Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid, Dirk Van Hertem

eess.SY ·submitted 2026-11-02 07:47 UTC · v1
published

Abstract

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

Comment
Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectures, Universitat Politècnica de Catalunya, & Cardiff University. (2026). Scientific deliverables of ADOreD Industrial Doctoral Network. Zenodo. https://doi.org/10.5281/zenodo.19736793
DOI
10.5281/zenodo.19736793

Closest papers

Nearest neighbours by meaning across the whole index.

Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?

eess.SY ·2026-11-12 ·Ziang Liu, Yimeng Liu, Francis Yunhe Hou
hot direction similarity 0.61
Abstract · 10 pages, 5 figures

Artificial intelligence data centers (AIDCs) are rapidly increasing in number and capacity. These large electronic loads are interfaced through power electronic devices and can sharply reduce grid power intake during fault-induced voltage sags. Disturbances exceeding equipment ride-through capabilities may also trigger protective disconnection, posing risks to power system security. Static synchronous compensators (STATCOMs) and appropriately controlled AIDC uninterruptible power supply (UPS) rectifiers can provide reactive power support during voltage sags. This paper compares the individual and combined effectiveness of STATCOM and UPS-based voltage support in mitigating fault-induced reductions in grid power intake through electromagnetic transient simulations of a 1 GW AIDC connected to an IEEE nine-bus system. Simulation results show that STATCOM support better preserves short-term intake in milder tested faults, whereas UPS coordination maintains rectifier operation under deeper sags by reducing active intake to reserve reactive current capacity. Combined support improves auxiliary load retention and recovery in selected cases. However, severe tested sags still cause substantial grid-demand reductions even with combined support.

0.37

Safe Barrier Function Control for Grid-Following Inverters under Weak Grid Conditions

eess.SY ·2026-10-18 ·Grigoris Michos, Christos K. Verginis
similarity 0.59
Abstract · 10 pages

This paper proposes a barrier control approach for the safe regulation of grid-following voltage-source-converters (VSC), operating in weak grid conditions. The proposed controller aims to enhance the transient performance and synchronization properties of the VSC, providing frequency and current limiting guarantees by employing smooth control barrier functions. First, a dynamic model is derived that includes the dynamic state interactions that are omitted in quasi-steady-state approaches, revealing the destabilizing elements both during transient and steady-state performance. Then, it is analytically proven that the proposed control law guarantees frequency limitation and inner current evolution in prescribed safety regions, while counteracting the destabilizing strong coupling between PCC voltage and injected current. In addition, sufficient conditions are formulated that guarantee the stability of the closed-loop system with respect to desired operating points. The theoretic results are verified in simulations of case studies operating in varying grid strength.

0.32

Evaluating Grid Strength with Rising Penetration of Inverter Based Resources

eess.SY ·2026-09-22 ·Mohammed N. Khamees, Gad Ilunga, Zhongxia Zhang, Richard E. Tuck
published similarity 0.57
Abstract · Accepted for publication in 2026 CIGRE USNC Grid of the Future (GOTF) Symposium

Over the years, Dominion Energy Virginia (DEV) has experienced recurring power quality disturbances, including voltage and power oscillations, particularly in areas with significant inverter-based generation. While these phenomena suggest a potential relationship to system strength, no definitive correlation has yet been established. This paper presents methodologies for assessing system strength across the DEV network and identifying regions that may be vulnerable to such disturbances. To this end, three grid-strength metrics are evaluated: the Simple Short-Circuit Ratio (SSCR), the Weighted Short-Circuit Ratio (WSCR), and the Composite Short-Circuit Ratio (CSCR). Historical event data will be analyzed using steady-state snapshots from DEV's proprietary Analysis on Demand (ANODE) platform, which provides 10-minute interval load-flow data. These snapshots will be processed using a developed software tool to compute system strength metrics. The analysis will investigate potential correlations between system strength and observed disturbances. Where such correlations are identified, the study will further evaluate the impact of deploying synchronous condensers (SynCons) as a mitigation strategy.

0.31

Development of an EMT model of the Balearic power system

eess.SY ·2026-09-02 ·Yousef Pipelzadeh, Dharshana Muthumuni, Farid Mosallat, Javier Renedo, Silvia Sanz Verdugo +3 more
similarity 0.57
Abstract

The Balearic Islands are striving to achieve 100% renewable energy, which poses new challenges in operating the power system securely and reliably. With a higher integration of inverter-based resources (IBRs) and a reduced presence of conventional synchronous generators, the system strength, particularly short circuit levels, becomes weaker and more susceptible to disturbances; and the total inertia of the system becomes lower. Technology enablers are planned to achieve energy transition in the Balearic power system: a new 2x200 MW VSC-HVDC link (bipole with metallic return), Synchronous Compensators (SC) and Battery Energy Storage Systems (BESS), as fully-integrated network components. Detailed ElectroMagnetic Transient (EMT) simulation studies may be needed to analyse stability of the system, due to the high amounts of power-electronics devices in the system. This paper describes the implementation of an EMT model of the Balearic power system.

0.22

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

eess.SY ·2026-08-31 ·Pengxiang Huang, Shahil Shah
similarity 0.57
Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

0.20

Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

eess.SY ·2026-08-27 ·Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa
similarity 0.56
Abstract · Added IEEE submission notice

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

0.26

Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based Resources

eess.SY ·2026-11-05 ·Henrik Johansson, Qianli Xing, Nathaniel Taylor, Xiongfei Wang
similarity 0.56
Abstract · 9 pages, 11 figures

Conventional power-swing blocking (PSB) schemes for distance protection face new and emerging challenges as the penetration levels of inverter-based resources (IBRs) increase. Several papers highlight interoperability issues concerning faster power swings and unconventional impedance trajectories. Revised relay settings are proposed in attempts to deal with the problems. However, the blinder-based PSB methodology suffers from being dependent on the speed of the apparent impedance trajectory over the tiny region between the blinders, making it difficult to distinguish between fast swings and faults. Moreover, blinders have the inherent limitation that they cannot operate if the measured impedance is inside the blinders when the fault is cleared and immediately enters the distance zones during the first swing cycle - an issue often overlooked in the current literature. This paper proposes a novel PSB scheme based on higher-order incremental quantities (IQs) for difficult swing scenarios with IBRs and synchronous generators (SGs). PSCAD/EMTDC simulations of an SG and an implemented grid-forming (GFM) inverter validate its superior performance compared to conventional dual-blinder PSB schemes. The impacts of GFM inverters on the impedance measured by distance relays during the fault-to-swing transition and first power swing cycle are also discussed.

0.39

Barrier Function Control for the Interconnection of DC Electronic Loads to Utility Grid

eess.SY ·2026-10-22 ·Grigoris Michos, Christos K. Verginis
similarity 0.56
Abstract · preprint for paper to appear in IEEE ISGT Europe conference 2026

This paper proposes a nonlinear control law that facilitates the safe integration of DC electronic loads to the utility grid. Specifically, by employing suitable reciprocal barrier functions, it is rigorously proven that the closed-loop system guarantees constrained operation within a desired operating region, despite the influence of fast converter dynamics and fluctuating constant power load demand. This way, the proposed controller guarantees safety of the electronic components from surges in power demand and high transients. The theoretic results are validated in simulation scenarios, where the performance of the proposed controller is compared against the conventional saturated-PI controller. Contrary to the latter, the proposed method guarantees stable and safe operation, enhancing the system robustness.

0.16