Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

Pengxiang Huang, Shahil Shah

eess.SY ·submitted 2026-08-31 19:32 UTC · v1

Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

Closest papers

Nearest neighbours by meaning across the whole index.

A Cost-Effective Submodule with Fault-Blocking Capability for Modular Multilevel Converters

eess.SY ·2026-11-05 ·Yu Liu, Shengbo Zhang
similarity 0.69
Abstract · 11 pages, 22 figures

Modular multilevel converter (MMC) has become an attractive technology for high-power electronics applications thanks to its high energy efficiency, high power rating, high modularity, flexible scalability, and superior output waveform quality. It has attracted considerable research attention, and numerous submodule (SM) variants have been developed for different objectives. Among them, the half-bridge SM (HBSM) is the most widely adopted thanks to its simplicity, but it cannot interrupt DC-side short-circuit currents. Various SM topologies with fault-blocking capability have been proposed. These SM topologies contain additional switches and passive components compared to the HBSM, leading to higher capital and operating costs. Aiming at these issue, an SM topology capable to block DC-side fault-currents with a reduced component count is proposed in this paper. The proposed SM includes two variants, one employs only two fully-controlled switches. An operation and control scheme for the proposed SM are also developed and presented in the paper. The functionality of the proposed SM is validated by experiment, and the value of the SM is demonstrated through a test simulation for an high-voltage direct-current (HVDC) transmission system.

0.30

An Interline Multiport DC Circuit Breaker with Power Flow Controller

eess.SY ·2026-11-07 ·Maliha Ferdous, Zhi Jin Zhang, Qichen Yang, Maryam Saeedifard
published similarity 0.64
Abstract

Currently, the high-voltage multi-terminal DC (MTDC) grids face two major challenges. First, fast rise rate and lack of zero-crossing point in DC-side fault currents render AC circuit breakers inoperable. Second, DC line currents are passively determined by terminal DC voltages and line resistances, which inherently limits the capability of changing individual line currents for essential grid services such as power flow management and overloading prevention. To address these two limitations, DC circuit breakers (DCCBs) and DC power flow controllers (DCPFCs) have been developed. The conventional DCCBs are two-port devices installed in series with DC lines at their terminals in an MTDC converter substation, so that any fault current flowing through the line can be rapidly cleared. Additionally, a DCPFC can be installed at line terminals to adjust terminal voltages and power exchanges among adjacent lines. As a result, for a substation that connects to multiple lines, it needs to host multiple DCCBs and a DCPFC, which significantly increases the cost and footprint of both the substation and the MTDC grid. To this end, this work proposes an integrated equipment combining multiple DCCBs and a DCPFC, called the interline multiport DCCB with DCPFC, which can reduce the number of components and enhance the economic feasibility of MTDC networks. This paper presents the topology, operation principles, and component selection procedures of the proposed equipment, and compares it with the state-of-the-art technologies. Electromagnetic transient (EMT) simulation results validate the fault interruption and power flow control performance of the interline multiport DCCB with PFC.

0.38

Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

eess.SY ·2026-08-27 ·Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa
similarity 0.59
Abstract · Added IEEE submission notice

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

0.26

Data-driven current control of modular multilevel converter-based HVDC transmission system

eess.SY ·2026-11-05 ·Victor D. Reyes Dreke, Rahul Rane, Aleksandra Lekić
similarity 0.58
Abstract · 8 pages, submitted to IET AC and DC Power Transmission (ACDC)

Model-based design (MBD) is a mature framework for designing the current controllers of modular multilevel converters (MMCs) in high-voltage direct current (HVDC) transmission systems. In MBD, linear state-space models are preferred for their good trade-off between accurate dynamics prediction and simplicity. However, first-principle derivations often neglect relevant MMC dynamics, which can hinder controller performance. Data-driven (DD) methods can deliver less biased models that capture parameter uncertainties, control-loop interactions, and grid dynamics, yet they remain under-exploited for controlling MMC currents. This paper studies DD current control method based on integral Subspace Predictive Control (iSPC), synthesized directly from input--output data measured in a high fidelity real-time digital simulator (RTDS), and proposes an initial guideline outlining the main steps for its systematic application to MMC current control. The proposed iSPC is compared against state-of-the-art DD solution, and the findings are validated through simulation studies in MATLAB/Simulink.

