An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets

Sina Mohammadi, Apurv Shukla, Junho Hong, Wencong Su

eess.SY ·submitted 2026-11-10 04:21 UTC · v1

Abstract

Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for $k \geq 8$) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for $k = 8$) under noisy conditions.

Comment
This work has been submitted to the IEEE TPWRD for possible publication. Copyright may be transferred without notice, after which this version may no longer be accessible

Closest papers

Nearest neighbours by meaning across the whole index.

Transformer-guided Variable Projection for Phasor and Fault-Time Estimation Under DDC Offset

eess.SY ·2026-11-02 ·Marcus Chen I Wada, Sina Mohammadi, Van-Hai Bui, Wencong Su
unusual similarity 0.67
Abstract · 5 pages, 3 figures, 3 tables. Submitted to PESGM

Decaying DC (DDC) offsets introduce substantial phasor estimation errors during the first post-fault cycle. Recent approaches have sought interpretable waveform representations, but identifying analytical expressions can incur substantial computational costs. This paper proposes a transformer-guided variable-projection estimator that extracts the fundamental phasor, DDC parameters, and fault inception time from point-on-wave (POW) samples as an interpretable analytical expression. An offline-trained transformer provides the signal structure and decay rate, while variable projection refines the parameters and handles windows containing the fault without knowledge of time of fault. Across single- and dual-DDC scenarios with time constants of 2.5--400~ms, the mean maximum overshoot (MO) is at most 2.7% on post-fault windows and 2.2% during online operation, where the DFT reaches 10--14%. The post-fault phasor settles within 5% approximately 12.5~ms after inception. Circuit-level validation on a 230-kV two-source system yields 1.6% mean MO, compared with 9.5% for the DFT.

0.32

On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation Assumptions

eess.SP ·2026-11-06 ·Chetan Mishra, Luigi Vanfretti, Jaime Delaree Jr. and, Kevin D. Jones
similarity 0.58
Abstract

Recent work highlights the inadequacy of standard synchrophasors in capturing high-frequency grid dynamics, including data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. This letter shows how synchrophasor ambient data spectrum itself contains information on attenuation, which provides a way to identify critically impacted measurements and potentially estimate and undo the effect. Results are shown for synthetic data as well as actual synchrophasor estimates from digital fault recorders (DFRs) within the Dominion Energy system.

0.14

Intelligent Fault and Lightning Detection Algorithm for VSC-MTDC grids based on ResNet with Hybrid Attention Mechanism

eess.SY ·2026-09-08 ·Yunqi Zhang
unusual similarity 0.51
Abstract

To address the existing challenges in fault detection for voltage source converter-based multi-terminal DC (VSC-MTDC) grids, this paper proposes an intelligent fault and lightning detection algorithm based on S transform and Residual Network with hybrid attention mechanism (RWHAM).The DC line double-ended initial current traveling waves (ICTWs) are first converted into time-frequency matrices by performing S transform and then visualized as a two-dimensional image. The image effectively characterizes the time-frequency features of ICTWs under different fault and lightning conditions, making it easier to extract critical features for the models. Next, the RWHAM model is constructed and the images are fed into the model to detect internal and external faults and lightning interference. The weight of the key information in the image is increased by hybrid attention mechanism, which in turn improves the fault detection ability of the RWHAM model. Extensive simulations involving 21,620 distinct cases on PSCAD/EMTDC validate the algorithm's high accuracy and rapid response across different types of faults and lightning interference. Furthermore, it exhibits excellent generalization ability when the parameters of VSC-MTDC grids change.

0.26

Non-Blocking Fault Current Limiting Control of Half-Bridge MMCs for MTDC Transmission

eess.SY ·2026-08-31 ·Pengxiang Huang, Shahil Shah
similarity 0.50
Abstract

A key protection requirement in multiterminal HVDC (MTDC) transmission systems is to selectively isolate faulted areas using DC circuit breakers (DCCBs) during DC faults while keeping the rest of the systems in operation. However, in MTDC systems using half-bridge modular multilevel converters (HB-MMCs), the lack of inherent fault current suppression capability in HB-MMCs can cause converter blocking before fault clearance by DCCBs. This work presents an active fault current limiting (AFCL) control strategy for HB-MMCs to mitigate DC fault currents, thus avoiding converter blocking and reducing the breaking capability required of DCCBs. In addition, a systematic approach is proposed to design the AFCL control strategy under converter and network stability constraints. The effectiveness of the proposed strategy is demonstrated through PSCAD on two typical MTDC systems during DC faults.

