Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa

eess.SY ·submitted 2026-08-27 04:21 UTC · v2

Abstract

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

Comment
Added IEEE submission notice

Closest papers

Nearest neighbours by meaning across the whole index.

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

eess.SY ·2026-08-31 ·Pengxiang Huang, Shahil Shah
similarity 0.59
Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

0.20

Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

eess.SY ·2026-11-02 ·Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid +1 more
published similarity 0.56
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

0.49

Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?

eess.SY ·2026-11-12 ·Ziang Liu, Yimeng Liu, Francis Yunhe Hou
hot direction similarity 0.56
Abstract · 10 pages, 5 figures

Artificial intelligence data centers (AIDCs) are rapidly increasing in number and capacity. These large electronic loads are interfaced through power electronic devices and can sharply reduce grid power intake during fault-induced voltage sags. Disturbances exceeding equipment ride-through capabilities may also trigger protective disconnection, posing risks to power system security. Static synchronous compensators (STATCOMs) and appropriately controlled AIDC uninterruptible power supply (UPS) rectifiers can provide reactive power support during voltage sags. This paper compares the individual and combined effectiveness of STATCOM and UPS-based voltage support in mitigating fault-induced reductions in grid power intake through electromagnetic transient simulations of a 1 GW AIDC connected to an IEEE nine-bus system. Simulation results show that STATCOM support better preserves short-term intake in milder tested faults, whereas UPS coordination maintains rectifier operation under deeper sags by reducing active intake to reserve reactive current capacity. Combined support improves auxiliary load retention and recovery in selected cases. However, severe tested sags still cause substantial grid-demand reductions even with combined support.

0.37

Short-Circuit Current Calculation in DC Shipboard Microgrid Using Operational Admittances

eess.SY ·2026-10-30 ·Pietro Cepollini, Fabio D'Agostino, Federico Silvestro, Antonio Chiarelli
published similarity 0.55
Abstract · Accepted and presented at ESARS-ITEC 2026. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE must be obt…

The increasing adoption of DC shipboard power systems is driven by the need to integrate energy storage systems seamlessly onboard. In this context, accurate calculation of short-circuit current transients is critical for sizing fast-acting protection devices. This paper proposes a methodology to calculate short-circuit current transients based on operational admittance modelling of network elements and power converters. The superposition principle is then applied to calculate current contributions and voltage time profiles. The methodology is validated with a detailed EMT model of a notional LVDC shipboard microgrid section consisting of an active front end, a bidirectional buck-boost converter and two special loads. Results demonstrate that the methodology accurately tracks nodal voltages and the fault current contributions dynamics up to the prospective fault current peak, thus providing a computationally efficient tool for fault analysis and protection coordination in LVDC microgrids.

0.38

An Interline Multiport DC Circuit Breaker with Power Flow Controller

eess.SY ·2026-11-07 ·Maliha Ferdous, Zhi Jin Zhang, Qichen Yang, Maryam Saeedifard
published similarity 0.54
Abstract

Currently, the high-voltage multi-terminal DC (MTDC) grids face two major challenges. First, fast rise rate and lack of zero-crossing point in DC-side fault currents render AC circuit breakers inoperable. Second, DC line currents are passively determined by terminal DC voltages and line resistances, which inherently limits the capability of changing individual line currents for essential grid services such as power flow management and overloading prevention. To address these two limitations, DC circuit breakers (DCCBs) and DC power flow controllers (DCPFCs) have been developed. The conventional DCCBs are two-port devices installed in series with DC lines at their terminals in an MTDC converter substation, so that any fault current flowing through the line can be rapidly cleared. Additionally, a DCPFC can be installed at line terminals to adjust terminal voltages and power exchanges among adjacent lines. As a result, for a substation that connects to multiple lines, it needs to host multiple DCCBs and a DCPFC, which significantly increases the cost and footprint of both the substation and the MTDC grid. To this end, this work proposes an integrated equipment combining multiple DCCBs and a DCPFC, called the interline multiport DCCB with DCPFC, which can reduce the number of components and enhance the economic feasibility of MTDC networks. This paper presents the topology, operation principles, and component selection procedures of the proposed equipment, and compares it with the state-of-the-art technologies. Electromagnetic transient (EMT) simulation results validate the fault interruption and power flow control performance of the interline multiport DCCB with PFC.

0.38

Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control

eess.SY ·2026-11-14 ·Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah +2 more
hot direction similarity 0.54
Abstract · 5 pages, 7 figures

The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.

0.29

Hosting Capacity Assessment of Data Centers with Voltage Ride-Through Capability in Power Systems

eess.SY ·2026-09-02 ·Pengyu Ren, Wei Sun, Fei Teng
similarity 0.54
Abstract

Large data centers are emerging as concentrated, power-electronic grid loads whose abrupt disconnection or transfer to on-site backup supply during voltage disturbances can remove large demand from the power system, and may create a system-level stability problem. Their interconnection feasibility therefore depends not only on steady-state thermal and voltage limits, but also on whether internal power-conditioning systems can maintain IT service while limiting customer-initiated load reduction. This paper presents a voltage ride-through (VRT)-aware data center and grid co-planning framework that couples transmission-level fault simulation with an internal data center ride-through model. Python-based dynamic simulations generate point-of-interconnection (POI) voltage trajectories under selected network faults, and the resulting waveforms drive an internal model incorporating IT and cooling-load dynamics, DC-link, Uninterruptible Power Supply (UPS) response, and converter apparent power limits. The IEEE 118-bus case study shows that internal VRT capability can become a binding interconnection constraint: steady-state planning alone can overestimate feasible data center capacity, whereas increased UPS converter headroom progressively restores hosting capacity. Under the reduced-order response models studied, the grid-forming mode provides greater ride-through margin than the current-limited grid-following mode under the same network fault conditions. The results further show that VRT constraints can materially change both the total hosting capacity of data centers and its spatial allocation across candidate interconnection buses.

0.16

Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage Control

eess.SY ·2026-11-05 ·Siyu Lu, Yang Weng
similarity 0.53
Abstract · 10 pages, 5 figures

Fault-induced transfers of large data centers to backup supply can cause abrupt reductions in grid-served demand. Coordinating reactive-power support to mitigate these transfers requires consideration of facility-specific voltage--duration ride-through characteristics, particularly when support capacity is limited. This paper develops a ride-through-aware extension of quadratic voltage control that assesses voltage deviations relative to the admissible margins specified by these characteristics. We establish four design requirements that jointly express envelope-based severity, duration dependence, and preventive voltage-restoration incentives. Within a multiplicatively gated quadratic class, we derive necessary and sufficient conditions for satisfying these requirements and construct an explicit family of envelope-normalized objectives. We apply the proposed objectives to reactive-power coordination and evaluate their performance on the IEEE 14-bus, New England 39-bus, and NPCC 140-bus systems. Comparisons with Volt/VAR control, conventional nominal-voltage tracking, and recent data-center voltage-control methods demonstrate improved data-center retention under matched reactive-power support constraints. In the IEEE 14-bus study, the proposed controller reduces the mean data-center disconnection rate by 44.8\% and grid-demand loss by 27.4\% compared with the best-performing baseline. These results highlight the benefit of incorporating data-center ride-through requirements into reactive-power allocation.

0.50