CS Paper Radar

Learning-Based Power Flow Estimation with Sparse PMU Deployment in Power Systems

Van-Hai Bui, Quang Manh Hoang, Akhtar Hussain, Wencong Su

eess.SY ·submitted 2026-10-09 14:48 UTC · v1

Abstract

Accurate monitoring of power flow is fundamental to the secure and reliable operation of modern power systems. Existing data-driven power flow estimation methods typically assume that synchronized measurements are available at every bus, requiring extensive deployment of phasor measurement units (PMUs). Such dense sensing infrastructures substantially increase installation, communication, and maintenance costs. This paper proposes a learning-based framework that minimizes the number of installed PMUs while maintaining high-accuracy systemwide power flow estimation. Instead of relying on measurements from all buses, the proposed method identifies an informative subset of buses whose synchronized measurements are sufficient to accurately reconstruct branch power flow across the network. To this end, a neural network is developed to learn the nonlinear relationship between PMU measurements and system-wide power flows, and multiple PMU deployment scenarios are evaluated to quantify the trade-off between measurement availability and estimation accuracy. The results enable utilities to identify cost-effective PMU placement strategies that balance deployment cost and prediction performance. Case studies on the IEEE 30-bus test system demonstrate that the proposed framework significantly reduces the number of required PMUs while maintaining accurate power flow estimation.

Comment
14

Closest papers

Nearest neighbours by meaning across the whole index.

Machine Learning-Based State Estimation for an Actual Transmission System Using Field PMU Data

eess.SY ·2026-09-22 ·Shiva Moshtagh, Nihar Thakkar, Anamitra Pal, Evangelos Farantatos
published similarity 0.72
Abstract · Accepted for presentation at the 60th Hawaii International Conference on System Sciences (HICSS-60), 2027

Time-synchronized state estimation (SE) plays a critical role in ensuring real-time situational awareness in modern power systems. However, achieving full system observability using phasor measurement units (PMUs) is often impractical due to cost and deployment constraints. Moreover, SE operation at PMU timescales imposes stringent requirements on latency, robustness, and reliability that are difficult to satisfy using conventional iterative hybrid SE techniques under incomplete observability by PMUs. This paper evaluates the feasibility of deploying deep neural networks for PMU-timescale, time-synchronized SE in real-world PMU-unobservable transmission systems using actual data from a US power utility. Key contributions include a systematic assessment of estimation accuracy, scalability, and computational performance under realistic operating conditions.

0.34

Bayesian Distribution System State Estimation with Flow Matching

cs.LG cs.AIeess.SP ·2026-10-29 ·Nan Lin, Peter Palensky, Pedro Vergara Barrios
similarity 0.69
Abstract · 10 pages

Medium-voltage feeders have few real-time measurements, so distribution system state estimation (DSSE) rests on pseudo-measurements of the secondary substations, a prior in Bayesian terms. Weighted least squares keeps the power flow exact but reduces this prior to a mean and variance, while supervised deep learning estimators also learn the power flow and are tied to one measurement set. We propose PoSE (posterior sampling for state estimation), which keeps the Bayesian structure of DSSE and learns only what the distribution system operator does not know, namely the distribution of substation injections, modelled by a neural network trained with flow matching on historical data. The power flow equations, grid topology and measurements enter only at sampling, through a noise-aware Kalman-type correction. The neural network therefore never approximates the power flow, but every posterior sample is a physically consistent operating point, and one trained prior serves any measurement set, noise level and topology. On the IEEE 33-bus feeder, PoSE lowers the probabilistic injection error (CRPS) by 6.7-7.5% against a full-covariance Gaussian prior in all 12 tested settings. It provides reliable uncertainty: the 90% intervals contain the true injection almost exactly as often as exact posterior samples would, whereas those of supervised estimators contain it in only 37-78% of cases. On the 240-bus unbalanced three-phase Iowa feeder, it gives the lowest injection, voltage and branch-current errors of all estimators. A fast variant matches this accuracy at 0.2-0.6s per snapshot and, without retraining, beats Gaussian priors and retrained supervised estimators on seven reconfigured topologies.

