Reachability-based Time-domain Distance Protection

Joshua A. Taylor, Nathan Baeckeland, Alejandro D. Domínguez-García

eess.SY ·submitted 2026-08-20 06:13 UTC · v1
unusual

Abstract

Distance relays detect faults on transmission lines from local voltage and current measurements. In this paper, we characterize the set of time-domain measurements a distance relay can observe during a fault as a reachable set. We define corresponding fault tests in terms of set-based state estimation. This allows us to model the full network as an RLC circuit with voltage and current sources. In general, computing reachable sets and set-based state estimates is intractable. For each fault type, we construct a reduced-order, two-dimensional model in terms of the apparent voltage and current seen by the relay. This makes all computations efficient, aligns with standard quantities in distance protection, and allows us to define instantaneous fault tests in terms of unsolved differential equations.

Closest papers

Nearest neighbours by meaning across the whole index.

A Systematic Evaluation of Machine Learning Methods for Fault Detection and Line Identification in Electrical Power Grids

cs.LG eess.SP ·2026-09-15 ·Julian Oelhaf, Georg Kordowich, Paula Andrea Pérez-Toro, Tomás Arias-Vergara, Andreas Maier +2 more
publishedhighly cited similarity 0.52
Abstract · Accepted at ICASSP 2025. 5 pages, 4 figures. Published version: DOI 10.1109/ICASSP49660.2025.10890544

The integration of renewable energy sources into the electrical grid introduces complex challenges in fault detection and coordination of grid recovery mechanisms. Traditional relay protection systems, which operate based on static rules and predefined thresholds, are inadequate for addressing these challenges, particularly in detecting and isolating faults such as short circuits. Consequently, the conventional methodologies applied to electrical network protection frequently fail to achieve optimal performance in fault detection, especially in terms of adherence to safety standards and the selective limitation of damage. Recent research indicates that machine learning (ML)-based approaches can effectively tackle these issues; however, variations in grid configurations and analysis windows have impeded consistent comparative assessments. In this study, we assess the efficacy of various ML models in detecting electrical faults and pinpointing defective transmission lines within a 10 ms measurement interval - a critical time-frame for real-time operational viability, for the first time. The most effective model attained an F1 score of 0.991 +/- 0.018 and demonstrated a processing time of 0.342ms +/- 0.509ms.

0.52

Directionally Supervised Neuromorphic Protection for Distribution Systems Using Local Measurements

eess.SP ·2026-11-12 ·Saurabh Prabhakar, Yubo Song, Pascal Schirmer, Bijaya Ketan Panigrahi, Subham Sahoo
similarity 0.51
Abstract · Submitted to IEEE Transactions on Smart Grid

Reliable protection under varying power system operating conditions requires rapid fault detection while preserving selectivity against external faults and non-fault disturbances. This requirement is particularly challenging in communication-free schemes, where relays must determine trip conditions solely from local electrical measurements. To address this challenge, this paper proposes a directionally supervised neuromorphic protection scheme that integrates disturbance-responsive leaky integrate-and-fire dynamics with a direction-dependent firing threshold to distinguish internal faults from reverse-direction events. The unified relay architecture combines local disturbance detection, directional discrimination, and spike-based trip generation without requiring inter-relay communication. Its performance is evaluated under grid-connected and islanded conditions using a ring microgrid and the IEEE 13-node distribution feeder. Across 240 evaluated fault scenarios, the framework achieves median operating times of 5.4--7.6 ms across the two networks, with 78% of cases operating within 10 ms and 95% within 20 ms. It also maintains protection security during load disturbances, while fault-resistance analysis confirms its response under high-resistance faults. Controller-hardware-in-the-loop (CHIL) experiments using an RTDS simulator and an external dSPACE controller demonstrate trip-command assertion in approximately 10 ms and 5 ms for the tested single-line-to-ground and three-phase-to-ground faults, respectively. The results establish real-time feasibility within the evaluated conditions and characterize operating-time variability across fault types and resistance levels for different network configurations.

