Data Center Oscillation Isolation and Grid Support: Fundamental Limits and Source-Selective Control

Cheng Feng

eess.SY math.DS ·submitted 2026-10-19 17:50 UTC · v1

Abstract

The grid integration of large data centers poses a growing power-system stability challenge. Rapidly varying computing demand can induce oscillations, while the facilities must provide a prescribed response to grid disturbances. Existing controls address load fluctuations and grid support but do not establish their jointly achievable performance. This paper derives fundamental limits and develops a source-selective controller for simultaneous oscillation isolation and grid support. A coupled closed-loop model gives a condition for distinguishing disturbance sources and reveals a direct isolation-support conflict under grid-import-power feedback alone; additional electrical measurements can remove this pointwise conflict but leave a conditional cross-frequency sensitivity limit. Guided by these limits, we design a local residual-feedback storage controller through convex frequency-domain optimization with stability, isolation, and grid-response constraints across operating points. Tests on a single-generator interconnection and a modified nine-bus network show stronger oscillation isolation than equal-order optimized comparators while meeting the prescribed grid response across operating points.

Closest papers

Nearest neighbours by meaning across the whole index.

Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation

eess.SY ·2026-11-04 ·Quang Manh Hoang, Sina Mohammadi, Phi Long Nguyen, Wencong Su, Van-Hai Bui
similarity 0.63
Abstract · Manuscript is submitted to PESGM2027

Oscillatory power components in AI data-center demand can produce large frequency deviations when they coincide with vulnerable grid modes. Mode-aware hybrid energy storage systems (HESSs) can selectively suppress these components, but their effectiveness degrades when the grid mode changes while the control target remains fixed. This paper proposes a closed-loop grid-mode-adaptive HESS control framework that integrates measurement-based modal identification with mode-selective control. A sliding-window N4SID estimator identifies the local grid dynamics from grid-side power and frequency measurements, and the resulting natural-frequency estimate is used to retune the modal suppression branch assigned to the supercapacitor. The framework is evaluated under a grid-mode shift from 0.50 to 1.35Hz while maintaining equal physical damping and approximately equal load excitation at both frequencies. Compared with the fixed-target controller, the adaptive method reduces the post-change grid-side modal power component from 8.78 to 2.02MW, corresponding to a 76.94% reduction, and substantially lowers the resulting frequency deviation.

0.21

A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center

eess.SY ·2026-11-18 ·Advith Natarajan, Xinyang Zhou, Guido Cavraro
similarity 0.61
Abstract

The rapid growth of data centers is creating new interactions between computational workload and power-system dynamics, with potentially significant implications for grid stability. We develop a four-dimensional nonlinear dynamical model of a data center campus interconnected with the bulk power system through a modified Single Machine Infinite Bus system. The model couples generator swing dynamics with a fluid-limit model of computational workload backlog and a grid-interactive data center power controller that incorporates both frequency feedback and computational backpressure. This formulation captures the coupled evolution of generator frequency, rotor angle, computational workload, and data center power consumption, providing a framework for studying the stability implications of flexible data center operation.

0.22

Grid-Mode-Aware AI Data Center Power Smoothing via Bayesian-Optimized Hybrid Energy Storage System

eess.SY ·2026-11-02 ·Sina Mohammadi, Quang Manh Hoang, Marcus Chen I Wada, Van-Hai Bui, Wencong Su
similarity 0.61
Abstract · 6 pages, 5 figures, Submitted, 2027 IEEE Texas Power and Energy Conference (TPEC)

AI data centers exhibit highly stochastic, volatile power demands from intensive workloads and synchronized GPU training cycles, which can excite grid natural frequencies and threaten system stability. This paper proposes a real-time, forecasting-independent control framework utilizing a Hybrid Energy Storage System (HESS) that coordinates a Battery Energy Storage System (BESS) and a supercapacitor (SC). Employing a parameterized frequency-decoupling and active modal-damping policy, the framework mitigates critical oscillatory load components while smoothing overall power fluctuations. To bypass the heavy computational burden of online receding-horizon optimization, this work introduces an offline Bayesian Optimization (BO) approach to optimally tune real-time control parameters, minimizing a multi-objective cost function that balances grid compliance penalties and storage degradation. Numerical simulations demonstrate that the proposed method ensures grid stability and strong target envelope adherence. Specifically, it reshapes extreme 75-160 MW raw demand fluctuations to largely fit within a tight 10 MW target band, with only brief transient excursions, while attenuating the critical 20 MW oscillatory component below 1 MW to suppress resonant excitation.

