Data Center Load Reductions: Attribution, Measurement Limits, and Estimation

Abdallah Alalem Albustami, Ahmad F. Taha, Mohammad Alwahdanee, Zuhaib Shakeel Muhammad

eess.SY ·submitted 2026-10-28 03:13 UTC · v1

Abstract

Hundreds of gigawatts of data center loads are seeking interconnection in the United States given the massive growth of artificial intelligence and cloud computing. In recent years, several incidents of data centers reducing their loads by hundreds to thousands of megawatts have been documented, raising grid reliability concerns. U.S. regulators have since ordered reliability standards for the integration of computational loads, and the North American Electric Reliability Corporation (NERC) now calls on transmission owners to install disturbance recorders at these facilities to support root cause analysis. Such recorders usually observe only electrical quantities at the point of interconnection (POI). A sudden load reduction can be caused by a change in workload or a switch to backup supply. This work shows when POI measurements can distinguish the two mechanisms. It is established that they can produce identical POI voltage and current in a quasi-static constant power model, and during the transient their separation depends on the reduction relative to measurement noise, the clearing time, the dynamics through which workload reaches the POI, and the recorder bandwidth. When POI data are insufficient, an estimator that uses workload data is proposed to determine how much of the facility stayed connected. The results of this work identify the measurements and grid information utilities need to determine why data center load dropped.

Closest papers

Nearest neighbours by meaning across the whole index.

Slasher: Power Flexibility for Cloud Datacenters

cs.DC cs.OSeess.SY ·2026-08-26 ·Liuzixuan Lin, Fiodar Kazhamiaka, Alok Gautam Kumbhare, Chaojie Zhang, Jaylen Wang +8 more
similarity 0.67
Abstract · 18 pages, 15 figures

Datacenters consume many megawatts of power, and regularly encounter scenarios that require modulating their power draw. These scenarios include datacenter infrastructure failures, power grid failures, grid services, and more, spanning a diverse range of requirements in terms of the power magnitude, the scope of the reduction, the notice time, and other dimensions. To address these scenarios, we have built Slasher, a general system for modulating the power of \azure datacenters to handle scenarios ranging from individual racks to regional multi-datacenter grid events. Slasher coordinates datacenter resources with the goal of meeting power targets while minimizing negative impact on hosted workloads. In this paper, we review the main power modulation scenarios, characterize the power reduction levers using data from production cloud datacenters, describe Slasher's system architecture, and formulate the cloud datacenter power modulation control problem. We also develop a high-fidelity datacenter simulator and propose a workload impact model, using them to design and evaluate power control algorithms.

0.31

Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

eess.SY ·2026-09-02 ·Pengyu Ren, Wei Sun, Fei Teng
similarity 0.66
Abstract

Large data centers are emerging as concentrated, power-electronic grid loads whose abrupt disconnection or transfer to on-site backup supply during voltage disturbances can remove large demand from the power system, and may create a system-level stability problem. Their interconnection feasibility therefore depends not only on steady-state thermal and voltage limits, but also on whether internal power-conditioning systems can maintain IT service while limiting customer-initiated load reduction. This paper presents a voltage ride-through (VRT)-aware data center and grid co-planning framework that couples transmission-level fault simulation with an internal data center ride-through model. Python-based dynamic simulations generate point-of-interconnection (POI) voltage trajectories under selected network faults, and the resulting waveforms drive an internal model incorporating IT and cooling-load dynamics, DC-link, Uninterruptible Power Supply (UPS) response, and converter apparent power limits. The IEEE 118-bus case study shows that internal VRT capability can become a binding interconnection constraint: steady-state planning alone can overestimate feasible data center capacity, whereas increased UPS converter headroom progressively restores hosting capacity. Under the reduced-order response models studied, the grid-forming mode provides greater ride-through margin than the current-limited grid-following mode under the same network fault conditions. The results further show that VRT constraints can materially change both the total hosting capacity of data centers and its spatial allocation across candidate interconnection buses.