0.30

Characterizing Cross-Relay Generalization Failure in Machine Learning-Based Power System Protection

cs.LG ·2026-10-20 ·Nithin Pradeep Nadayil Kizhakkethil, Julian Oelhaf, Christian Bergler, Andreas Maier, Siming Bayer
published similarity 0.50
Abstract · 6 pages, 3 figures. Accepted for presentation at the IEEE Power & Energy Student Summit (PESS 2026), Karlsruhe, Germany

Machine learning-based fault detectors are often evaluated at the relay locations used for training, although local voltage and current measurements vary across power networks. This work investigates cross-relay generalization for binary detection of faults anywhere in the network using local measurements, rather than line-selective tripping. Using 50 ms windows from a simulated 110 kV transmission network, we evaluate a multilayer perceptron across all 64 source target combinations of eight relays and five random seeds. A shared simulation-level split and source-only threshold selection provide a controlled held-out evaluation without target-specific calibration. Despite nearly unchanged mean F1-scores (0.730 within-relay versus 0.734 cross-relay), the mean false-positive rate (FPR) increases from 0.088 to 0.341, while the mean false-negative rate decreases from 0.399 to 0.318. The change is strongly directional: models trained at Bus 2 relays yield a mean FPR of 0.670 at Bus 1 and Bus 3 relays, compared with 0.096 for cross-relay transfers within the same bus group. Linear probing indicates that learned representations retain coarse bus-group information, while exploratory class-conditional latent distribution analysis shows no consistent monotonic association with transfer errors. These findings demonstrate that aggregate metrics can conceal location-structured changes in false-alarm behavior, highlighting the importance of evaluating error types separately when assessing cross-relay generalization.

0.23

Distributed Algorithms for Filtering, Estimation, and Fault Detection over Cyber-Physical-Systems: A Tutorial and Survey

eess.SY eess.SPmath.OC ·2026-08-29 ·Mohammadreza Doostmohammadian, Mahdi Shamsi, Hadi Zayyani, Nader Meskin, Hamid R. Rabiee +2 more
publishedsurvey similarity 0.49
Abstract · Annual Reviews in Control

This survey provides overview of distributed estimation, filtering, and fault detection techniques in the context of cyber-physical systems (CPS). To establish a strong foundation, we first define essential aspects of linear dynamical systems and related graph theoretic concepts, emphasizing observability conditions that are key for local state estimation. After discussing consensus algorithms, this survey highlights single-time and double-time-scale consensus-based estimation and filtering approaches. We provide a detailed comparative analysis of these methodologies, examining their computational requirements, communication overhead, and performance characteristics in resource-constrained environments. We further explore different diffusion-based estimation techniques and observationally redundant designs to enhance resilience and robustness against failures and adversarial attacks. In addition, we investigate distributed fault detection methods that enable local isolation of faults over large-scale CPS. We present both stateless and stateful detection mechanisms, along with threshold-based techniques that balance detection accuracy and false alarm rates. These approaches are essential for maintaining system integrity and preventing cascading failures in critical infrastructure. This survey concludes with an exploration of diverse real-world applications. We examine implementation challenges and algorithm adaptations in smart grid and power networks, social systems, target tracking and localization, and intelligent transportation systems. By bridging theoretical insights with practical applications, this survey and tutorial provides valuable understanding and research directions in the field of distributed algorithm design for CPS, offering both newcomers and experienced researchers a comprehensive resource for addressing current challenges and future opportunities.

0.39

An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets

eess.SY ·2026-11-10 ·Sina Mohammadi, Apurv Shukla, Junho Hong, Wencong Su
similarity 0.49
Abstract · This work has been submitted to the IEEE TPWRD for possible publication. Copyright may be transferred without notice, after which this versi…

Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for $k \geq 8$) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for $k = 8$) under noisy conditions.

