An Interline Multiport DC Circuit Breaker with Power Flow Controller

Maliha Ferdous, Zhi Jin Zhang, Qichen Yang, Maryam Saeedifard

eess.SY ·submitted 2026-11-07 21:40 UTC · v1
published

Abstract

Currently, the high-voltage multi-terminal DC (MTDC) grids face two major challenges. First, fast rise rate and lack of zero-crossing point in DC-side fault currents render AC circuit breakers inoperable. Second, DC line currents are passively determined by terminal DC voltages and line resistances, which inherently limits the capability of changing individual line currents for essential grid services such as power flow management and overloading prevention. To address these two limitations, DC circuit breakers (DCCBs) and DC power flow controllers (DCPFCs) have been developed. The conventional DCCBs are two-port devices installed in series with DC lines at their terminals in an MTDC converter substation, so that any fault current flowing through the line can be rapidly cleared. Additionally, a DCPFC can be installed at line terminals to adjust terminal voltages and power exchanges among adjacent lines. As a result, for a substation that connects to multiple lines, it needs to host multiple DCCBs and a DCPFC, which significantly increases the cost and footprint of both the substation and the MTDC grid. To this end, this work proposes an integrated equipment combining multiple DCCBs and a DCPFC, called the interline multiport DCCB with DCPFC, which can reduce the number of components and enhance the economic feasibility of MTDC networks. This paper presents the topology, operation principles, and component selection procedures of the proposed equipment, and compares it with the state-of-the-art technologies. Electromagnetic transient (EMT) simulation results validate the fault interruption and power flow control performance of the interline multiport DCCB with PFC.

Journal ref
CIGRE Paris Session 2026

Closest papers

Nearest neighbours by meaning across the whole index.

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

eess.SY ·2026-08-31 ·Pengxiang Huang, Shahil Shah
similarity 0.64
Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

0.20

DCCB-Capability-Aware Optimal Info-Power Flow for Transmission Switching in AC/MTDC Grids

eess.SY ·2026-10-12 ·Haixiao Li, Aleksandra Lekić
similarity 0.56
Abstract

Transmission switching is an effective approach for restoring operational flexibility and improving the economic performance of AC/multi-terminal DC (MTDC) grids following DC-side faults. Its practical implementation requires that the faulted branch be safely isolated and that the associated switching commands be successfully delivered through the communication network. However, conventional transmission switching models generally represent switching actions using binary variables, without considering the availability of communication resources or whether the corresponding DC circuit breakers (DCCBs) can interrupt the fault current affected by time delay. To address these issues, this paper develops an explicit optimal info--power flow (OIPF) formulation that incorporates information transmission into the post-fault transmission-switching optimization for AC/MTDC grids. The switching status of each DC branch is determined by the availability of its communication path and associated communication resources. In addition, binary switching decisions are supplemented by a DCCB feasibility constraint that limits the estimated delayed-interruption current to the DCCB breaking capability. The resulting problem is formulated as a mixed-integer second-order cone programming (MISOCP) model that can be efficiently solved using off-the-shelf optimization solvers. Numerical results reveal that limited communication capacity and additional routing costs may render electrically beneficial switching actions infeasible or uneconomical, while delay-aware DCCB interruption constraints may favor lower-delay communication routes despite their higher costs.

0.23

Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

eess.SY ·2026-08-27 ·Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa
similarity 0.54
Abstract · Added IEEE submission notice

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

0.26

Short-Circuit Current Calculation in DC Shipboard Microgrid Using Operational Admittances

eess.SY ·2026-10-30 ·Pietro Cepollini, Fabio D'Agostino, Federico Silvestro, Antonio Chiarelli
published similarity 0.51
Abstract · Accepted and presented at ESARS-ITEC 2026. Copyright 2026 IEEE. Personal use of this material is permitted. Permission from IEEE must be obt…

The increasing adoption of DC shipboard power systems is driven by the need to integrate energy storage systems seamlessly onboard. In this context, accurate calculation of short-circuit current transients is critical for sizing fast-acting protection devices. This paper proposes a methodology to calculate short-circuit current transients based on operational admittance modelling of network elements and power converters. The superposition principle is then applied to calculate current contributions and voltage time profiles. The methodology is validated with a detailed EMT model of a notional LVDC shipboard microgrid section consisting of an active front end, a bidirectional buck-boost converter and two special loads. Results demonstrate that the methodology accurately tracks nodal voltages and the fault current contributions dynamics up to the prospective fault current peak, thus providing a computationally efficient tool for fault analysis and protection coordination in LVDC microgrids.

