CS Paper Radar

Real-Time Edge-based Detection of Correlated AI Data-Center Load Episodes

Chandan Chaudhary, Abanish Tiwari, Yansong Pei, Mohammed Ben-Idris, Joydeep Mitra

eess.SY ·submitted 2026-08-24 02:11 UTC · v1

Abstract

Artificial-intelligence data centers running bulk-synchronous training can impose sub-second power swings. When several facilities synchronize their training cycles, these load variations become spatially correlated and amplify the aggregate disturbance on the grid. A grid operator without access to data-center telemetry must infer this correlation from electrical measurements alone. However, the required observation time and the feasibility of detection on substation-deployable hardware remain uncharacterized. This paper develops a correlation-based detection method to classify the multi-facility operating regime from cross-facility power measurements. Analytical derivations and experimental validation show that the resulting detection confidence increases with the observation-window length at a rate governed by the load correlation time. The method is demonstrated in a real-time hardware-in-the-loop testbed, where load setpoints generated from a validated semi-Markov data-center load model are applied to an electromagnetic-transient grid simulation on a Real-Time Digital Simulator. A compact classifier built on pairwise power correlations runs on an edge device in this loop and determines whether the data-center load variations are independent or spatially correlated. The cross-facility correlation separates the independent and correlated cases across independent realizations. The held-out detection accuracy improves with the observation window, consistent with the predicted relation. A raw-waveform network fails to generalize, supporting pairwise correlation as the discriminative signal. The detector executes in real time on commodity edge hardware. A closed-loop demonstration against the running simulator tracks a regime change within one observation window.

Comment
Submitted to 2027 IEEE PES Grid Edge, to be held in 19-22 April, Salt Lake City, Utah, USA

Closest papers

Nearest neighbours by meaning across the whole index.

Adaptive State Estimation Under Topological Uncertainty in Unobservable Primary Distribution Systems Using Strategically Placed Sensors

eess.SY ·2026-09-23 ·Farah Elsherif, Behrouz Azimian, Anamitra Pal
published similarity 0.65
Abstract · 6 pages, 6 figures, 4 tables. Accepted for presentation at the 2026 North American Power Symposium (NAPS)

The rapid integration of distributed energy resources is fundamentally altering power flow patterns in primary distribution networks and intensifying operational uncertainty. These problems are further compounded by lack of real-time situational awareness and frequent topology changes. To address these problems, this paper proposes an integrated deep learning framework for simultaneous topology identification (TI) and distribution system state estimation (DSSE) in real-time unobservable primary distribution networks instrumented by a minimal set of synchronized measurement devices (SMDs). A correlation-driven SMD placement algorithm is introduced first that jointly satisfies TI accuracy and DSSE performance requirements by exploiting temporal and spatial correlations in nodal voltage measurements. A dual deep neural network (DNN)-based DSSE model is developed next to estimate three-phase voltage magnitudes and angles across diverse operating conditions. To extend the framework beyond the base topology, fine-tuning-based transfer learning is employed to adapt the DSSE model to reconfigured topologies using limited retraining data. The framework is validated under both Gaussian and non-Gaussian measurement noise and benchmarked against a conventional estimation approach and a single DNN model.

0.35

Learning-Based Power Flow Estimation with Sparse PMU Deployment in Power Systems

eess.SY ·2026-10-09 ·Van-Hai Bui, Quang Manh Hoang, Akhtar Hussain, Wencong Su
similarity 0.61
Abstract · 14

Accurate monitoring of power flow is fundamental to the secure and reliable operation of modern power systems. Existing data-driven power flow estimation methods typically assume that synchronized measurements are available at every bus, requiring extensive deployment of phasor measurement units (PMUs). Such dense sensing infrastructures substantially increase installation, communication, and maintenance costs. This paper proposes a learning-based framework that minimizes the number of installed PMUs while maintaining high-accuracy systemwide power flow estimation. Instead of relying on measurements from all buses, the proposed method identifies an informative subset of buses whose synchronized measurements are sufficient to accurately reconstruct branch power flow across the network. To this end, a neural network is developed to learn the nonlinear relationship between PMU measurements and system-wide power flows, and multiple PMU deployment scenarios are evaluated to quantify the trade-off between measurement availability and estimation accuracy. The results enable utilities to identify cost-effective PMU placement strategies that balance deployment cost and prediction performance. Case studies on the IEEE 30-bus test system demonstrate that the proposed framework significantly reduces the number of required PMUs while maintaining accurate power flow estimation.

