CS Paper Radar

Fixed-Time Voltage Regulation in Distribution Networks with Impedance Awareness

Nilanjan Roy Chowdhury, Venkatesh Sarangan

eess.SY ·submitted 2026-10-01 10:46 UTC · v1

Abstract

This letter introduces an optimization-based fixed time control algorithm for solving the voltage regulation problem of a radial and balanced power distribution network. The proposed algorithm requires no prior knowledge of the exact network impedance (resistance and reactance), yet guarantees voltage convergence to the predefined safe limit within a fixed time-window. We embrace results from Fixed-time stability (FxTs) and Control Lyapunov function (CLF) to analyze the stability and robustness of the underlying algorithm and then synthesize it leveraging the Quadratic Programming (QP) approach. We first analytically provide sufficient conditions on the control gains and the design parameters, that can ensure voltage regulation in fixed-time. Thereafter we transform the existing voltage regulation problem into an equivalent QP-based optimization framework and translate the aforesaid conditions to find feasible solutions for voltage stability. We empirically verify the efficacy of our proposed algorithm on the IEEE-33 bus distribution network and compare its performance against other existing robust control methods.

Comment
8 pages, 6 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage Control

eess.SY ·2026-11-05 ·Siyu Lu, Yang Weng
similarity 0.67
Abstract · 10 pages, 5 figures

Fault-induced transfers of large data centers to backup supply can cause abrupt reductions in grid-served demand. Coordinating reactive-power support to mitigate these transfers requires consideration of facility-specific voltage--duration ride-through characteristics, particularly when support capacity is limited. This paper develops a ride-through-aware extension of quadratic voltage control that assesses voltage deviations relative to the admissible margins specified by these characteristics. We establish four design requirements that jointly express envelope-based severity, duration dependence, and preventive voltage-restoration incentives. Within a multiplicatively gated quadratic class, we derive necessary and sufficient conditions for satisfying these requirements and construct an explicit family of envelope-normalized objectives. We apply the proposed objectives to reactive-power coordination and evaluate their performance on the IEEE 14-bus, New England 39-bus, and NPCC 140-bus systems. Comparisons with Volt/VAR control, conventional nominal-voltage tracking, and recent data-center voltage-control methods demonstrate improved data-center retention under matched reactive-power support constraints. In the IEEE 14-bus study, the proposed controller reduces the mean data-center disconnection rate by 44.8\% and grid-demand loss by 27.4\% compared with the best-performing baseline. These results highlight the benefit of incorporating data-center ride-through requirements into reactive-power allocation.

0.50

Co-Optimization of Scheduling, Control, and Incentivization of Electric Vehicles for Improving Power System Stability

eess.SY ·2026-10-10 ·Amit Kumer Podder, Tomonori Sadamoto, Aranya Chakrabortty
similarity 0.61
Abstract

We present a finite-horizon, greedy heuristic-based co-optimization and optimal control framework that jointly determines the optimized charging rates, charging times, and an optimal charging control law for electric vehicles (EVs) to improve both voltage stability and small-signal dynamic performance of a power distribution system. The proposed strategy encourages EV drivers to be flexible in choosing their charging rates and times through monetary incentivization under a fixed budget. The design is validated using the IEEE 33-bus distribution system model with ten EV charging stations (EVCSs). Results show that incentivizing drivers to settle for lower charging rates, implemented by a wait-and-save strategy, and rescheduling their charging times strategically can significantly improve the voltage stability index (VSI) of the system as well as the damping factors for the mid-frequency oscillation modes seen in the DC-link bus voltage.

0.20

Controller- and Communication-Aware Flexibility Margins for Electric Distribution Networks

eess.SY ·2026-10-14 ·Saif R. Kazi, Kaarthik Sundar
similarity 0.61
Abstract · 11 pages

This paper develops a framework for quantifying operational flexibility in radial electric distribution systems under coupled active- and reactive-load uncertainty. Flexibility is defined as the largest scaling of a prescribed uncertainty set that can be accommodated while satisfying network and actuator limits under a given control architecture. We consider a one-sided Euclidean set for robust demand-growth capability, with a direct extension to bidirectional variations. Under LinDistFlow, controllable distributed resources and feeder-head exchange with the upstream grid jointly balance active-power disturbances, while local Volt/VAR feedback regulates reactive power. The resulting affine closed-loop disturbance response admits exact second-order-cone robust counterparts. For fixed Volt/VAR gains, a convex reformulation jointly optimizes the flexibility margin and active-power participation factors, including feeder-head participation. A sparse load-to-generator feedforward map further captures communication constraints. Numerical studies on the Iowa-240 feeder demonstrate how the amount of control authority and communication structure shape the achievable flexibility margin.

0.24

A Novel Asymmetric Distributed Voltage Regulation Scheme to Enhance the Utilization of Distributed Energy Resources

eess.SY ·2026-11-05 ·Madhura Sondharangalla, Dan Moldovan, Raja Ayyanar
published similarity 0.60
Abstract

Passive voltage regulation in distribution grids using distributed energy resources (DERs) is becoming the standard for feeder voltage management in both under-voltage and over-voltage scenarios. Their simple control, ease of implementation, and fast response make them ideal for distribution feeders with high-DER penetration. This paper proposes a novel distributed voltage control for DERs based on the voltage at the point of common coupling, inverter rating, and operating active power. The proposed control is designed to utilize feeder inverters efficiently to reduce the burden on the inverters in both under-voltage and over-voltage operations and increase the fairness in reactive power ($Q$) support in over-voltage operations. The proposed control is implemented in static and dynamic simulations of a real feeder to validate the performance. Results for the under-voltage scenario are also presented in the paper.

