Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics

Guido Cavraro

eess.SY ·submitted 2026-11-17 23:35 UTC · v1

Abstract

The growing deployment of data centers poses challenges for power-system operation. However, data centers possess flexible resources that can be leveraged to mitigate their impact on the grid and provide grid services. This paper develops a linear-affine dynamic model of a transmission network with multiple data centers, explicitly coupling electromechanical grid dynamics with data center power demand and computational backlog. Grid-aware computing policies are incorporated to represent how data centers adjust their computational power in response to grid frequency deviations and workload backlog. The proposed framework provides a tractable means of investigating the interactions between multiple data centers and the transmission grid and assessing the potential of flexible computing to support power-system stability.

Closest papers

Nearest neighbours by meaning across the whole index.

A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

eess.SY ·2026-11-18 ·Advith Natarajan, Xinyang Zhou, Guido Cavraro
similarity 0.82
Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

0.23

Grid-Forming AI Data Centers: Coordinated Grid Support Control from IT Loads and Energy Storage

eess.SY ·2026-11-13 ·Xuechun Zhang, Zhiyi Zhao, Fei Teng, Zhen Wang
hot direction similarity 0.74
Abstract

To exploit the grid-support capability of AI data centers (AIDCs), this paper proposes a grid-forming (GFM) control scheme which coordinates the IT loads and energy storage (ES) in the AIDC. First, the framework of a grid-connected AIDC is presented, with the multi-stage power conversion from the grid to the IT loads presented. A dual GFM scheme is then proposed for the back-to-back converters to provide grid support through coordinated power adjustments from IT loads and ES. In addition, an aggregated power response model is established to characterize the IT-load flexibility considering multiple IT servers executing diverse tasks. Time-domain simulations of a 100 MW grid-connected AIDC demonstrate that the proposed control scheme can effectively support the grid.

0.25

Job-Level Workload Allocation for Data Centers Under Flexible Interconnections

eess.SY ·2026-11-14 ·Tanmay Mishra, Arash Omidi, Mads R. Almassalkhi
hot direction similarity 0.74
Abstract · Submitted to IEEE PES General Meeting 2027

Flexible interconnections allow data centers to connect to the grid sooner without upgrading the grid infrastructure, if they accept limits on their grid power during periods of grid stress. When a limit is reached, the data center must slow some of its computing jobs. This choice sets the cost of flexibility, because the work done by a job is worth far more than the energy it uses. This paper models how jobs respond when their power is reduced, and proposes a real-time method that shares the available power among jobs according to their value. It also gives grid planners a simple measure of how much power a data center can reduce, and for how long. A one-year case study of a 100-MW data center shows that the proposed method lowers the cost of meeting grid limits, and that on-site generation and storage lower it further.

0.24

Unlocking AI Data Center Interconnection Capacity Through Coordinated Grid and Data Center Flexibility

eess.SY ·2026-10-04 ·Rida Fatima, Xingpeng Li
similarity 0.70
Abstract

The rapid growth of AI data centers is creating concentrated electricity demands that can exceed available distribution network headroom and delay interconnection. This paper investigates whether capacity can be used effectively by coordinating flexibility on both sides of the interconnection. A day-ahead mixed integer second order cone programming framework maximizes feasible AI data center IT capacity using utility side conservation voltage reduction and network topology reconfiguration, together with data center workload shifting and reserve constrained uninterruptible power supply storage. Background feeder demand uses voltage dependent ZIP models, while the data center is modeled as constant power demand using Training, Inference, and Mixed workload profiles. A two-stage solution first maximizes interconnection capacity and then minimizes feeder losses for the retained capacity, with numerical relaxation screening. Studies on a 116-bus model derived from the IEEE 123-node feeder show that, at the constrained bus-60 connection point, grid side flexibility, driven almost entirely by network reconfiguration, increases feasible IT capacity by approximately 42.5-45.0%, while data center flexibility alone provides approximately 2.1-5.4% gains. Coordinated operation increases feasible IT capacity from approximately 10.5-10.6 MW under BASE operation to 15.3-16.0 MW, corresponding to gains of approximately 45.9-50.8%; the 16.0 MW Inference result is limited by the adopted UPS reserve requirement. Benefits are strongly location dependent and influenced by workload flexibility, deferral duration, PUE, UPS energy and reserve requirements, and feeder loading. Under a combined adverse operating condition, FULL capacity decreases by only 3.4% relative to the nominal Mixed case while retaining substantial additional capacity over BASE.

