CS Paper Radar

Fair Dynamic Operating Envelopes using Distributed Multi-Period Optimal Power Flow and Jain Index for Active Distribution Networks

Pedro Salomão Quessongo, Daniel Gebbran, Clodomiro Unsihuay-Vila

eess.SY cs.CE ·submitted 2026-08-24 16:15 UTC · v2

Abstract

Dynamic operating envelopes (DOEs) are increasingly used to publish time-varying export limits that keep distribution networks within operational limits. Purely technical DOE allocation, however, can systematically privilege electrically favorable prosumers, while embedding fairness directly into a single-period optimal power flow (OPF) objective mixes network feasibility, equity and efficiency in a way that obscures the cost of fairness. This paper proposes a two-stage, multi-period framework that addresses both of these. Initially, a technical distributed OPF computes network-feasible export envelopes. The subsequent stage then applies a dynamic aggregate export budget and redistributes capacity through cumulative proportional fairness, limiting the additional curtailment by an admissible efficiency budget. The resulting fair DOEs are treated as first-stage decisions, while battery storage provides scenario-dependent recourse under demand and renewable uncertainty. The operational problem is solved by a calibrated regional alternating direction method of multipliers (ADMM) on a lossless LinDistFlow model and independently validated using AC power flow. We observe a trade-off between increases in curtailment \emph{versus} improvements on fairness, as expected, reaching Jain fairness indices close to unity. Results show that considering both storage (which alleviates curtailment impact) and multi-period fairness (which increases curtailment) is an interesting approach for modern DOE design, which in turn requires a multi-period, co-designed approach.

Comment
10 pages, submitted to CLAGTEE 2026 Conference

Closest papers

Nearest neighbours by meaning across the whole index.

Risk Assessment of Fair Multi-Period Dynamic Operating Envelopes under Uncertainty

eess.SY cs.CE ·2026-10-30 ·Pedro Salomão Quessongo, Daniel Gebbran, Wilhiam de Carvalho, Clodomiro Unsihuay-Vila
published similarity 0.79
Abstract

Dynamic operating envelopes (DOEs) can allocate time-varying export capacity to distributed energy resources (DERs), and while they are not intended to make operations immune to voltage violations, they should guide operations to mostly remain inside expected values under changing regimes and residual forecast errors. However, although recent literature proposed many different techniques for implementing DOEs, there is sparse discussion of analyzing and quantifying the risk of using more or less conservative DOEs under uncertain operating regimes. Having this gap in mind, this paper develops a risk-oriented extension of a previously established fair distributed multi-period optimal power flow (OPF) framework, where fair or technical DOEs are fixed as first-stage decisions and the OPF leverages battery energy storage and renewable curtailment as recourse under regime uncertainties. An independent nonlinear AC power flow then computes a resulting ensemble, which is summarized by (i) voltage-violation probability, severity, and a persistence metric for consecutive out-of-band hours, (ii) curtailment and Jain and Gini indices, and (iii) model deviations. Different probability situations are assessed, ranging from uniform, sunny-heavy, night-peak-heavy, and adversarial, which separate the envelope design from the assumed operating distribution. An optional outer loop allows for fine-tuning a fairness--efficiency parameter under explicit violation and persistence budgets. The combination of the outer loop and the overall framework, which quantifies how often and how severely operating limits are exceeded, creates an auditable methodology mixing equitable export allocation, distributed recourse, and AC risk assessment for active distribution network operators, and this framework is assessed using up to 1000 Monte Carlo scenarios per mixture and DOE design.

0.35

DOE-Constrained Distributed Battery Coordination in Unbalanced Distribution Networks

eess.SY ·2026-11-09 ·Bohang Fang, Anderson Toler, Lijun Ding, Wenqi Cui, Cong Chen
similarity 0.69
Abstract · 8 pages; substantially revised version with a new title, revised formulation and theoretical results, and updated numerical results

Dynamic operating envelopes (DOEs) provide injection and withdrawal limits for distributed energy resource scheduling while respecting network operational constraints. This paper develops a risk-aware DOE framework for distributed battery operation in unbalanced three-phase networks using a semidefinite program (SDP). We derive sufficient conditions for exactness of the SDP relaxation, ensuring that the recovered operating points corresponding to the DOE vertices satisfy all voltage and nodal power injection constraints of the original AC network model. The method computes hourly active-power DOEs under uncertain load conditions and incorporates them directly into a 24-hour battery operation problem. On a modified IEEE 13-bus feeder, empirical comparisons with unconstrained arbitrage and local Volt--VAR/Volt--Watt control show that DOE-constrained battery scheduling eliminates the observed out-of-sample voltage violations while retaining 94.6\% of the unconstrained arbitrage profit.

