlinear Program (MINLP). The lower-level problem is replaced by its Karush-Kuhn-Tucker (KKT) optimality conditions and the Strong Duality Theorem, yielding a single-level Mathematical Program with Equilibrium Constraints (MPEC). Complementarity conditions are then linearized via the Fortuny-Amat big-M transformation. The framework is validated on the IEEE 33-bus feeder over a 24-hour horizon, with four distributed resources aggregated into a single VPP. Compared with individual dispatch against a regulated time-of-use tariff, aggregation reduces active losses by 10.5 %, the accumulated voltage deviation by 18.3 %, and the bus-hours below 0.95 p.u. from 132 to 29. These gains cost 0.31 % in social cost and 0.26 % in DSO expenditure, while the rent of the aggregator is preserved.

0.14

Reliability Value of Long-Duration Energy Storage against Extreme Events in High-Renewable Grids: A Full-Year AC-OPF Assessment

eess.SY ·2026-09-06 ·Jeongdong Kim, Jonggeol Na, Sungho Shin
similarity 0.61
Abstract · 39 pages, 12 figures

Long-duration energy storage (LDES) can mitigate prolonged renewable--load imbalances during Dunkelflaute events, but existing studies rely on zonal or linearized DC network models and inadequately analyze the operational feasibility of the grid across a wide range of full-year renewable, load, and contingency scenarios. To address this gap, this paper introduces a multi-period alternating-current optimal power flow (AC-OPF) formulation that captures the full nonlinear network physics and assesses the reliability value of LDES in high-renewable grids. To evaluate scarcity events spanning multiple days to weeks, full-year operation is modeled as an 8,760-h load-shedding minimization over scenarios sampled from a Gaussian copula model, fitted to 2010--2025 historical wind and bus-level load data, that represents both typical variability and tail events. On a synthetic 200-bus Illinois transmission network, a hybrid fleet of battery energy storage (BESS) and LDES with 50 MW total power reduces annual load shedding by 83.0% on average relative to the base network, versus 68.5% for short-duration BESS alone at equal power. To further account for unexpected line outages throughout the year, the formulation is extended to a multi-day security-constrained AC-OPF. Under N-1contingencies, no feasible operating solution is obtained for the base network, whereas the LDES-equipped network remains feasible in all considered cases, thereby saving the cost of additional generation and transmission capacity. During the contingency period, LDES acts as a backup power supply, requiring only 5.5% more generation on average than the no-contingency base case.

0.21

Explicit Convex Inner Approximation of TSO-DSO Flexibility Regions via Exact Second-order Cone Relaxation in Radial Networks

eess.SY ·2026-10-20 ·Wenyu Liu, Mario Paolone
benchmark similarity 0.61
Abstract · 10 pages, 4 figures

Accurate representations of the flexibility in distribution grids via tractable algorithms are essential for TSO-DSO coordination. However, flexibility region (FR) estimation based on nonlinear optimal power flow (OPF) generally lacks feasibility guarantees, while conventional convex relaxations may suffer from inexactness. This paper proposes a framework for constructing explicit inner approximations of active-reactive power FRs in radial networks based on the augmented relaxed OPF (AR-OPF). First, less-conservative sufficient conditions for the AR-OPF exactness are derived and extended to generalized objectives. Furthermore, an interior-feasibility analysis is established, guaranteeing that the entire region enclosed by the traced boundary is AC feasible under the proposed sufficient conditions. Building on these theoretical results, two adaptive algorithms are developed to construct explicit inner approximations and numerically convex representations of FRs. Numerical evaluations on different benchmark networks demonstrate consistently small relaxation residuals and high flexibility area retention in most cases, showing that the proposed methods provide a grounded approach to construct operationally admissible FRs for TSO-DSO coordination.

0.35

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.59
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12

Optimal Coordination of Multiple Ancillary Service Provisions in Active Distribution Networks

eess.SY ·2026-11-14 ·Xinbao Jia, Yi Guo, Ognjen Stanojev, Zhen Chen, Yuning Jiang +1 more
similarity 0.59
Abstract · 16 pages

We propose a multi-rate model predictive control (MPC) framework for coordinating primary frequency control (PFC), automatic generation control (AGC), and voltage control (VC) in active distribution networks. The framework allocates distributed energy resource (DER) flexibility among these three ancillary services while retaining their different update rates. To account for the intertemporal flexibility of electric vehicle aggregations and aggregations of buildings with thermostatically controlled loads (TCLs), we incorporate time-varying power-energy envelopes into our multi-rate MPC formulation. These constraints couple the combined PFC and AGC response to the demand-side flexibility available later in the prediction horizon. Furthermore, the input-multirate structure enables coordinated ancillary service provision by DERs with different response dynamics. The controller optimizes the three services together, allowing fast regulation to be coordinated with the developing slow response within the available DER flexibility. We demonstrate the coordinated provision of the three ancillary services through closed-loop simulations on a modified IEEE 33-bus system using a nonlinear differential-algebraic model.

0.25