0.32

Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems

eess.SY ·2026-11-02 ·Alexander Novikov, Luis A. Garcia-Reyes, Anup Joshi, Ahmar Farooque, Junaid Khalid +1 more
published similarity 0.57
Abstract · Danmarks Tekniske Universitetet, Katholieke Universiteit Leuven, Department of Electrical Engineering, Electrical Energy Computer Architectu…

The decarbonization of the energy sector, driven by the Paris Agreement and the European Green Deal, is increasing the share of renewable energy sources (RES) in power systems. Unlike traditional systems, RES-based systems rely on power electronic converters, which creates unprecedented challenges for reliability and resilience. The future power system is expected to combine a low-level AC layer with an upper-level High Voltage Direct Current (HVDC) backbone, which requires new understanding of fault protection, stability, and interaction between AC and DC components, as well as new models and simulation tools. This is especially critical in systems moving towards 100 percent converter-based generation. Protection systems detect, locate, and isolate faults to protect assets while the rest of the system keeps operating. Traditionally, they rely on the large fault currents supplied by synchronous machines. In modern systems, converter controls limit the fault current contribution to about 120 percent of rated current, so relays that distinguish faults from normal overcurrents based on current level may operate incorrectly. In addition, inverter-based resources (IBR) may not inject enough negative and zero sequence current for directional relays to work properly, and converters hold the voltage at a fixed value only within their reach, beyond which it drops quickly. As a result, existing protection schemes may not provide the expected accuracy and reliability. This report reviews the protection challenges identified in recent academic literature for power systems with high shares of converter-based resources. It covers the specific characteristics of RES, the challenges for protection with intelligent electronic devices (IED), the challenges of converter control during faults, and the main solutions proposed in research over the last decade.

0.49

Generalized Frequency-Domain Stability Analysis Formulation for Multi-Terminal HVDC Systems

eess.SY ·2026-11-05 ·Francisco J. Cifuentes Garcia, Thomas Roose, Luis Müller, Jef Beerten
code/data similarity 0.50
Abstract · Under review (10 pages). For the associated packages visit http://github.com/Electa-Git/PowerImpedance.jl and http://github.com/Electa-Git/Z…

The integration of offshore wind farms (OWFs) and the interconnection of different transmission networks are key drivers for multi-terminal DC (MTDC) systems. Bipolar high-voltage direct current (HVDC) employing dedicated metallic return (DMR) are attractive due to their increased availability, which co-exist with monopolar and rigid bipole configurations. While existing works focus on symmetric operation and particular configurations, we present a unified framework for MTDC stability analysis valid for both symmetric and asymmetric conditions. The formulation uses the minimum number of variables without loss of information, and combines the analytical network representation with black-box converter models, thereby enabling sensitivity studies. In addition, a closed-form expression guiding the stability improvement is presented, which requires minimal data exchange between involved parties. The framework is demonstrated on several case studies of increasing complexity, which highlight the importance of considering intra-station converter couplings and possible uncertainty of network parameters.

0.44

An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets

eess.SY ·2026-11-10 ·Sina Mohammadi, Apurv Shukla, Junho Hong, Wencong Su
similarity 0.50
Abstract · This work has been submitted to the IEEE TPWRD for possible publication. Copyright may be transferred without notice, after which this versi…

Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for $k \geq 8$) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for $k = 8$) under noisy conditions.

0.19

DCCB-Capability-Aware Optimal Info-Power Flow for Transmission Switching in AC/MTDC Grids

eess.SY ·2026-10-12 ·Haixiao Li, Aleksandra Lekić
similarity 0.48
Abstract

Transmission switching is an effective approach for restoring operational flexibility and improving the economic performance of AC/multi-terminal DC (MTDC) grids following DC-side faults. Its practical implementation requires that the faulted branch be safely isolated and that the associated switching commands be successfully delivered through the communication network. However, conventional transmission switching models generally represent switching actions using binary variables, without considering the availability of communication resources or whether the corresponding DC circuit breakers (DCCBs) can interrupt the fault current affected by time delay. To address these issues, this paper develops an explicit optimal info--power flow (OIPF) formulation that incorporates information transmission into the post-fault transmission-switching optimization for AC/MTDC grids. The switching status of each DC branch is determined by the availability of its communication path and associated communication resources. In addition, binary switching decisions are supplemented by a DCCB feasibility constraint that limits the estimated delayed-interruption current to the DCCB breaking capability. The resulting problem is formulated as a mixed-integer second-order cone programming (MISOCP) model that can be efficiently solved using off-the-shelf optimization solvers. Numerical results reveal that limited communication capacity and additional routing costs may render electrically beneficial switching actions infeasible or uneconomical, while delay-aware DCCB interruption constraints may favor lower-delay communication routes despite their higher costs.

0.23