On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation Assumptions

Chetan Mishra, Luigi Vanfretti, Jaime Delaree Jr. and, Kevin D. Jones

eess.SP ·submitted 2026-11-06 17:45 UTC · v1

Abstract

Recent work highlights the inadequacy of standard synchrophasors in capturing high-frequency grid dynamics, including data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. This letter shows how synchrophasor ambient data spectrum itself contains information on attenuation, which provides a way to identify critically impacted measurements and potentially estimate and undo the effect. Results are shown for synthetic data as well as actual synchrophasor estimates from digital fault recorders (DFRs) within the Dominion Energy system.

Closest papers

Nearest neighbours by meaning across the whole index.

Does Synchrophasor Attenuation Preclude Detection of High-Frequency Oscillations?

eess.SP ·2026-10-19 ·Chetan Mishra, Luigi Vanfretti, Jaime Delaree, Kevin D. Jones
theory similarity 0.75
Abstract

Recent work suggests that standard synchrophasors are inadequate for capturing high-frequency data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. We prove that widely used periodogram and RMS energy detectors remain largely robust to it and confirm this by simulation.

0.21

Locating Power System Oscillation Sources by Extracting Interharmonics from Synchrophasor Data

eess.SY ·2026-09-03 ·Sophia Xu, Wilsun Xu
similarity 0.59
Abstract · 6 pages and 13 figures

Recent studies have shown that oscillating phasors arise from beating waves caused by interharmonics. This finding has led to an interharmonic-based oscillation source-location method. But waveform data needed for the method are less available than PMU synchrophasor data. This paper investigates whether interharmonics can be extracted directly from phasor data for similar applications. The results show that, for certain oscillation phenomena, phasor data can support interharmonic extraction and oscillation source location. Sensitivity studies have identified the requirements, and a cloud-based software tool is developed for PMU-based source location.

0.28

PMU Foundation Model Bridge: A Tool for Connecting Synchrophasor Streams to Time Series Foundation Models

eess.SY cs.SE ·2026-10-24 ·Haozong Wang, Jiahui Yang, Yuru Wu, Chujie Zeng, Qian Liu +4 more
code/dataunusual similarity 0.58
Abstract

This paper presents PMU Foundation Model Bridge, an open source tool that connects online phasor measurement unit (PMU) or phasor data concentrator (PDC) streams to publicly available time series foundation models (TSFM). Through a desktop interface or command line interface, users can select measurement channels, define preprocessing, choose TSFMs, and configure outputs. In the initial release, 4 publicly available TSFMs were supported, including Chronos-2, TimesFM 2.5, Timestral, and TimesFM-3. The tool supports both file and synchrophasor streaming outputs, therefore enabling both offline use and integration into C37.118-based online workflow applications. In addition to supporting raw synchrophasor data, the framework provides a preprocessing layer for deriving customized additional quantities for forecasting. The tool is validated using a virtual PMU and real-time laboratory measurements from a frequency disturbance recorder (FDR). The tool aims to support community research on combining synchrophasor technology with TSFMs.

0.33

An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets

eess.SY ·2026-11-10 ·Sina Mohammadi, Apurv Shukla, Junho Hong, Wencong Su
similarity 0.58
Abstract · This work has been submitted to the IEEE TPWRD for possible publication. Copyright may be transferred without notice, after which this versi…

Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for $k \geq 8$) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for $k = 8$) under noisy conditions.

0.19

A Hybrid Systems Approach to Parameterizing the PERC1 Model for Data Centers Using Synchrophasor Measurements

eess.SY ·2026-11-16 ·Bukunmi Gabriel Odunlami, Marcos Netto
similarity 0.58
Abstract

The Power Electronic Reconnecting and Ceasing (PERC1) load model represents the timed ceasing and reconnection of large power-electronic loads, including data centers. Voltage thresholds and timers govern its response, with a ramp on reconnection, making it a hybrid dynamical system. This paper formulates PERC1 as a hybrid automaton and uses that structure to identify its parameters from synchrophasor records of grid disturbances. We propose a four-stage identification procedure: mode-sequence identification, estimation of logic parameters from event-time constraints, and joint Gauss-Newton refinement using hybrid trajectory sensitivities and saltation matrices. The resulting salted Fisher information is then used to analyze parameter identifiability. Two structural results are established. The detection and actuation delays are identifiable only through their sum unless a second dip interrupts the reconnection ramp, and a single disturbance leaves one unidentifiable direction in each threshold-delay pair, which two disturbances with different voltage slopes resolve. A case study using synthetic 60 frames/s synchrophasor records demonstrates recovery of the ceasing and reconnection dynamics and identifies poorly observable parameters.

0.27

Cyber-physical attack detection approaches in the wide-area measurement system

cs.LG ·2026-10-30 ·Zakaria El Mrabet, Prakash Ranganathan
published similarity 0.55
Abstract

Improving situational awareness within the Smart Grid is an effective preventive measure to detect potential anomalies, and avoid their adverse consequences. A wide area measurement system (WAMS) based Phasor Measurement Unit (PMU) can assist in improving visibility within the grid by collecting relevant measurements including magnitude, phase angle, frequency, voltage, and current, with a precise GPS-based timestamp. So far, there are more than 2500 PMUs deployed in the North American power grid, where each of which generates between 30 and 60 samples/s, roughly 1.5 TB/month of streamed data. Thus, processing such large PMU streams requires expensive computational resources and faster algorithms. This paper provides state-of-the-art cyber and physical anomalies in the WAMS and analyses their impact on the integrity and availability of the system. Next, it investigates the current anomaly detection approach in historical and streaming PMU data, including conventional machine learning and hybrid approaches, and assesses their advantages and main drawbacks. Lastly, it sheds light on the importance of handling missing PMU data and concept drifts.

0.68

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.53
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.34

Frequency Measurement Practices for Inertia Assessment in Inverter Based Resources Dominated Power Systems

eess.SY ·2026-09-28 ·Christos M. Nikolakakos, Hassan Haes Alhelou, Nikos Hatziargyriou
similarity 0.53
Abstract · Under Review in IEEE Transactions on Power Systems

Transmission system operators and protective relays compute the rate of change of frequency (RoCoF) from frequency averaged over tens to hundreds of milliseconds, as standards and grid codes specify. Any response delivered inside that window lowers the measured RoCoF, so the inferred inertia depends on the window and the responses in service. This paper defines the windowed inertia estimate and derives an exact identity the system inertia divided by one minus the fraction of the disturbance energy delivered inside the window and a closed-form prediction that applies the same estimator to the trajectory of a linear response model. Eleven IEEE 9-bus RMS runs synchronous, grid-following and grid-forming configurations, disturbance sizes and parameter sweeps are reproduced by that model, and the identity closes on the measured response powers. Fast frequency response inflates the estimate most: at 500 ms a grid-following system with 20 % less synchronous inertia reports the same value as the all-synchronous system, the grid-forming system a higher one. On a reduced Greek transmission system the 500ms estimate exceeds the inertia by 17-26%, and a scenario with 10% less synchronous inertia reports more than the all-synchronous scenario's inertia. Operators can thus compute what their measurement reports.

0.26