Designing Grid-Aware Dynamic Specifications for Large Data Center Loads

Ashutossh Gupta, Vassilis Kekatos

eess.SY ·submitted 2026-09-16 16:22 UTC · v1

Abstract

As data center (DC) loads increasingly penetrate the power grid, there is an urgent need for grid operators to provide clear dynamic specifications to DC owners to ensure safe grid operation. To this end, we study two salient behaviors of large language model (LLM) training loads: abrupt ramps at job initiation and termination, which induce transient frequency excursions, and sustained periodic oscillations during training, which result in oscillatory steady-state behavior. For ramping loads, we show that nodal rotor frequencies can be accurately approximated by the center-of-inertia (COI) frequency and derive analytical expressions for its nadir and rate of change of frequency (RoCoF). These expressions determine allowable combinations of ramp times and steady-state load demands satisfying prescribed frequency limits. For oscillatory loads, we derive spectral specifications on their Fourier coefficients and show that the admissible coefficient set can be approximated by a polytope. We further obtain a compact representation via its maximum-volume inscribed ellipsoid, which we show is axis-aligned. Numerical tests on the WECC 179-bus system demonstrate that the resulting specifications remain valid for higher-order nonlinear dynamics. The proposed framework provides actionable specifications for regulating the dynamic behavior of large DC loads and informing load-shaping mechanisms within the data center ecosystem.

Comment
10 pages, 8 figures, IEEE TPWRS

Closest papers

Nearest neighbours by meaning across the whole index.

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.65
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.34

Forced Oscillations in Power Systems Induced by Data Centers Hosting AI Workloads

eess.SY ·2026-09-23 ·Jovan Krajacic, Georgia Pierrou, Maitraya Desai, Gabriela Hug, Gustavo Valverde
similarity 0.61
Abstract · Revised and extended version of the manuscript previously posted on TechRxiv: https://www.techrxiv.org/doi/full/10.36227/techrxiv.176127304.…

Power swings in large Data Centers (DTCs) running Artificial Intelligence (AI) workloads can excite poorly damped modes in power systems. The resulting forced oscillations can lead to flicker, equipment disconnection, or blackouts. This paper investigates the risks of such load fluctuations for different system strengths and damping conditions. Using an analytical approach based on transfer functions, we identify critical DTC locations in the power grid at which load fluctuations could induce the largest forced oscillations and further characterize the harmonic spectrum of the resulting system response. Depending on the frequency and magnitude of the DTC load fluctuations, forced oscillations can become unbounded. The underlying instabilities are classified into saddle-node bifurcations of the forced periodic response and impasse-surface encounters, using Floquet multipliers and the minimum singular value of the algebraic Jacobian. Furthermore, the impact of different duty cycles and harmonic components beyond the fundamental oscillation frequency in square-wave load profiles is analyzed. Finally, the interaction of two oscillating DTCs is investigated for different locations and forcing frequencies, considering both synchronized and unsynchronized operation. The findings can help system operators to define new regulations on the maximum load fluctuations permitted for DTC facilities at specific grid locations, without negatively affecting the stability and operation of the system.

0.56

A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

eess.SY ·2026-11-18 ·Advith Natarajan, Xinyang Zhou, Guido Cavraro
similarity 0.58
Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

0.18

Rented Oscillations: Multi-Tenant Data Center Workload Synchronization Attacks and Mitigation

eess.SY cs.CR ·2026-11-18 ·Zaint A. Alexakis, Li Zhou, S. Gokul Krishnan, Charalambos Konstantinou
similarity 0.57
Abstract

Multi-tenant data center (DC) facilities rent computing capacity on demand, placing controllable load within reach of anyone willing to pay for it. This paper considers a stealthy adversary who rents workstations and runs deliberately unoptimized large language model (LLM) training, synchronizing their consumption into large periodic oscillations while each workload remains individually indistinguishable from benign training. The periodicity of such workloads is characterized experimentally and used to model facility consumption, showing that oscillations emerge from the interaction of concurrent workloads, whether aligned by an adversary or arising naturally. A combined small- and large-signal assessment, under a hardware-grounded threat model whose feasibility is supported by experiments on a supercomputer, locates the oscillatory weak points of the network. MW-scale oscillations are shown to saturate the generators' control limiters, amplifying their effect, while Floquet analysis reveals a lightly damped mode emerging near the forcing frequency. To counter both origins, signal-energy-based detection and mitigation are proposed, the latter re-timing the workloads to minimize the facility's oscillatory energy. The approach is validated through power hardware-in-the-loop (PHIL) experiments and real-time simulations on a surrogate model of the Saudi Arabian transmission network.