0.29

Harmonic-Constrained Hosting Capacity of Active Distribution Networks Using ESS Compensation and Certified Adaptive Decision-Tree Envelopes

eess.SY ·2026-11-16 ·Pengyu Ren, Wei Sun, Fei Teng, Gareth Harrison
similarity 0.67
Abstract

Active distribution networks increasingly rely on coordinated inverter-based resources to accommodate renewable generation, while harmonic limits constrain the capacity that can be connected. This paper proposes a harmonic optimal power flow (HOPF) method with active energy-storage-system (ESS) support. ESS charging, discharging and harmonic-current compensation are jointly scheduled under state-of-charge dynamics and a shared converter-current rating. An adaptive decision tree learns voltage-current partitions from OPF operating points. Within each leaf, an affine plane is fitted on an analytic grid and certified as a lower envelope. A disaggregated mixed-integer formulation embeds these envelopes in a second-order-cone-relaxed network model. Annual hourly data are assessed through daily capacity optimization, followed by componentwise capacity aggregation and chronological full-year feasibility validation. In the case study, the OPF reference of 65.572 MW exceeds the adopted harmonic bounds, whereas HOPF without harmonic support yields an annually validated capacity of 56.892 MW. With each generator capacity bounded by its OPF reference, the proposed method recovers the complete reference allocation. Coordinated energy dispatch and harmonic compensation thus recover generation capacity within the installed ESS converter ratings.

0.23

Reliability Value of Long-Duration Energy Storage against Extreme Events in High-Renewable Grids: A Full-Year AC-OPF Assessment

eess.SY ·2026-09-06 ·Jeongdong Kim, Jonggeol Na, Sungho Shin
similarity 0.65
Abstract · 39 pages, 12 figures

Long-duration energy storage (LDES) can mitigate prolonged renewable--load imbalances during Dunkelflaute events, but existing studies rely on zonal or linearized DC network models and inadequately analyze the operational feasibility of the grid across a wide range of full-year renewable, load, and contingency scenarios. To address this gap, this paper introduces a multi-period alternating-current optimal power flow (AC-OPF) formulation that captures the full nonlinear network physics and assesses the reliability value of LDES in high-renewable grids. To evaluate scarcity events spanning multiple days to weeks, full-year operation is modeled as an 8,760-h load-shedding minimization over scenarios sampled from a Gaussian copula model, fitted to 2010--2025 historical wind and bus-level load data, that represents both typical variability and tail events. On a synthetic 200-bus Illinois transmission network, a hybrid fleet of battery energy storage (BESS) and LDES with 50 MW total power reduces annual load shedding by 83.0% on average relative to the base network, versus 68.5% for short-duration BESS alone at equal power. To further account for unexpected line outages throughout the year, the formulation is extended to a multi-day security-constrained AC-OPF. Under N-1contingencies, no feasible operating solution is obtained for the base network, whereas the LDES-equipped network remains feasible in all considered cases, thereby saving the cost of additional generation and transmission capacity. During the contingency period, LDES acts as a backup power supply, requiring only 5.5% more generation on average than the no-contingency base case.

0.21

Zero-Sum Power Factor Games

eess.SY math.OC ·2026-08-20 ·Cameron Khanpour, Samuel Talkington, Mathieu Dahan, Daniel K. Molzahn
similarity 0.64
Abstract

Variable active power injections arising from device behavior or compromised dispatch complicate voltage regulation in electric power networks with distributed energy resources (DERs). An operator can limit the resulting voltage deviations by remotely selecting DER reactive power parameters before observing the active power injections. IEEE Standard 1547-2018 specifies constant power factor as one such control mode, coupling each device's reactive power to its realized active power. Using a linear voltage model, we formulate the operator's decision as a robust minimax problem in which the operator minimizes the largest feasible aggregate voltage deviation. We solve this problem by expressing the power factor decisions through continuous reactive to active power ratios and exactly decomposing the payoff according to the signs of the voltage deviations. When every feasible voltage residual remains on its initial side of nominal, the resulting ratios cancel each injection's contribution and yield a closed form minimax strategy. We identify realistic DER ratings for which this strategy applies and quantify the regulation capacity lost under restricted power factor ranges. Numerical tests check the cancellation computation, solve the complete minimax problem directly at a representative DER rating, and compare the linear voltage predictions with nonlinear AC power flow.