0.17

Adaptive State Estimation Under Topological Uncertainty in Unobservable Primary Distribution Systems Using Strategically Placed Sensors

eess.SY ·2026-09-23 ·Farah Elsherif, Behrouz Azimian, Anamitra Pal
published similarity 0.69
Abstract · 6 pages, 6 figures, 4 tables. Accepted for presentation at the 2026 North American Power Symposium (NAPS)

The rapid integration of distributed energy resources is fundamentally altering power flow patterns in primary distribution networks and intensifying operational uncertainty. These problems are further compounded by lack of real-time situational awareness and frequent topology changes. To address these problems, this paper proposes an integrated deep learning framework for simultaneous topology identification (TI) and distribution system state estimation (DSSE) in real-time unobservable primary distribution networks instrumented by a minimal set of synchronized measurement devices (SMDs). A correlation-driven SMD placement algorithm is introduced first that jointly satisfies TI accuracy and DSSE performance requirements by exploiting temporal and spatial correlations in nodal voltage measurements. A dual deep neural network (DNN)-based DSSE model is developed next to estimate three-phase voltage magnitudes and angles across diverse operating conditions. To extend the framework beyond the base topology, fine-tuning-based transfer learning is employed to adapt the DSSE model to reconfigured topologies using limited retraining data. The framework is validated under both Gaussian and non-Gaussian measurement noise and benchmarked against a conventional estimation approach and a single DNN model.

0.35

Unified Heterogeneous Graph Neural Network solver for Power Flow, Optimal Power Flow and State Estimation

eess.SY cs.LG ·2026-09-15 ·Ferran Bohigas-Daranas, Hamid Latif-Martínez, Eduardo Prieto-Araujo, Oriol Gomis-Bellmunt, Pere Barlet-Ros
similarity 0.64
Abstract

Power Flow (PF), Optimal Power Flow (OPF), and State Estimation (SE) are fundamental problems in power system analysis, but solving them is computationally expensive. Graph Neural Networks (GNNs) have been proposed as fast surrogates, yet existing solvers are trained for a single problem at a time, producing narrow models that must be rebuilt for each new task. We propose a more general approach: a single Heterogeneous Residual Gated Graph Convolutional Network that solves all three problems with one shared backbone. Rather than learning one mapping, the model learns a reusable representation of how the network behaves, from which PF, OPF, and SE can each be estimated. Trained jointly on the three problems across diverse topologies and loading conditions, and evaluated on the IEEE 14-bus and 118-bus systems, the shared model matches the accuracy of task-specific GNN solvers and stays robust on unseen loading levels and topologies. These results show that a single model can capture the basic operation of a power network and serve several analysis tasks at once, a first step toward a foundation model for power systems.

0.11

Dynamic State Estimation from Sparse PMUs via Physics-Informed Graph Neural Operators

cs.LG eess.SY ·2026-11-07 ·Huy Hoang Le, Haoguang Wang, Christian Moya, Marcos Netto, Guang Lin
benchmark similarity 0.63
Abstract · 10 pages, 10 figures, 4 tables

This paper proposes a physics-informed graph neural operator for power system dynamic state estimation. From a sparse, intermittent measurement window at a few generator buses, the operator estimates the rotor-angle and speed trajectories of all machines, unmeasured ones included, in one forward pass. A graph-attention encoder processes the measurements, and the swing equations are imposed as a hard constraint or as a soft one with a learned correction that absorbs model errors. It is trained on simulated measurements, without state labels. With several phasor measurement units, masked training hides one from the input but keeps it in the loss. On four transmission systems, simulations show that the operator is the most accurate estimator that neither optimizes per scenario nor uses state labels, except on the smallest system at large model errors, where tuned Kalman smoothers are better. Networks trained on simulated states are more accurate on the two smallest systems but not on the 118-bus system, where the operator is faster and more accurate than hard-constrained moving-horizon estimation. Under model errors, it matches or outperforms an optimization-based benchmark at a fraction of its cost. The results hold for a detailed machine model with exact parameters seen only through voltage phasors.