0.18

Data Center Load Reductions: Attribution, Measurement Limits, and Estimation

eess.SY ·2026-10-28 ·Abdallah Alalem Albustami, Ahmad F. Taha, Mohammad Alwahdanee, Zuhaib Shakeel Muhammad
similarity 0.61
Abstract

Hundreds of gigawatts of data center loads are seeking interconnection in the United States given the massive growth of artificial intelligence and cloud computing. In recent years, several incidents of data centers reducing their loads by hundreds to thousands of megawatts have been documented, raising grid reliability concerns. U.S. regulators have since ordered reliability standards for the integration of computational loads, and the North American Electric Reliability Corporation (NERC) now calls on transmission owners to install disturbance recorders at these facilities to support root cause analysis. Such recorders usually observe only electrical quantities at the point of interconnection (POI). A sudden load reduction can be caused by a change in workload or a switch to backup supply. This work shows when POI measurements can distinguish the two mechanisms. It is established that they can produce identical POI voltage and current in a quasi-static constant power model, and during the transient their separation depends on the reduction relative to measurement noise, the clearing time, the dynamics through which workload reaches the POI, and the recorder bandwidth. When POI data are insufficient, an estimator that uses workload data is proposed to determine how much of the facility stayed connected. The results of this work identify the measurements and grid information utilities need to determine why data center load dropped.

0.31

AI Data Centers Meet Electrical Grids: A Review of Power Challenges and Coordinated Solutions

eess.SY ·2026-10-06 ·Mariam Mughees, Yuzhuo Li, Yize Chen, Yunwei Ryan Li
survey similarity 0.60
Abstract

Artificial intelligence (AI) workloads are creating large, power-electronic loads whose effects on power systems depend on location, temporal variability, controllability, and interactions with other loads and resources. Annual electricity consumption alone cannot capture these effects. This review examines how AI data centers affect power systems stability, renewable-energy integration, and low-carbon planning by tracing the power-delivery chain from accelerators and workloads through rack converters, uninterruptible power supplies (UPS), storage, and microgrids to the transmission point of interconnection. Reported oscillatory events and multi-gigawatt load transfers highlight how facility responses can amplify disturbances, while programmable workloads and controllable power converters offer opportunities for demand flexibility. Challenges and mitigation strategies are organized across device, rack, facility, and power systems levels, spanning millisecond-to-year timescales. A bandwidth-matching framework relates disturbances to the response capabilities of mitigation resources. The review distinguishes computational energy efficiency from power systems and sustainability outcomes: lower energy consumption per token does not necessarily reduce peak demand, electrical disturbances, or carbon emissions. It examines how coordinated workload scheduling, grid-interactive UPS systems, storage, high-voltage DC distribution, and flexible interconnection can support reliability, efficiency, and decarbonization. Key research needs include dynamic load models, high-bandwidth telemetry, carbon-and grid-aware scheduling, and mechanisms for valuing flexible computational demand.

0.08

Multi-Timescale Deliverability of Shared Hybrid Storage for AI Data Center Campuses

eess.SY ·2026-10-30 ·Zihan Meng, Ruizhang Yang, Chenxi Hu, Francis Yunhe Hou
similarity 0.59
Abstract

Artificial intelligence data center (AIDC) campuses contain sustained power variations and subsecond power fluctuations, requiring both sufficient stored energy and fast response. A shared hybrid energy storage system (HESS) can mitigate aggregate AIDC power deviations, but interval-based schedules cannot capture the delay between commanded and delivered power at the campus point of common coupling (PCC). To this end, this paper proposes a multi-timescale scheduling model for mitigating AIDC power fluctuations with the shared HESS. First, it models electrical pooling at the campus bus and constrains the shared HESS to a single PCC injection. Second, a two-layer model passes five-minute scheduled power, energy state, and reserve capacity to a causal fast response model that distinguishes commanded power from delivered power. Case studies using the National Laboratory of the Rockies (NLR) GenAI Power Profiles Dataset show reductions in both PCC and fast integral absolute error (IAE), while retaining most of the improvement available under ideal response.