0.36

Coordinated Conservation Voltage Reduction and Network Topology Reconfiguration in Active Distribution Networks

eess.SY ·2026-10-12 ·Rida Fatima, Hassan Zahid Butt, Xingpeng Li
similarity 0.60
Abstract

Distribution networks rely on conservation voltage reduction (CVR) and network topology reconfiguration (NTR) to manage demand, distributed energy resources (DERs), and tighter operating margins. Yet these strategies are typically deployed independently, despite coupled effects on feeder voltages, losses, and loading. This paper addresses that gap by developing a day-ahead mixed-integer second order cone programming (MISOCP) framework that jointly optimizes feeder head voltage control and network reconfiguration. The formulation incorporates AC branch flow constraints, ZIP load models, DERs, battery energy storage systems, and multi substation radiality. Using modified IEEE 33 bus and 123 bus systems, four configurations isolate the individual and coordinated effects of CVR and NTR. On the 33-bus system under mixed ZIP loading, NTR reduces active energy loss by 2.50%, while coordinated operation reduces it by 2.91% relative to SDN and produces a 2.46% CVR induced active load reduction relative to SDNTR. Under constant impedance loading, coordinated operation reduces active energy loss by 17.65% relative to SDN, while CVR reduces active load by 14.61% relative to SDNTR. DER portfolio scaling shows a nonmonotonic coordinated load reduction response, strongest at 20% penetration and decreasing at higher levels. On the 123 bus system, NTR reduces losses by 19.3%, while CVR reduces voltage dependent load energy by 2.3 to 2.4%. Under loading stress, SDN becomes infeasible at 120% loading, whereas CEDNTR remains feasible. Overall, the results demonstrate complementary, operating condition dependent benefits shaped by load composition, DER portfolio scaling, feeder topology, voltage margins, and source constraints, highlighting the value of joint optimization.

0.29

Safety Verification for Voltage Control in Inverter Dominated Radial Distribution Networks under Actuator and Sensor Adversarial Attacks

eess.SY math.OC ·2026-10-30 ·Georgios Pantazis, Revi Boelen, Michelle S. Chong
benchmark similarity 0.59
Abstract

This paper develops a safety verification framework for inverter-based radial distribution networks under sensor and actuator attacks. Each customer is equipped with a droop-based controller to regulate its voltage within a desirable bound of a reference, i.e., to achieve safety. In our setting, attacks and disturbances enter the droop-based controllers, while actuator attacks corrupt the reactive power injected into the network. Consequently, invariance of the controller state alone does not guarantee compliance with inverter capacities or customer voltage limits. To address this challenge, we derive conditions to guarantee that the reactive power state remains inside a predefined ellipsoid, while at the same time ensuring that the attacked reactive power injections and customer voltages respect predetermined operating limits that hold uniformly for the entire predefined ellipsoid. Together, these conditions guarantee safety under all admissible disturbances and state-dependent sensor and actuator attacks. Finally, we express the resulting containment condition as a linear matrix inequality (LMI) feasibility problem. A five-customer radial network based on the CIGRE benchmark corroborates our theoretical developments in simulations.

0.26

Volt-VAr-Watt Optimization in Four-Wire Low-Voltage Networks: Exact Nonlinear Models and Smooth Approximations - Extended Version

eess.SY ·2026-09-14 ·Sleiman Mhanna, Frederik Geth, Lucas Quiertant, Pierluigi Mancarella
top venue similarity 0.59
Abstract · Extended version of the article published in IEEE Transactions on Power Systems, vol. 41, no. 5, pp. 3663-3677, 2026. DOI: 10.1109/TPWRS.202…

The proliferation of distributed energy resources is increasing the prevalence of both overvoltages and undervoltages in low-voltage (LV) distribution networks. Smart inverter functionalities, such as Volt-VAr and Volt-Watt control, can regulate voltage at the consumer level but are challenging to capture in optimization models due to their nondifferentiability. This paper proposes three nonlinear models for four-wire unbalanced optimal power flow that incorporate these nonsmooth functions without binary or integer variables. The first model encodes these nonsmooth functions directly as user-defined functions using control flow, a feat enabled by many state-of-the-art algebraic modeling languages. The second and third introduce bespoke smooth approximations with tunable approximation errors to address potential numerical issues arising from nondifferentiability, improving reliability while maintaining accuracy. All three methods are evaluated on real four-wire unbalanced LV networks with varying rooftop solar adoption levels, including a 539-bus system with 302 smart inverters. This paper is not only the first to demonstrate accurate, reliable, and tractable Volt-Var-Watt optimization (VVWO) on real four-wire unbalanced LV network models, but it also establishes that optimization-based, non-incremental methods offer superior reliability compared to commonly used incremental (quasi-steady-state) approaches.

0.61

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.59
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12