A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

Advith Natarajan, Xinyang Zhou, Guido Cavraro

eess.SY ·submitted 2026-11-18 00:17 UTC · v1

Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

Closest papers

Nearest neighbours by meaning across the whole index.

Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics

eess.SY ·2026-11-17 ·Guido Cavraro
similarity 0.82
Abstract

The growing deployment of data centers poses challenges for power-system operation. However, data centers possess flexible resources that can be leveraged to mitigate their impact on the grid and provide grid services. This paper develops a linear-affine dynamic model of a transmission network with multiple data centers, explicitly coupling electromechanical grid dynamics with data center power demand and computational backlog. Grid-aware computing policies are incorporated to represent how data centers adjust their computational power in response to grid frequency deviations and workload backlog. The proposed framework provides a tractable means of investigating the interactions between multiple data centers and the transmission grid and assessing the potential of flexible computing to support power-system stability.

0.26

Job-Level Workload Allocation for Data Centers Under Flexible Interconnections

eess.SY ·2026-11-14 ·Tanmay Mishra, Arash Omidi, Mads R. Almassalkhi
hot direction similarity 0.69
Abstract · Submitted to IEEE PES General Meeting 2027

Flexible interconnections allow data centers to connect to the grid sooner without upgrading the grid infrastructure, if they accept limits on their grid power during periods of grid stress. When a limit is reached, the data center must slow some of its computing jobs. This choice sets the cost of flexibility, because the work done by a job is worth far more than the energy it uses. This paper models how jobs respond when their power is reduced, and proposes a real-time method that shares the available power among jobs according to their value. It also gives grid planners a simple measure of how much power a data center can reduce, and for how long. A one-year case study of a 100-MW data center shows that the proposed method lowers the cost of meeting grid limits, and that on-site generation and storage lower it further.

0.31

Grid-Forming AI Data Centers: Coordinated Grid Support Control from IT Loads and Energy Storage

eess.SY ·2026-11-13 ·Xuechun Zhang, Zhiyi Zhao, Fei Teng, Zhen Wang
hot direction similarity 0.68
Abstract

To exploit the grid-support capability of AI data centers (AIDCs), this paper proposes a grid-forming (GFM) control scheme which coordinates the IT loads and energy storage (ES) in the AIDC. First, the framework of a grid-connected AIDC is presented, with the multi-stage power conversion from the grid to the IT loads presented. A dual GFM scheme is then proposed for the back-to-back converters to provide grid support through coordinated power adjustments from IT loads and ES. In addition, an aggregated power response model is established to characterize the IT-load flexibility considering multiple IT servers executing diverse tasks. Time-domain simulations of a 100 MW grid-connected AIDC demonstrate that the proposed control scheme can effectively support the grid.

0.32

Impact of Grid-Interactive Data Center Microgrids on Grid Reliability

eess.SY ·2026-11-11 ·Kiran Kumar Challa, Kumarsinh Jhala
hot direction similarity 0.67
Abstract · 5 Pages, 9 Figurs, Conference

Traditional data centers, operating as passive loads with standby backup resources, present significant challenges for grid integration due to their scale, rapid load fluctuations, and limited operational flexibility. This article investigates the transformative potential of grid-interactive data center microgrids, which integrate battery energy storage, on-site generation, and intelligent microgrid controllers to actively support both facility and grid operations. The proposed simulation framework enables the study comparing conventional and grid-interactive architectures under a range of steady-state and contingency scenarios. Results reveal that grid-interactive microgrids can substantially reduce peak grid demand, improve voltage stability, and improve system reliability especially when data center and system load peaks coincide. The findings highlight the critical role of coordinated resource management in enabling the reliable and efficient integration of large data center loads, and provide a practical methodology for assessing their system-level impacts.

0.33

Unlocking AI Data Center Interconnection Capacity Through Coordinated Grid and Data Center Flexibility

eess.SY ·2026-10-04 ·Rida Fatima, Xingpeng Li
similarity 0.66
Abstract

The rapid growth of AI data centers is creating concentrated electricity demands that can exceed available distribution network headroom and delay interconnection. This paper investigates whether capacity can be used effectively by coordinating flexibility on both sides of the interconnection. A day-ahead mixed integer second order cone programming framework maximizes feasible AI data center IT capacity using utility side conservation voltage reduction and network topology reconfiguration, together with data center workload shifting and reserve constrained uninterruptible power supply storage. Background feeder demand uses voltage dependent ZIP models, while the data center is modeled as constant power demand using Training, Inference, and Mixed workload profiles. A two-stage solution first maximizes interconnection capacity and then minimizes feeder losses for the retained capacity, with numerical relaxation screening. Studies on a 116-bus model derived from the IEEE 123-node feeder show that, at the constrained bus-60 connection point, grid side flexibility, driven almost entirely by network reconfiguration, increases feasible IT capacity by approximately 42.5-45.0%, while data center flexibility alone provides approximately 2.1-5.4% gains. Coordinated operation increases feasible IT capacity from approximately 10.5-10.6 MW under BASE operation to 15.3-16.0 MW, corresponding to gains of approximately 45.9-50.8%; the 16.0 MW Inference result is limited by the adopted UPS reserve requirement. Benefits are strongly location dependent and influenced by workload flexibility, deferral duration, PUE, UPS energy and reserve requirements, and feeder loading. Under a combined adverse operating condition, FULL capacity decreases by only 3.4% relative to the nominal Mixed case while retaining substantial additional capacity over BASE.