0.29

Grid-Forming E-STATCOMs for Stable Integration of Large-Scale Data Centers: Modeling and Control

eess.SY ·2026-09-27 ·Prabhat Ranjan Bana, Novan Zakkia, Jean-Philippe Hasler, Christer Danielsson
published similarity 0.70
Abstract · To be published in CIGRE: Grid of the Future Symposium 2026, in Richmond, Virginia, US

The rapid expansion of large-scale AI data centers (AIDC) is introducing new stability challenges, particularly in weak or low-inertia networks characterized by fast, step-like demand variations and strict requirements on voltage and dynamic performance. This paper investigates the use of grid-forming (GFM) Enhanced STATCOMs (E-STATCOMs) to support reliable integration of such facilities. A power-admittance-based linear modelling framework is developed to capture system interactions and is validated through detailed EMT simulations. The results demonstrate that E-STATCOMs provide fast, well-damped responses to abrupt load changes while effectively mitigating low-frequency oscillations and interactions with network resonances. By enabling tunable dynamic behavior via a load balancer, virtual impedance, and coordinated active-reactive power support, the proposed approach allows precise shaping of system response and improved regulation at the point of connection. These features make E-STATCOMs a flexible and scalable solution for integrating large data centers into weak grids and long transmission systems, supported by a design-oriented framework that facilitates parameter selection and performance assessment without extensive reliance on EMT studies to meet grid codes and AIDC interconnection requirements.

0.24

Impact of Grid-Interactive Data Center Microgrids on Grid Reliability

eess.SY ·2026-11-11 ·Kiran Kumar Challa, Kumarsinh Jhala
hot direction similarity 0.69
Abstract · 5 Pages, 9 Figurs, Conference

Traditional data centers, operating as passive loads with standby backup resources, present significant challenges for grid integration due to their scale, rapid load fluctuations, and limited operational flexibility. This article investigates the transformative potential of grid-interactive data center microgrids, which integrate battery energy storage, on-site generation, and intelligent microgrid controllers to actively support both facility and grid operations. The proposed simulation framework enables the study comparing conventional and grid-interactive architectures under a range of steady-state and contingency scenarios. Results reveal that grid-interactive microgrids can substantially reduce peak grid demand, improve voltage stability, and improve system reliability especially when data center and system load peaks coincide. The findings highlight the critical role of coordinated resource management in enabling the reliable and efficient integration of large data center loads, and provide a practical methodology for assessing their system-level impacts.

0.26

A Critical Review of Grid Integration Challenges and Flexibility Opportunities for Large-Scale Data Centers

eess.SY ·2026-10-14 ·Bibek Dhakal, Manohar Chamana, Biswambhar Gayen, Jatendar Kumar, S M Shams Rahman +5 more
similarity 0.68
Abstract

The rapid proliferation of cloud computing and artificial intelligence workloads is fundamentally reshaping the magnitude, spatial concentration, and electrical characteristics of data center power demand. Data centers differ from conventional commercial loads because they combine high rack densities, converter-dominated interfaces, thermally coupled cooling, uninterruptible power supplies, programmable workloads, and increasingly complex behind-the-meter generation and storage within a single facility. This review examines their grid integration from utility and sustainable-energy perspectives across resource planning, large-load interconnection, distribution feeders, market operation, real-time dynamics, power quality, and asset management. Particular attention is given to distribution-level issues that receive limited treatment in broader energy reviews: bidirectional operation on renewable-rich feeders, harmonic propagation and resonance, ride-through and reconnection, transformer derating, cable ampacity, neutral-conductor heating, protection, and measurement. Static, composite, physics-based dynamic, calibrated, impedance, electromagnetic transient, and hybrid load models are compared according to study purpose and data requirements, and utility coordination platforms, uninterruptible power supply and battery control, workload flexibility, renewable co-location, cogeneration, fuel cells, thermal storage, and clean firm supply are assessed. The central finding is that requested peak demand and annual energy matching alone cannot establish reliable or sustainable integration. Credible assessment must consider hourly and locational supply, network deliverability, marginal emissions, lifecycle and water impacts, backup obligations, rebound, asset health, and verified operating capability.

0.12

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.67
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08