0.19

The Race between Protection and Control: Fast Reactive Reserves Against Overvoltage Cascade

eess.SY ·2026-11-14 ·Abdallah Alalem Albustami, Mads Almassalkhi, Ahmad F. Taha
similarity 0.46
Abstract

In an overvoltage cascade, each relay trip removes reactive power absorption and raises the voltage at other plants, often faster than controls can act. This paper determines how much fast reactive power to hold, where, and how fast, so that no contingency trips a plant. A trip certificate allows a relay to pick up if it resets before its delay expires, making the sizing a linear program. A necessary condition identifies the relays that only preventive action can protect, and the reserve of one control decreases with the relay delay and increases with its latency. In nonlinear simulations of four systems, the corrective actions prevent every trip within the analysis window for relays without reset hysteresis, and each plant's own set point is the most effective reserve. A 2\% hysteresis or a small error in the relay voltage can change the reserve as much as the relay delay.

0.24

D-Pingmesh: Dynamic Probing and Fault Localization for Reconfigurable Datacenter Networks

cs.NI ·2026-10-21 ·Yunze Wei, Kaicheng Yang, Xiaohui Xie, Dunkai Mao, Peiying Tao +7 more
published similarity 0.45
Abstract · 15 pages, 13 figures, 1 table. Accepted at the 2026 ACM SIGOPS Annual Technical Conference (SIGOPS ATC 2026)

Pingmesh monitors datacenter networks through periodic pings between servers. In reconfigurable datacenter networks, topology engineering (TPE) and traffic engineering (TE) make uniform server-pair probing inefficient: a pinglist wastes budget retesting common paths while missing low-probability interfaces. Frequent control-plane updates further require rapid pinglist refresh, and cause path ambiguity at control-plane boundaries for fault localization. We present D-Pingmesh, a probing and fault-localization system co-designed with the TPE/TE control plane. Its control-plane-aware generator builds task-efficient pinglists by greedily admitting probes with high interface coverage under the current TPE/TE snapshot. An incremental replay-and-repair mechanism updates pinglists across reconfigurations rather than recomputing from scratch. At control-plane boundaries, a Rho-EM localizer jointly infers per-task old/new-path mixture weights and the fault set through EM-style iteration. We evaluate D-Pingmesh on an 8-pod reconfigurable topology under dynamic TPE/TE. At a 0.99 coverage target, D-Pingmesh uses 17.7x fewer tasks than Pingmesh and generates each pinglist about 5.1x faster than RD-Probe. In ns-3 simulation, boundary-aware localization improves micro F1 from 0.871 to 0.953 over the deTector PLL baseline. A testbed deployment demonstrates second-scale fault localization with low host overhead. These results demonstrate that D-Pingmesh is practical for reconfigurable datacenter networks with control-plane-aware monitoring.

0.49

DynaTrust-VVC: Directional Physics-Informed Trust-Based Detection and Mitigation for Cyber-Resilient Multi-Agent Volt--VAR Control

eess.SY cs.MA ·2026-08-30 ·Md Fazley Rafy, Kamrul Hasan, Anurag K. Srivastava
published similarity 0.45
Abstract · 6 pages, 2 figures and accepted in 2026 Cyber Awareness and Research Symposium (CARS)

Distributed Volt--VAR control relies on voltage measurements and is therefore vulnerable to false-data injection. Neighbor corroboration can distinguish an isolated corrupted measurement from a physical disturbance, but coordinated agents can falsely corroborate one another. This paper proposes DynaTrust-VVC, a cyber-resilient multi-agent Volt--VAR framework that assigns each incoming neighbor message a directional trust value based on the consistency between its reported voltage increment and a sensitivity-based prediction from active- and reactive-power changes. Trust falls immediately after a physics mismatch and recovers gradually after sustained consistency. DynaTrust-VVC further uses a physics-adaptive evidence threshold and counterfactual safe-voltage recovery-based mitigation. The proposed method was validated using a nonlinear IEEE 123-bus feeder with minute-resolution residential profiles and 27 matched replicates. DynaTrust-VVC identifies a coordinated three-bus attack one minute after onset in all 27 matched replicates, whereas an otherwise identical configuration with fixed neighbor trust identifies none. The composite resilience index also increases from 0.227 to 0.315, with no statistically significant increase in the benign false-alarm rate.

0.41