0.31

A unified power-grid representation for reuse across network structures and computational tasks

eess.SY ·2026-09-07 ·Yanhao Huang, Changqing Liu, Zichang Wang, Qianhong Wu
similarity 0.61
Abstract

Data-driven power-system models are typically developed for specific grids and computational tasks, but their performance can deteriorate markedly or even fail when network structures or analytical objectives change. This paper develops a unified grid representation that separates physical-grid description from downstream computation. A self-supervised encoder represents each grid as a variable number of fixed-dimensional node, branch and global vectors under a common latent description. Although pretrained only on systems with at most 270 buses, the frozen encoder transfers without adaptation to a 70,000-bus network, more than 250 times larger in bus count, while preserving 0.7919 bus-correspondence accuracy. The same representation supports four independently trained downstream tasks: power-flow calculation, reactive-power adjustment, operating-condition generation and transient-stability assessment. On the previously unseen 70,000-bus grid, power-flow calculation achieves mean errors of 0.108$^{\circ}$ in phase angle and 3.8$\times$10\textsuperscript{-6} p.u. in voltage magnitude. Reactive-power adjustment achieved a 75\% PSASP-verified correction rate on the previously unseen 70,000-bus grid, while operating-condition generation delivered at least one PSASP-verified feasible state for 82.2\% of requests on previously unseen 400--1,000-bus grid families. For transient-stability assessment, the frozen encoder achieves accuracy within 0.8 percentage points of full encoder adaptation under matched training conditions. These results demonstrate that a unified power-grid representation can be learned once and reused unchanged across structurally different power systems and heterogeneous computational tasks.

0.47

Real-Time Edge-based Detection of Correlated AI Data-Center Load Episodes

eess.SY ·2026-08-24 ·Chandan Chaudhary, Abanish Tiwari, Yansong Pei, Mohammed Ben-Idris, Joydeep Mitra
similarity 0.61
Abstract · Submitted to 2027 IEEE PES Grid Edge, to be held in 19-22 April, Salt Lake City, Utah, USA

Artificial-intelligence data centers running bulk-synchronous training can impose sub-second power swings. When several facilities synchronize their training cycles, these load variations become spatially correlated and amplify the aggregate disturbance on the grid. A grid operator without access to data-center telemetry must infer this correlation from electrical measurements alone. However, the required observation time and the feasibility of detection on substation-deployable hardware remain uncharacterized. This paper develops a correlation-based detection method to classify the multi-facility operating regime from cross-facility power measurements. Analytical derivations and experimental validation show that the resulting detection confidence increases with the observation-window length at a rate governed by the load correlation time. The method is demonstrated in a real-time hardware-in-the-loop testbed, where load setpoints generated from a validated semi-Markov data-center load model are applied to an electromagnetic-transient grid simulation on a Real-Time Digital Simulator. A compact classifier built on pairwise power correlations runs on an edge device in this loop and determines whether the data-center load variations are independent or spatially correlated. The cross-facility correlation separates the independent and correlated cases across independent realizations. The held-out detection accuracy improves with the observation window, consistent with the predicted relation. A raw-waveform network fails to generalize, supporting pairwise correlation as the discriminative signal. The detector executes in real time on commodity edge hardware. A closed-loop demonstration against the running simulator tracks a regime change within one observation window.

0.43

PowerModels-ACOPF-AI: On-the-Fly Machine Learning Approach for Solving AC Optimal Power Flow Integrating Renewable Energy Sources

eess.SY ·2026-09-16 ·Bhuban Dhamala, Jose Tabarez, Anup Pandey
benchmark similarity 0.61
Abstract

The increasing complexity of modern power systems, driven by high renewable penetration, load variability, and operational uncertainty, demands fast and reliable solutions to the AC optimal power flow problem (AC-OPF). Traditional optimization methods, though accurate, often struggle with scalability and high computational burdens, making them impractical for real-time use in large networks. This paper introduces PowerModels-ACOPF-AI, a two-stage Bayesian Neural Network (BNN) surrogate designed to predict generator set points, bus voltages, and phase angles with uncertainty. The framework integrates a performance-sensitive on-the-fly learning mechanism that identifies regions of degraded prediction accuracy and dynamically retrains with additional AC-OPF solutions generated by PowerModels.jl. This self-adaptive loop ensures robust performance, enabling the model to maintain accuracy under novel or highly variable operating conditions. Validation on benchmark test systems of different sizes, namely the 30-bus, 200-bus, and 500-bus networks, demonstrates strong generalization capability, efficient handling of stochastic renewable injections, and the ability to provide rapid, uncertainty-aware predictions. Beyond predictive accuracy, the proposed approach offers practical value as both a real-time advisory tool for system operators and a fast initializer for conventional solvers, thus supporting resilient and efficient grid operation in future power systems.

0.16