Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

Min-Seung Ko, Hao Zhu

eess.SY ·submitted 2026-11-17 01:34 UTC · v1

Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

Closest papers

Nearest neighbours by meaning across the whole index.

Forced Oscillations in Power Systems Induced by Data Centers Hosting AI Workloads

eess.SY ·2026-09-23 ·Jovan Krajacic, Georgia Pierrou, Maitraya Desai, Gabriela Hug, Gustavo Valverde
similarity 0.68
Abstract · Revised and extended version of the manuscript previously posted on TechRxiv: https://www.techrxiv.org/doi/full/10.36227/techrxiv.176127304.…

Power swings in large Data Centers (DTCs) running Artificial Intelligence (AI) workloads can excite poorly damped modes in power systems. The resulting forced oscillations can lead to flicker, equipment disconnection, or blackouts. This paper investigates the risks of such load fluctuations for different system strengths and damping conditions. Using an analytical approach based on transfer functions, we identify critical DTC locations in the power grid at which load fluctuations could induce the largest forced oscillations and further characterize the harmonic spectrum of the resulting system response. Depending on the frequency and magnitude of the DTC load fluctuations, forced oscillations can become unbounded. The underlying instabilities are classified into saddle-node bifurcations of the forced periodic response and impasse-surface encounters, using Floquet multipliers and the minimum singular value of the algebraic Jacobian. Furthermore, the impact of different duty cycles and harmonic components beyond the fundamental oscillation frequency in square-wave load profiles is analyzed. Finally, the interaction of two oscillating DTCs is investigated for different locations and forcing frequencies, considering both synchronized and unsynchronized operation. The findings can help system operators to define new regulations on the maximum load fluctuations permitted for DTC facilities at specific grid locations, without negatively affecting the stability and operation of the system.

0.56

Designing Grid-Aware Dynamic Specifications for Large Data Center Loads

eess.SY ·2026-09-16 ·Ashutossh Gupta, Vassilis Kekatos
similarity 0.65
Abstract · 10 pages, 8 figures, IEEE TPWRS

As data center (DC) loads increasingly penetrate the power grid, there is an urgent need for grid operators to provide clear dynamic specifications to DC owners to ensure safe grid operation. To this end, we study two salient behaviors of large language model (LLM) training loads: abrupt ramps at job initiation and termination, which induce transient frequency excursions, and sustained periodic oscillations during training, which result in oscillatory steady-state behavior. For ramping loads, we show that nodal rotor frequencies can be accurately approximated by the center-of-inertia (COI) frequency and derive analytical expressions for its nadir and rate of change of frequency (RoCoF). These expressions determine allowable combinations of ramp times and steady-state load demands satisfying prescribed frequency limits. For oscillatory loads, we derive spectral specifications on their Fourier coefficients and show that the admissible coefficient set can be approximated by a polytope. We further obtain a compact representation via its maximum-volume inscribed ellipsoid, which we show is axis-aligned. Numerical tests on the WECC 179-bus system demonstrate that the resulting specifications remain valid for higher-order nonlinear dynamics. The proposed framework provides actionable specifications for regulating the dynamic behavior of large DC loads and informing load-shaping mechanisms within the data center ecosystem.

0.50

Quantifying Power to Voltage and Frequency Dynamics for Oscillation Propagation Assessment

eess.SY ·2026-09-03 ·Onur Alican, Dionysios Moutevelis, Marc Cheah-Mañe, Oriol Gomis-Bellmunt, Eduardo Prieto-Araujo
benchmark similarity 0.64
Abstract

The integration of Inverter-Based Resources (IBRs) into power systems introduces multi-timescale dynamics and oscillations which may propagate to distant areas and endanger the safe system operation. These oscillations pose a significant challenge as their source, frequency, and propagation pathways are often challenging to identify in large interconnected systems, comprising numerous synchronous machines and IBRs. For the above reasons, analytical tools that identify the sensitivity of the system to oscillations within a large frequency spectrum, affecting both voltage and frequency variables across various network locations, are of interest. This paper addresses this topic by introducing a frequency-domain framework based on linear analysis, which characterizes the sensitivity to oscillations of each network bus voltage and of each generation unit frequency. Within this framework, two quantitative indicators are proposed, namely the Frequency Sensitivity Index (FSI) and Voltage Sensitivity Index (VSI). These indexes are derived analytically from the transfer functions which relate the active and reactive power injections to each bus with the voltage and frequency variables across the network, derived from the linear Electromagnetic Transient (EMT) power system model. The proposed indices quantify the sensitivity of the system to oscillations of different type and frequency, providing insights for both oscillation detection and propagation analysis. The methodology is applied to a case study based on the modified IEEE 68-bus benchmark system under partial and full IBR penetration, while its accuracy is validated through EMT time-domain simulations using linear and nonlinear models developed in Matlab/Simulink environment.

0.29

Profile Screening and Frequency-Secure Operating Limit Derivation for Data Center Microgrids

eess.SY ·2026-11-17 ·Zishuo Yang, Yu Ma, Jong Ha Woo, Aaditya Pandey, Wenyuan Tang +2 more
similarity 0.63
Abstract

Rapid power variations from artificial intelligence (AI) workloads pose frequency-security challenges for islanded data-center microgrids. This paper proposes a generator step- response-based framework to rapidly screen candidate load pro- files and derive frequency-secure operating limits for IT workload scheduling. Identified generator responses are superimposed to assess the cumulative frequency effects of successive load changes without repeated dynamic simulations. The framework identifies potentially unsafe intervals and determines allowable load magni- tudes, ramp rates, and minimum event spacing, while accounting for prediction uncertainty and governor limits. Validation on a 2.5 MVA islanded microgrid with eight generator configurations and 14 synthetic AI workload profiles shows that 94.75% of 40,208 assessment windows receive decisive screening labels, with no frequency-violating windows classified as secure.