0.16

Comparative Analysis of Large Load Interconnection Requirements Across U.S. Transmission Entities

cs.AR ·2026-10-27 ·Rafi Zahedi, Rahul Anilkumar, Amin Zamani
publishedbenchmark similarity 0.65
Abstract

The rapid growth of large loads, especially data centers driven by artificial intelligence, is creating unprecedented demands on the North American electric grid. Data centers now account for nearly 80% of large load interconnection requests in the Western Interconnection, and U.S. electricity consumption from data centers is projected to reach 325-580 TWh by 2028. Despite this urgency, technical interconnection requirements for large loads have not yet matured and still contain several gaps. This paper presents a comparative analysis of large load interconnection requirements across eleven U.S. entities, including AEP, Ameren, CAISO, Dominion, Duke Energy, ERCOT, LIPA, MISO, PJM, Southern Company, and SPP, under seven technical categories: large load definition, load data and modeling, fault ride-through, load curtailment and shedding, dispatchability, power quality, and reactive power control. The analysis reveals significant variation in both the scope and specificity of requirements. LIPA addresses all seven technical categories at least partially, while Dominion and Duke Energy provide detailed coverage across nearly all categories. The analysis also finds that data center applicants can be viewed as potential grid resources, rather than only as consumers. The findings provide a structured baseline from which utilities, regulators, ISOs/RTOs, and developers can identify gaps, benchmark against peers, and accelerate the development of interconnection standards.

0.33

Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation

eess.SY ·2026-11-12 ·Salish Maharjan, Junyuan Zheng, Lung-An Lee, Min Lwin, Zhaoyu Wang
similarity 0.62
Abstract · 13 pages, 16 figures. Submitted for IEEE publications

Data centers are now one of the fastest-growing loads on the bulk power system, and most of their demand reaches the grid through power converters inside uninterruptible power supplies (UPS). Whether these loads can take part in sub-synchronous control interaction (SSCI), as wind and HVDC converters do, has not been studied extensively. We examine this question with impedance-based frequency scans at the point of common coupling (PCC). Using a detailed proprietary model (INS-ISU), we scan the motor, variable-frequency-drive (VFD), lighting, and UPS-fed information-technology (IT) branches of a representative facility separately. Only the UPS in double-conversion mode shows negative resistance; it covers the whole sub-synchronous band and continues up to about 170 Hz. The other branches, and the UPS in bypass mode, stay passive. We then repeat the scans on three public models from PNNL, TAMU, and NLR. None of them shows negative resistance in bypass mode, while three of the four models do in double-conversion mode. Lowering the load from rated to light load makes the negative resistance deeper, as expected for a constant-power load, so a lightly loaded facility in double-conversion mode is the worst case. Raising the UPS DC-link capacitance pushes the negative resistance into a narrow band around the fundamental. These findings give a basis for screening data centers for SSCI during interconnection studies.

0.38

Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics

eess.SY ·2026-11-17 ·Guido Cavraro
similarity 0.61
Abstract

The growing deployment of data centers poses challenges for power-system operation. However, data centers possess flexible resources that can be leveraged to mitigate their impact on the grid and provide grid services. This paper develops a linear-affine dynamic model of a transmission network with multiple data centers, explicitly coupling electromechanical grid dynamics with data center power demand and computational backlog. Grid-aware computing policies are incorporated to represent how data centers adjust their computational power in response to grid frequency deviations and workload backlog. The proposed framework provides a tractable means of investigating the interactions between multiple data centers and the transmission grid and assessing the potential of flexible computing to support power-system stability.