0.08

From Grid to Chip: Power Architecture, Stability, and Flexibility of AI Data Centers

cs.ET cs.AReess.SY ·2026-09-10 ·Yubo Song, Rui Kong, Takuro Umihara, Pooya Davari, Frede Blaabjerg +1 more
hot direction similarity 0.65
Abstract · The manuscript has been submitted for review to IEEE Open Journal of Power Electronics

The rapid growth of artificial intelligence (AI) computing is transforming data centers into large, dynamic electrical loads. Their deployment is primarily constrained by energy availability and grid-connection capacity, which is further aggravated by the ability of power-delivery architectures, control systems, and computing workloads to operate reliably during fast grid disturbances. This article presents a technological perspective on AI data centers as grid-interactive computing systems. First, it reviews grid-integration bottlenecks, evolving connection policies, grid-code requirements, which has fostered new technological trends via spatio-temporal flexibility available through workload orchestration, cooling systems, on-site resources, and energy storage. Second, it maps the evolution of power-delivery architectures from medium-voltage grid interfaces to chip-level, discussing higher-voltage DC distribution, solid-state transformers, wide-bandgap devices, advanced chip-level power delivery, and liquid cooling. Third, it establishes a three-level stability framework spanning rack-level DC-bus dynamics, facility-level converter interactions, and system-level grid-coupled behavior. The framework connects dominant instability mechanisms, including constant power load effects, impedance interactions, forced oscillations, and operating-mode transitions, with suitable modeling, assessment, and mitigation approaches. Synthesizing these topics, this article highlights grid-to-chip co-design as a central requirement for scalable AI infrastructure, linking computing workloads, power-delivery systems, energy buffers, and grid operation.

0.27

Forced Oscillations in Power Systems Induced by Data Centers Hosting AI Workloads

eess.SY ·2026-09-23 ·Jovan Krajacic, Georgia Pierrou, Maitraya Desai, Gabriela Hug, Gustavo Valverde
similarity 0.65
Abstract · Revised and extended version of the manuscript previously posted on TechRxiv: https://www.techrxiv.org/doi/full/10.36227/techrxiv.176127304.…

Power swings in large Data Centers (DTCs) running Artificial Intelligence (AI) workloads can excite poorly damped modes in power systems. The resulting forced oscillations can lead to flicker, equipment disconnection, or blackouts. This paper investigates the risks of such load fluctuations for different system strengths and damping conditions. Using an analytical approach based on transfer functions, we identify critical DTC locations in the power grid at which load fluctuations could induce the largest forced oscillations and further characterize the harmonic spectrum of the resulting system response. Depending on the frequency and magnitude of the DTC load fluctuations, forced oscillations can become unbounded. The underlying instabilities are classified into saddle-node bifurcations of the forced periodic response and impasse-surface encounters, using Floquet multipliers and the minimum singular value of the algebraic Jacobian. Furthermore, the impact of different duty cycles and harmonic components beyond the fundamental oscillation frequency in square-wave load profiles is analyzed. Finally, the interaction of two oscillating DTCs is investigated for different locations and forcing frequencies, considering both synchronized and unsynchronized operation. The findings can help system operators to define new regulations on the maximum load fluctuations permitted for DTC facilities at specific grid locations, without negatively affecting the stability and operation of the system.

0.55

A Critical Review of Grid Integration Challenges and Flexibility Opportunities for Large-Scale Data Centers

eess.SY ·2026-10-14 ·Bibek Dhakal, Manohar Chamana, Biswambhar Gayen, Jatendar Kumar, S M Shams Rahman +5 more
similarity 0.63
Abstract

The rapid proliferation of cloud computing and artificial intelligence workloads is fundamentally reshaping the magnitude, spatial concentration, and electrical characteristics of data center power demand. Data centers differ from conventional commercial loads because they combine high rack densities, converter-dominated interfaces, thermally coupled cooling, uninterruptible power supplies, programmable workloads, and increasingly complex behind-the-meter generation and storage within a single facility. This review examines their grid integration from utility and sustainable-energy perspectives across resource planning, large-load interconnection, distribution feeders, market operation, real-time dynamics, power quality, and asset management. Particular attention is given to distribution-level issues that receive limited treatment in broader energy reviews: bidirectional operation on renewable-rich feeders, harmonic propagation and resonance, ride-through and reconnection, transformer derating, cable ampacity, neutral-conductor heating, protection, and measurement. Static, composite, physics-based dynamic, calibrated, impedance, electromagnetic transient, and hybrid load models are compared according to study purpose and data requirements, and utility coordination platforms, uninterruptible power supply and battery control, workload flexibility, renewable co-location, cogeneration, fuel cells, thermal storage, and clean firm supply are assessed. The central finding is that requested peak demand and annual energy matching alone cannot establish reliable or sustainable integration. Credible assessment must consider hourly and locational supply, network deliverability, marginal emissions, lifecycle and water impacts, backup obligations, rebound, asset health, and verified operating capability.

0.12