0.37

System-Level Factors Influencing AGC Cyber-Attack Success and RAS Vulnerability in Multi-Area Grids

eess.SY ·2026-10-30 ·Abdulmannan Ajabnoor, Zhi Jin Zhang, Maryam Saeedifard, Dominic Groß
published similarity 0.62
Abstract

Automatic generation control (AGC) stabilizes frequency and scheduled power exchanges among interconnected areas, yet its reliance on communication networks introduces cyber-vulnerabilities. This work examines coordinated AGC cyber-attacks in the presence of remedial action schemes (RAS) and identifies operating conditions under which an attacker can drive grid frequency beyond safe limits while evading RAS. A feedback-based attack policy is used to manipulate AGC signals and steer system frequency toward unsafe trajectories. Then, a large nested-loop parametric sweep---spanning attacked-area inertia relative to its interconnected neighboring area, AGC capacity versus maximum tie-line transfer, AGC update rate, load damping, and bi-directional power transfers---generates over 1.45 million scenarios. These are classified using a decision tree to establish guidelines to distinguish successful from unsuccessful attacks based on frequency deviations. The resulting vulnerability guidelines are validated on a three-area system using phasor-domain simulations with IEEE 9-bus area models, detailed turbine--governor dynamics, and under/over-frequency load and generation shedding. Results show that specific combinations of AGC capacity, inertia distribution, and pre-attack tie-line loading increase the likelihood of successful attacks, offering operators actionable criteria for identifying vulnerable operating conditions.

0.41

Attack-Resiliency Analytics for Wide-Area Control Systems in Smart Grids

eess.SY ·2026-09-29 ·Mohammad Zakaria Haider, Prabin Mali, Nur Imtiazul Haque, Muhammad Nadeem, Sumit Paudyal +1 more
similarity 0.61
Abstract

Wide-area monitoring, protection, and control (WAMPAC) systems damp inter-area oscillations in large interconnected grids, but their reliance on synchronized PMU measurements carried over wide-area networks exposes them to false data injection (FDI) attacks. This paper presents an attack-resiliency analytics framework that formally models the coupled dynamics of the wide-area damping loop, automatic generation control, and the governor and excitation systems, and formulates the optimal stealthy FDI attack as a mixed-integer linear program (MILP). The anomaly detection model (ADM) enters as a replaceable constraint set: either a static bad-data detection (BDD) rule or a boundary learned from benign operation calibrated to a common false-positive rate. On the IEEE 39 and 118 bus systems, with reference dynamics validated on an OPAL-RT hardware-in-the-loop testbed, the optimal attack with wide-area access attains 3.3 and 8.1 times the benign objective and reaches a 0.5Hz frequency excursion more than twice as fast as an attack confined to automatic generation control. Learned boundaries reduce the attack objective by 15.5 55.0% and prevent over-frequency relay trips in all configurations, with feasible stealthy attacks remaining in every case, and residual risk tracks the width of the learned boundary rather than the detector family.

0.31

Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective Control

eess.SY math.DS ·2026-10-19 ·Cheng Feng
similarity 0.60
Abstract

The grid integration of large data centers poses a growing power-system stability challenge. Rapidly varying computing demand can induce oscillations, while the facilities must provide a prescribed response to grid disturbances. Existing controls address load fluctuations and grid support but do not establish their jointly achievable performance. This paper derives fundamental limits and develops a source-selective controller for simultaneous oscillation isolation and grid support. A coupled closed-loop model gives a condition for distinguishing disturbance sources and reveals a direct isolation-support conflict under grid-import-power feedback alone; additional electrical measurements can remove this pointwise conflict but leave a conditional cross-frequency sensitivity limit. Guided by these limits, we design a local residual-feedback storage controller through convex frequency-domain optimization with stability, isolation, and grid-response constraints across operating points. Tests on a single-generator interconnection and a modified nine-bus network show stronger oscillation isolation than equal-order optimized comparators while meeting the prescribed grid response across operating points.

0.22

Regional Frequency Constrained Dispatch Method Considering Spatial-joint Stochastic Disturbances and Contingencies

eess.SY ·2026-09-04 ·Nian Liu, Yubing Chen, Kai Jiang, Jiahao Liu, Cheng Wang +1 more
similarity 0.60
Abstract

The increasing penetration of renewable energy challenges frequency stability due to high variability and declining inertia. Traditional frequency security constrained dispatch methods fail to capture regional frequency heterogeneity and spatially correlated stochastic disturbances, resulting in inaccurate frequency security enforcement. To address this, a regional frequency constrained dispatch method is proposed, considering the spatially joint stochastic disturbances and contingencies. Firstly, a multi-regional frequency response model is constructed, incorporating the Vine-Copula based characterization of regional stochastic disturbances and regional frequency support. Then, a progressive latent-bottleneck physics-informed neural network is applied to characterize differential frequency nadir terms and regional frequency support integral terms via an encoder-decoder architecture, which enables optimization compatible expressions of system frequency dynamics. Finally, a day ahead dispatch model is developed in which regional stochastic frequency constraints are embedded using a CVaR-based formulation. A case study on the IEEE 118-bus system shows that the proposed method outperforms the unified center of inertia embedded approach in mitigating regional frequency violations, with the regional frequency nadir and RoCoF improved by 32.76% and 2.06%, respectively.

0.32