0.26

Real-Time Edge-based Detection of Correlated AI Data-Center Load Episodes

eess.SY ·2026-08-24 ·Chandan Chaudhary, Abanish Tiwari, Yansong Pei, Mohammed Ben-Idris, Joydeep Mitra
similarity 0.61
Abstract · Submitted to 2027 IEEE PES Grid Edge, to be held in 19-22 April, Salt Lake City, Utah, USA

Artificial-intelligence data centers running bulk-synchronous training can impose sub-second power swings. When several facilities synchronize their training cycles, these load variations become spatially correlated and amplify the aggregate disturbance on the grid. A grid operator without access to data-center telemetry must infer this correlation from electrical measurements alone. However, the required observation time and the feasibility of detection on substation-deployable hardware remain uncharacterized. This paper develops a correlation-based detection method to classify the multi-facility operating regime from cross-facility power measurements. Analytical derivations and experimental validation show that the resulting detection confidence increases with the observation-window length at a rate governed by the load correlation time. The method is demonstrated in a real-time hardware-in-the-loop testbed, where load setpoints generated from a validated semi-Markov data-center load model are applied to an electromagnetic-transient grid simulation on a Real-Time Digital Simulator. A compact classifier built on pairwise power correlations runs on an edge device in this loop and determines whether the data-center load variations are independent or spatially correlated. The cross-facility correlation separates the independent and correlated cases across independent realizations. The held-out detection accuracy improves with the observation window, consistent with the predicted relation. A raw-waveform network fails to generalize, supporting pairwise correlation as the discriminative signal. The detector executes in real time on commodity edge hardware. A closed-loop demonstration against the running simulator tracks a regime change within one observation window.

0.43

Steady-State Equivalent Circuit Model for Data Center Loads

eess.SY ·2026-08-18 ·Muhammad Hamza Ali, Peng Sang, Hyeon Woo, Hyein Kang, Sungyun Choi +1 more
similarity 0.61
Abstract

Planners currently represent data centers as aggregate constant-PQ or ZIP loads in steady-state interconnection and contingency studies. These aggregate models are computationally convenient. However, they obscure the electrical relationship between computational workloads, server utilization, and grid-side demand. They ignore the internal power-electronic conversion stages of IT loads and assume homogeneous workload distributions across the compute clusters. This hides operating-point-dependent converter losses and efficiency variations. We propose a steady-state equivalent-circuit model (ECM) for data centers, which explicitly builds circuit models for IT loads, power supply units, cooling, and auxiliary systems. For power supply units, the equivalent circuit model explicitly represents internal power-electronic conversion stages. For IT loads, we develop a utilization-dependent server power model, and we combine it with loss-aware ECMs of power supply units. This approach captures the grid-side impact of heterogeneous workload distributions while preserving compatibility with conventional power-flow analysis. We evaluate this data center ECM in large-scale transmission power flows, using Monte Carlo simulations under heterogeneous and homogeneous cluster utilization. In comparison with the fixed-efficiency constant-PQ model, the ECM predicts that the most stressed line exceeds its thermal limit in about 30% of Monte Carlo samples. The results further show that homogeneous server utilization overstates line-loading variability by 17%-46% relative to heterogeneous server utilization, depending on the intra-cluster workload correlation.

0.47

Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?

eess.SY ·2026-11-12 ·Ziang Liu, Yimeng Liu, Francis Yunhe Hou
hot direction similarity 0.61
Abstract · 10 pages, 5 figures

Artificial intelligence data centers (AIDCs) are rapidly increasing in number and capacity. These large electronic loads are interfaced through power electronic devices and can sharply reduce grid power intake during fault-induced voltage sags. Disturbances exceeding equipment ride-through capabilities may also trigger protective disconnection, posing risks to power system security. Static synchronous compensators (STATCOMs) and appropriately controlled AIDC uninterruptible power supply (UPS) rectifiers can provide reactive power support during voltage sags. This paper compares the individual and combined effectiveness of STATCOM and UPS-based voltage support in mitigating fault-induced reductions in grid power intake through electromagnetic transient simulations of a 1 GW AIDC connected to an IEEE nine-bus system. Simulation results show that STATCOM support better preserves short-term intake in milder tested faults, whereas UPS coordination maintains rectifier operation under deeper sags by reducing active intake to reserve reactive current capacity. Combined support improves auxiliary load retention and recovery in selected cases. However, severe tested sags still cause substantial grid-demand reductions even with combined support.

0.37