Does Synchrophasor Attenuation Preclude Detection of High-Frequency Oscillations?

Chetan Mishra, Luigi Vanfretti, Jaime Delaree, Kevin D. Jones

eess.SP ·submitted 2026-10-19 14:26 UTC · v1
theory

Abstract

Recent work suggests that standard synchrophasors are inadequate for capturing high-frequency data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. We prove that widely used periodogram and RMS energy detectors remain largely robust to it and confirm this by simulation.

Closest papers

Nearest neighbours by meaning across the whole index.

On PMU Adequacy for Wideband Dynamics Tracking Beyond Attenuation Assumptions

eess.SP ·2026-11-06 ·Chetan Mishra, Luigi Vanfretti, Jaime Delaree Jr. and, Kevin D. Jones
similarity 0.75
Abstract

Recent work highlights the inadequacy of standard synchrophasors in capturing high-frequency grid dynamics, including data center oscillations, primarily due to filtering and windowing attenuation during phasor estimation. This letter shows how synchrophasor ambient data spectrum itself contains information on attenuation, which provides a way to identify critically impacted measurements and potentially estimate and undo the effect. Results are shown for synthetic data as well as actual synchrophasor estimates from digital fault recorders (DFRs) within the Dominion Energy system.

0.14

Locating Power System Oscillation Sources by Extracting Interharmonics from Synchrophasor Data

eess.SY ·2026-09-03 ·Sophia Xu, Wilsun Xu
similarity 0.60
Abstract · 6 pages and 13 figures

Recent studies have shown that oscillating phasors arise from beating waves caused by interharmonics. This finding has led to an interharmonic-based oscillation source-location method. But waveform data needed for the method are less available than PMU synchrophasor data. This paper investigates whether interharmonics can be extracted directly from phasor data for similar applications. The results show that, for certain oscillation phenomena, phasor data can support interharmonic extraction and oscillation source location. Sensitivity studies have identified the requirements, and a cloud-based software tool is developed for PMU-based source location.

0.28

Optimally Setting RMS Energy Bands for Detecting Oscillations

eess.SP ·2026-10-10 ·Chetan Mishra, Luigi Vanfretti, Bikal Pudasaini, Jaime Delaree, Kevin D. Jones
similarity 0.59
Abstract

Oscillation monitors have root-mean-square (RMS) energy detectors at their core. These detect oscillation in a predefined frequency band by comparing the signal power in that band with a threshold (usually set empirically). A key design decision is the choice of frequency bands. Traditionally, for monitoring the stability of wide-area electromechanical modes, finer bands were set below 1 Hz, while higher frequencies were covered by wider bands. However, this approach can yield poor detection in modern power systems with fast and largely unknown local dynamics. This letter proposes an algorithm to set frequency bands from the ambient noise spectrum to maximize the average detection performance.

0.25

PMU Foundation Model Bridge: A Tool for Connecting Synchrophasor Streams to Time Series Foundation Models

eess.SY cs.SE ·2026-10-24 ·Haozong Wang, Jiahui Yang, Yuru Wu, Chujie Zeng, Qian Liu +4 more
code/dataunusual similarity 0.50
Abstract

This paper presents PMU Foundation Model Bridge, an open source tool that connects online phasor measurement unit (PMU) or phasor data concentrator (PDC) streams to publicly available time series foundation models (TSFM). Through a desktop interface or command line interface, users can select measurement channels, define preprocessing, choose TSFMs, and configure outputs. In the initial release, 4 publicly available TSFMs were supported, including Chronos-2, TimesFM 2.5, Timestral, and TimesFM-3. The tool supports both file and synchrophasor streaming outputs, therefore enabling both offline use and integration into C37.118-based online workflow applications. In addition to supporting raw synchrophasor data, the framework provides a preprocessing layer for deriving customized additional quantities for forecasting. The tool is validated using a virtual PMU and real-time laboratory measurements from a frequency disturbance recorder (FDR). The tool aims to support community research on combining synchrophasor technology with TSFMs.