0.23

Computation of Price Signals for Controlling Flexible Prosumers in Distribution Grids Incorporating Stochasticity and Fairness

eess.SY ·2026-10-13 ·Plouton Grammatikos, Chloé Voirol, Pierre Roduit, Fabrizio Sossan
similarity 0.64
Abstract

This paper proposes a method for distribution system operators (DSOs) to design spatially fair dynamic price signals for flexible prosumers, accounting for both distribution grid constraints and the stochastic behavior of prosumers. Since locational pricing can introduce price unfairness when grid constraints are active, the proposed approach includes mechanisms to enforce price fairness across the network. The method involves the DSO solving a scenario-based optimal power flow (OPF) problem to derive, similarly to locational marginal prices in transmission systems, the Lagrange multipliers associated with grid constraints and to compute individualized price signals for each prosumer under various PV generation and demand scenarios. Subsequently, two methods are introduced to aggregate these individualized prices into a single fair price across prosumers. Their performance is evaluated through simulations on a model distribution grid, comparing prosumer revenues, grid constraint violations, and analyzing the impact of fairness on reducing cost variance among prosumers.

0.22

Multi-objective Electric Vehicle Charging Strategies at Energy Hubs with Justice-informed Profit Distribution among Users

eess.SY ·2026-11-05 ·Twan Stolwijk, Diego Fernandez-Zapico, Alessandro Piazza, Mauro Salazar
similarity 0.64
Abstract

This paper studies potential energy cost savings in electric vehicle (EV) charging hubs when users allow cooperative vehicle-to-grid (V2G), and how such savings should be redistributed. To this end, we present multi-objective operational strategies and justice-informed profit sharing methods for a charging energy hub equipped with a battery storage system and solar panels. Specifically, we first frame the dynamic energy hub operational problem aiming to minimize a combination of grid costs and emissions, accounting for time-varying prices and energy mix as well as storage system and EV battery degradation, which is especially relevant when considering V2G operations. We parse the problem as a second-order conic program that can be efficiently solved to global optimality. Our real-world case-study shows the importance of flexibility for hub operation: Equipping a charging station with a stationary battery and leveraging dynamic V2G can significantly reduce the total costs and emissions compared to conventional settings without a battery or dynamic charging by more than 10%. To redistribute these cost benefits to users, we compare standard Nash bargaining with a justice-informed sufficientarian version which caps charging prices to safeguard adequate access to affordable charging. Our results show that the sufficientarian approach better accounts for inequalities in flexibility capital without significantly affecting aggregate costs, highlighting how justice-informed pricing only marginally affects total revenues.

0.24

Approximating Energy-Regulation Feasible Region of Virtual Power Plants: A Data-driven Inverse Optimization Approach

eess.SY math.OC ·2026-08-26 ·Ruike Lyu, Hongye Guo, Qixin Chen
publishedhighly cited similarity 0.63
Abstract · Published in: 2024 IEEE Power & Energy Society General Meeting (PESGM)

System operators will probably allow virtual power plants (VPPs) to submit their feasible region (FR) for market clearing and dispatch. A VPP needs to determine its FR to submit as a whole based on the individual operation model of its internal distributed energy resources (DERs), which is an FR aggregation problem. Existing FR aggregation approaches rely on analytical methods, which have issues with generality and adaptability. In this paper, we propose a data-driven approach to approximate the energy-regulation FR of VPPs. It adopts the virtual battery model to approximate the aggregate FR of a VPP and determines the model parameters through inverse optimization based on generated multi-scenario operation data using the original operation model. Numerical tests verified the accuracy of the proposed method. We believe that our work helps to better leverage the flexibility of DERs.

0.63