0.20

A Novel Open Phase Detection Method with Synchronized Phasors for Distribution Systems

eess.SY ·2026-08-23 ·Jinlei Xing, Longhua Mu
similarity 0.49
Abstract · 10 pages

An effective open phase detection is one of the unsolved challenges for utilities. Open phase detection is expected to detect the broken power line before it falls to the ground, to prevent the ignition of wildfires. The existing open phase detection methods are normally based on abnormal currents or voltages due to three phase unbalances after open phase events. For a complicated distribution feeder with multiple branches, current-based methods usually have a limited protection range, and voltage-based methods possibly failed due to the recreated voltage on the open phase due to back-feed. This paper presents a new open phase detection method based on the connection impedance of two measuring points, which is calculated with the synchronized phasors. Under an internal open phase condition, the calculated positive-sequence impedance is much larger than the impedance under other conditions, and its sign is negative. This new method is applicable for a distribution feeder with a closed-loop configuration, or DER units connected at the load side. It is almost not impacted by back-feed. This new method only requires point-to-point communication. This method can be easily implemented in the existing recloser controllers or RTUs. It is scalable, cost effective, and reliable.

0.30

A Hybrid Systems Approach to Parameterizing the PERC1 Model for Data Centers Using Synchrophasor Measurements

eess.SY ·2026-11-16 ·Bukunmi Gabriel Odunlami, Marcos Netto
similarity 0.49
Abstract

The Power Electronic Reconnecting and Ceasing (PERC1) load model represents the timed ceasing and reconnection of large power-electronic loads, including data centers. Voltage thresholds and timers govern its response, with a ramp on reconnection, making it a hybrid dynamical system. This paper formulates PERC1 as a hybrid automaton and uses that structure to identify its parameters from synchrophasor records of grid disturbances. We propose a four-stage identification procedure: mode-sequence identification, estimation of logic parameters from event-time constraints, and joint Gauss-Newton refinement using hybrid trajectory sensitivities and saltation matrices. The resulting salted Fisher information is then used to analyze parameter identifiability. Two structural results are established. The detection and actuation delays are identifiable only through their sum unless a second dip interrupts the reconnection ramp, and a single disturbance leaves one unidentifiable direction in each threshold-delay pair, which two disturbances with different voltage slopes resolve. A case study using synthetic 60 frames/s synchrophasor records demonstrates recovery of the ceasing and reconnection dynamics and identifies poorly observable parameters.

0.27

Reachability-based Time-domain Distance Protection

eess.SY ·2026-08-20 ·Joshua A. Taylor, Nathan Baeckeland, Alejandro D. Domínguez-García
unusual similarity 0.49
Abstract

Distance relays detect faults on transmission lines from local voltage and current measurements. In this paper, we characterize the set of time-domain measurements a distance relay can observe during a fault as a reachable set. We define corresponding fault tests in terms of set-based state estimation. This allows us to model the full network as an RLC circuit with voltage and current sources. In general, computing reachable sets and set-based state estimates is intractable. For each fault type, we construct a reduced-order, two-dimensional model in terms of the apparent voltage and current seen by the relay. This makes all computations efficient, aligns with standard quantities in distance protection, and allows us to define instantaneous fault tests in terms of unsolved differential equations.

0.27

Current-Limiting Control for Fault Ride-Through of LLC-based Solid-State Transformer in Data Centers

eess.SY ·2026-08-27 ·Haoyu Wang, Chi Zhang, Mafu Zhang, Rudy Wang, Peter Barbosa
similarity 0.47
Abstract · Added IEEE submission notice

Solid-State Transformers (SSTs) are increasingly proposed as the interface between distribution grids and data centers due to flexible power flows and fast dynamic response. However, when a short-circuit fault occurs in a load branch, the SST with a voltage-source-type DC-DC stage is forced to shut down due to fault currents. Therefore, current-limiting strategies are strongly needed to prevent catastrophic equipment damage and cascading blackouts by instantly restricting massive current spikes and offering sufficient currents for protection devices to act at the faulted branch. This paper proposes a coordinated DC load fault-tolerant current-limiting and recovery strategy embedded directly in the control of the SST DC-DC stage, avoiding additional hardware cost. Specifically, the fault mechanism of an example LLC resonant converter is studied. Accordingly, a fault detection framework is implemented, a closed-loop current controller is proposed to limit the DC current to a designated value within microseconds by surging the switching frequency and adjusting the duty cycle, and a ramped recovery stage will then restore the DC bus after the fault isolation without inrush currents. Experiments on an LLC converter prototype have verified the feasibility of the proposed current-limiting strategy, enabling faster and lower-cost fault response suitable for resilient data center power architectures.

0.26