0.33

A Hybrid Systems Approach to Parameterizing the PERC1 Model for Data Centers Using Synchrophasor Measurements

eess.SY ·2026-11-16 ·Bukunmi Gabriel Odunlami, Marcos Netto
similarity 0.50
Abstract

The Power Electronic Reconnecting and Ceasing (PERC1) load model represents the timed ceasing and reconnection of large power-electronic loads, including data centers. Voltage thresholds and timers govern its response, with a ramp on reconnection, making it a hybrid dynamical system. This paper formulates PERC1 as a hybrid automaton and uses that structure to identify its parameters from synchrophasor records of grid disturbances. We propose a four-stage identification procedure: mode-sequence identification, estimation of logic parameters from event-time constraints, and joint Gauss-Newton refinement using hybrid trajectory sensitivities and saltation matrices. The resulting salted Fisher information is then used to analyze parameter identifiability. Two structural results are established. The detection and actuation delays are identifiable only through their sum unless a second dip interrupts the reconnection ramp, and a single disturbance leaves one unidentifiable direction in each threshold-delay pair, which two disturbances with different voltage slopes resolve. A case study using synthetic 60 frames/s synchrophasor records demonstrates recovery of the ceasing and reconnection dynamics and identifies poorly observable parameters.

0.27

Real-Time Edge-based Detection of Correlated AI Data-Center Load Episodes

eess.SY ·2026-08-24 ·Chandan Chaudhary, Abanish Tiwari, Yansong Pei, Mohammed Ben-Idris, Joydeep Mitra
similarity 0.45
Abstract · Submitted to 2027 IEEE PES Grid Edge, to be held in 19-22 April, Salt Lake City, Utah, USA

Artificial-intelligence data centers running bulk-synchronous training can impose sub-second power swings. When several facilities synchronize their training cycles, these load variations become spatially correlated and amplify the aggregate disturbance on the grid. A grid operator without access to data-center telemetry must infer this correlation from electrical measurements alone. However, the required observation time and the feasibility of detection on substation-deployable hardware remain uncharacterized. This paper develops a correlation-based detection method to classify the multi-facility operating regime from cross-facility power measurements. Analytical derivations and experimental validation show that the resulting detection confidence increases with the observation-window length at a rate governed by the load correlation time. The method is demonstrated in a real-time hardware-in-the-loop testbed, where load setpoints generated from a validated semi-Markov data-center load model are applied to an electromagnetic-transient grid simulation on a Real-Time Digital Simulator. A compact classifier built on pairwise power correlations runs on an edge device in this loop and determines whether the data-center load variations are independent or spatially correlated. The cross-facility correlation separates the independent and correlated cases across independent realizations. The held-out detection accuracy improves with the observation window, consistent with the predicted relation. A raw-waveform network fails to generalize, supporting pairwise correlation as the discriminative signal. The detector executes in real time on commodity edge hardware. A closed-loop demonstration against the running simulator tracks a regime change within one observation window.

0.43

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.45
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.34

Measurement-Based Assessment of Decadal Inertia and Primary Frequency Response Trends in the US Eastern Interconnection

eess.SY ·2026-10-30 ·Saurav Dulal, Mark Baldwin, Narges Ghiasi, Mohammed Olama, Ali R. Ekti +2 more
similarity 0.43
Abstract · Presented in CIGRE 2026 Grid of the Future Symposium.The paper has 12 pages and 6 figures in total

Changes in the generation mix of the U.S. Eastern Interconnection (EI) raise questions about long-term frequency performance, particularly inertia and primary frequency response (PFR). This paper jointly examines these characteristics using synchronized FNET/GridEye frequency measurements and confirmed generation-trip events from 2013 to 2025. A representative EI frequency trajectory is constructed using the median of geographically distributed measurements. Effective inertia is estimated quarterly from the early post-disturbance rate of change of frequency (RoCoF), using a 3-second window and least-squares fitting. PFR is evaluated using the beta metric, which measures aggregate frequency response from disturbance size and the A-to-B frequency deviation. Annual beta estimates are obtained after filtering events by starting frequency and disturbance size to improve comparability across years. Results show that EI effective inertia varies seasonally and follows a non-monotonic trend rather than a uniform long-term decline. Over the same period, coal generation decreased while natural gas, wind, and solar generation increased. Changes in synchronous generator commitment and operating conditions may have offset some expected inertia reductions. Filtered beta generally increased from the mid-2010s to the early 2020s, with year-to-year variability thereafter. The different trends show that early inertial behavior and broader aggregate frequency response have not evolved in parallel. Joint analysis of inertia and beta offers a more complete measurement-based assessment of EI frequency performance during the generation transition.

0.30