0.38

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

eess.SY ·2026-11-05 ·Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten
code/data similarity 0.51
Abstract · Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z…

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

0.44

Can STATCOM and UPS-Based Voltage Support Mitigate Fault-Induced Reductions in AI Data Center Grid Power Draw?

eess.SY ·2026-11-12 ·Ziang Liu, Yimeng Liu, Francis Yunhe Hou
hot direction similarity 0.49
Abstract · 10 pages, 5 figures

Artificial intelligence data centers (AIDCs) are rapidly increasing in number and capacity. These large electronic loads are interfaced through power electronic devices and can sharply reduce grid power intake during fault-induced voltage sags. Disturbances exceeding equipment ride-through capabilities may also trigger protective disconnection, posing risks to power system security. Static synchronous compensators (STATCOMs) and appropriately controlled AIDC uninterruptible power supply (UPS) rectifiers can provide reactive power support during voltage sags. This paper compares the individual and combined effectiveness of STATCOM and UPS-based voltage support in mitigating fault-induced reductions in grid power intake through electromagnetic transient simulations of a 1 GW AIDC connected to an IEEE nine-bus system. Simulation results show that STATCOM support better preserves short-term intake in milder tested faults, whereas UPS coordination maintains rectifier operation under deeper sags by reducing active intake to reserve reactive current capacity. Combined support improves auxiliary load retention and recovery in selected cases. However, severe tested sags still cause substantial grid-demand reductions even with combined support.

0.29

AC Assessment of DC Power Flow Screening for Data Center Hosting Capacity and Siting

eess.SY ·2026-11-14 ·Haoxiang Wan, Jesus Silva-Rodriguez, Jonghwan Kwon, Xingpeng Li
hot direction similarity 0.48
Abstract · 5 pages, 5 figures, 1 table. Submitted to the 2027 IEEE PES General Meeting

A screening procedure based on direct current (DC) power flow estimates the data center hosting capacity of a candidate bus, termed the DC-screened capacity, and selects the generator commitment that supports it. This paper assesses that estimate under the alternating current (AC) network model. With the selected commitment fixed, an AC optimal power flow reoptimizes dispatch and voltages to find the largest data center load the bus can carry, termed the AC-assessed capacity. On a synthetic Texas system with 123 buses, the DC-screened capacity exceeds the AC-assessed capacity at 113 buses. Across all 123, the ratio of DC-screened to AC-assessed capacity has a median of 143% (a 43% overestimate) and a maximum of 1,070%. At these 113 buses, the DC-screened capacity violates a branch apparent power limit or a generator reactive power limit in the AC model, two limits the DC model omits. The overestimate changes decisions: a 1-GW project passes DC screening at every bus but exceeds the AC-assessed capacity at 37, and the bus ranked first by DC screening has 205.5 MW less AC-assessed capacity than the bus ranked second. Reporting the AC-assessed capacity beside each DC-screened capacity lets planners reject oversized projects or choose better sites.

0.30

Generalized and Unified Power Flow Framework for Converter-Dominated AC/DC Power Grids

eess.SY ·2026-10-18 ·Hamin Chang, Fei Teng, Gyu-Sub Lee, Jae-Won Chang
code/data similarity 0.48
Abstract · Submitted to IEEE Transactions on Power Systems. 10 pages + 10-page appendix (Appendices A-C included at the end). Code: https://github.com/…

Modern power grids increasingly rely on power electronic interfaces, requiring steady-state power flow analysis to accommodate diverse operating modes and network structures. Conventional approaches often rely on system-specific formulations and sequential approaches to handle such complexity. However, these approaches may limit applicability to diverse grid configurations and lead to convergence and computational issues. To address these limitations, this paper proposes a generalized and unified Newton-Raphson (NR) power flow framework for AC/DC hybrid grids. For generalized operational modeling, conventional and droop operating modes of generators and interlinking converters are represented through a common set of coefficients. For generalized structural modeling, models of AC transformers and DC/DC converters accommodate different transformer winding configurations and converter operating modes. For a unified solution, augmented variables are introduced to incorporate droop deadbands, output limits, and converter station losses into a single NR formulation, eliminating the need for sequential outer loops. To validate the effectiveness of the proposed framework, its results are compared with those obtained from existing power flow methods and electromagnetic transient simulations across transmission networks, distribution networks, and microgrids. The implementation is made publicly available to facilitate its use in analyzing AC/DC hybrid grids.

0.36