0.12

Cyber-physical attack detection approaches in the wide-area measurement system

cs.LG ·2026-10-30 ·Zakaria El Mrabet, Prakash Ranganathan
published similarity 0.59
Abstract

Improving situational awareness within the Smart Grid is an effective preventive measure to detect potential anomalies, and avoid their adverse consequences. A wide area measurement system (WAMS) based Phasor Measurement Unit (PMU) can assist in improving visibility within the grid by collecting relevant measurements including magnitude, phase angle, frequency, voltage, and current, with a precise GPS-based timestamp. So far, there are more than 2500 PMUs deployed in the North American power grid, where each of which generates between 30 and 60 samples/s, roughly 1.5 TB/month of streamed data. Thus, processing such large PMU streams requires expensive computational resources and faster algorithms. This paper provides state-of-the-art cyber and physical anomalies in the WAMS and analyses their impact on the integrity and availability of the system. Next, it investigates the current anomaly detection approach in historical and streaming PMU data, including conventional machine learning and hybrid approaches, and assesses their advantages and main drawbacks. Lastly, it sheds light on the importance of handling missing PMU data and concept drifts.

0.68

Machine Learning-Based State Estimation for an Actual Transmission System Using Field PMU Data

eess.SY ·2026-09-22 ·Shiva Moshtagh, Nihar Thakkar, Anamitra Pal, Evangelos Farantatos
published similarity 0.58
Abstract · Accepted for presentation at the 60th Hawaii International Conference on System Sciences (HICSS-60), 2027

Time-synchronized state estimation (SE) plays a critical role in ensuring real-time situational awareness in modern power systems. However, achieving full system observability using phasor measurement units (PMUs) is often impractical due to cost and deployment constraints. Moreover, SE operation at PMU timescales imposes stringent requirements on latency, robustness, and reliability that are difficult to satisfy using conventional iterative hybrid SE techniques under incomplete observability by PMUs. This paper evaluates the feasibility of deploying deep neural networks for PMU-timescale, time-synchronized SE in real-world PMU-unobservable transmission systems using actual data from a US power utility. Key contributions include a systematic assessment of estimation accuracy, scalability, and computational performance under realistic operating conditions.

0.34

Large-Scale Data Center Integration in Power Systems: Uncertainty and Multi-Scale Variation

eess.SY ·2026-10-09 ·Le Xie, Dongjoo Kim, Qian Zhang, Grant Ruan, Paul L. Joskow
published similarity 0.57
Abstract · Accepted for publication in Proceedings of the IEEE. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE m…

Hyperscale artificial intelligence (AI) data centers are emerging as a structurally new class of electricity demand. Unlike conventional loads, they materialize as spatially concentrated, transmission-level point loads with rapid deployment timelines and converter-dominated dynamics. Their integration is governed by two defining properties: forecast uncertainty in load realization and multi-scale temporal variation spanning sub-seconds to planning horizons. We develop a unified framework that links reliability and affordability to these dimensions through a four-quadrant structure: (reliability, affordability) $\times$ (uncertainty, variation), which integrates probabilistic resource adequacy, generation and transmission expansion, operational security, and market design. Measured traces from a public generative-AI workload dataset show strongly tonal GPU power spectra rather than smooth broadband behavior: harmonic combs at the training-step cadence, and a distinct sub-second periodicity in inference. Across these traces the dominant variance band shifts with workload type (seconds for training and offline inference; tens of seconds and longer for online inference). We report this as a characterization of the measured workloads rather than a universal signature, and take it to indicate that such loads warrant a spectral description rather than a peak-demand one. These signatures directly affect reserve requirements, ramping products, voltage stability, ride-through performance, and harmonic interactions in converter-rich grids. Taken together, the analytical framework and empirical results establish a system-level basis for assessing the reliability and cost implications of large AI data center integration across planning and operational horizons.

0.27