0.40

Frequency-Security-Aware Real-Time Economic Dispatch with Data Center UPS Flexibility for Inertia and Primary Frequency Response Services

eess.SY ·2026-11-13 ·Shengyi Wang, Liang Du
hot direction similarity 0.56
Abstract

The increasing penetration of renewable energy and the rapid growth of AI data centers are introducing significant challenges to power system frequency security. There is an urgent need to identify grid-compatible resources capable of providing fast frequency support. This paper proposes a frequency-security-aware real-time economic dispatch (RTED) model that enables data center (DC) uninterruptible power supply (UPS) systems to provide steady-state power balancing, inertia response, and primary frequency response (PFR) services. Specifically, tractable analytical frequency-security constraints are derived and incorporated into the RTED framework through second-order cone programming (SOCP) formulation. The proposed model jointly optimizes energy, reserve, and inertia to minimize system operation cost while preventing under-frequency load shedding (UFLS). Numerical validation on a modified IEEE 39-bus system demonstrates that the proposed RTED model with UPS flexibility can economically support system operation and significantly improve frequency security under active-power deficit disturbances.

0.30

Data Center Load Accommodation under QoS and Checkpoint-Induced Frequency Security Constraints

eess.SY ·2026-10-16 ·Ruolan Cui, Ziang Liu, Chenxi Hu, Francis Yunhe Hou
benchmark similarity 0.56
Abstract · 10 pages

The rapid growth of artificial intelligence workloads is accelerating the expansion and grid interconnection of data centers (DCs). Existing data center load accommodation (DCLA) assessments primarily focus on grid and resource adequacy and often imply that greater workload flexibility always increases accommodable capacity. However, workload flexibility has a dual effect. Workload deferral and temporal shifting can alleviate network congestion, whereas synchronized checkpointing of training workloads can cause large and rapid load reductions, threatening frequency stability. Therefore, DCLA cannot be determined solely by grid adequacy. This paper develops an optimal DCLA method that jointly accounts for workload quality of service (QoS), checkpoint-induced frequency security (FS), and grid adequacy. First, a QoS-aware model characterizes workload-dependent flexibility while ensuring service feasibility. Second, checkpoint-induced FS constraints are developed for periodic and event-triggered power variations, with key frequency-security limits reformulated in algebraic form. Third, a two-stage lexicographic model is developed to maximize DCLA and minimizes the required energy storage (ES) deployment, and then optimizes system operation under the given DC and ES siting and sizing decisions. Case studies show that the proposed method avoids a 40.3% overestimation of DCLA compared with the grid-adequacy benchmark. QoS is the primary limiting factor, while checkpoint-induced frequency-security constraints become more restrictive as training workloads increase. These findings highlight that reliable DCLA should account for both its grid-support value and the associated QoS and FS risks.

0.16

Graph Neural Network Prediction of Frequency Nadir and RoCoF Under Topology Variations

eess.SY ·2026-11-13 ·Linhan Fang, Fan Jiang, Xingpeng Li
similarity 0.55
Abstract

Accurate prediction of frequency dynamics under varying network topologies is essential for rapid frequency security assessment, whereas repeated electromagnetic transient (EMT) simulations are computationally intensive. This paper develops a topology-aware graph neural network with a radial basis function Kolmogorov-Arnold network (RBF-KAN) regression head, termed RK-GNN, to predict frequency nadir and maximum absolute rate of change of frequency (RoCoF). Scenarios combine load scaling, regional load redistribution, and generator redispatch with intact, N-1, and N-2 transmission topologies. After checks for network connectivity, generator reference limits, and numerical consistency, the retained scenarios are simulated in PSCAD to construct the reference dataset. The RK-GNN is evaluated against a conventional deep neural network (DNN) and a baseline GNN. On the IEEE 39-bus system, the RK-GNN reduces the mean absolute errors (MAEs) of nadir and RoCoF by 48% and 59% relative to the DNN and by 42% and 61% relative to the baseline GNN. Incorporating the bridge indicator and disturbance hop distance yields further MAE reductions of 27% and 54%. These results show that the proposed topology-aware architecture provides accurate prediction of both frequency metrics under varying topologies and substantially reduces the need for repeated EMT simulations.

0.23

Grid-Forming E-STATCOMs for Stable Integration of Large-Scale Data Centers: Modeling and Control

eess.SY ·2026-09-27 ·Prabhat Ranjan Bana, Novan Zakkia, Jean-Philippe Hasler, Christer Danielsson
published similarity 0.55
Abstract · To be published in CIGRE: Grid of the Future Symposium 2026, in Richmond, Virginia, US

The rapid expansion of large-scale AI data centers (AIDC) is introducing new stability challenges, particularly in weak or low-inertia networks characterized by fast, step-like demand variations and strict requirements on voltage and dynamic performance. This paper investigates the use of grid-forming (GFM) Enhanced STATCOMs (E-STATCOMs) to support reliable integration of such facilities. A power-admittance-based linear modelling framework is developed to capture system interactions and is validated through detailed EMT simulations. The results demonstrate that E-STATCOMs provide fast, well-damped responses to abrupt load changes while effectively mitigating low-frequency oscillations and interactions with network resonances. By enabling tunable dynamic behavior via a load balancer, virtual impedance, and coordinated active-reactive power support, the proposed approach allows precise shaping of system response and improved regulation at the point of connection. These features make E-STATCOMs a flexible and scalable solution for integrating large data centers into weak grids and long transmission systems, supported by a design-oriented framework that facilitates parameter selection and performance assessment without extensive reliance on EMT studies to meet grid codes and AIDC interconnection requirements.