0.20

Unlocking AI Data Center Interconnection Capacity Through Coordinated Grid and Data Center Flexibility

eess.SY ·2026-10-04 ·Rida Fatima, Xingpeng Li
similarity 0.60
Abstract

The rapid growth of AI data centers is creating concentrated electricity demands that can exceed available distribution network headroom and delay interconnection. This paper investigates whether capacity can be used effectively by coordinating flexibility on both sides of the interconnection. A day-ahead mixed integer second order cone programming framework maximizes feasible AI data center IT capacity using utility side conservation voltage reduction and network topology reconfiguration, together with data center workload shifting and reserve constrained uninterruptible power supply storage. Background feeder demand uses voltage dependent ZIP models, while the data center is modeled as constant power demand using Training, Inference, and Mixed workload profiles. A two-stage solution first maximizes interconnection capacity and then minimizes feeder losses for the retained capacity, with numerical relaxation screening. Studies on a 116-bus model derived from the IEEE 123-node feeder show that, at the constrained bus-60 connection point, grid side flexibility, driven almost entirely by network reconfiguration, increases feasible IT capacity by approximately 42.5-45.0%, while data center flexibility alone provides approximately 2.1-5.4% gains. Coordinated operation increases feasible IT capacity from approximately 10.5-10.6 MW under BASE operation to 15.3-16.0 MW, corresponding to gains of approximately 45.9-50.8%; the 16.0 MW Inference result is limited by the adopted UPS reserve requirement. Benefits are strongly location dependent and influenced by workload flexibility, deferral duration, PUE, UPS energy and reserve requirements, and feeder loading. Under a combined adverse operating condition, FULL capacity decreases by only 3.4% relative to the nominal Mixed case while retaining substantial additional capacity over BASE.

0.08

Grid-Aware Assessment of Forced Oscillations from Spatially Distributed Large Loads

eess.SY ·2026-11-17 ·Min-Seung Ko, Hao Zhu
similarity 0.60
Abstract

This paper develops a unified analytical framework for assessing forced oscillations induced by spatially distributed large-load fluctuations to determine their grid-aware fluctuation magnitudes. Emerging computational loads, such as hyperscale datacenters, present cyclic power variations with dynamic impacts depending on the waveform characteristics, forcing frequency, and source location. Our grid-aware framework represents these fluctuations using deterministic harmonic and probabilistic spectral models, and analyzes the resulting bus-wise frequency deviations based on a generic grid frequency-response model. Deterministic, risk-aware, and band-based probabilistic severity measures are further developed to obtain admissible fluctuation limits under different assumptions on frequency and phase uncertainty. We also formulate a security-constrained (SC) optimization of locational fluctuation magnitudes among existing large loads, accounting for their aggregated frequency deviation level. Case studies on the IEEE 39-bus and 14-generator Australian systems validate the proposed severity measures and admissible limit analysis. The SC optimization results further show that distributing a given amount of aggregate fluctuation toward dynamically less sensitive locations can substantially reduce system-wide oscillation severity.

0.35

Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics

eess.SY ·2026-11-17 ·Guido Cavraro
similarity 0.59
Abstract

The growing deployment of data centers poses challenges for power-system operation. However, data centers possess flexible resources that can be leveraged to mitigate their impact on the grid and provide grid services. This paper develops a linear-affine dynamic model of a transmission network with multiple data centers, explicitly coupling electromechanical grid dynamics with data center power demand and computational backlog. Grid-aware computing policies are incorporated to represent how data centers adjust their computational power in response to grid frequency deviations and workload backlog. The proposed framework provides a tractable means of investigating the interactions between multiple data centers and the transmission grid and assessing the potential of flexible computing to support power-system stability.

0.26

When Gigawatts of Computational Load Disappear: Cycle-Space Certificates for Grid Synchronization and Transient Stability

eess.SY math.DSphysics.soc-ph ·2026-09-23 ·Michael Chertkov
similarity 0.58
Abstract · 13 pages, 2 figures

Rapid growth of data centers and artificial-intelligence services is producing computational loads at scales once associated mainly with largest power plants. Recent grid events show that a routine transmission disturbance can cause several gigawatts of data-center demand to disconnect or transfer to backup nearly at once. This article revisits the classical synchronization and transient-stability theory needed to reason about such events. We organize four lines of work---graph-based synchronization conditions, winding-number descriptions of nonlinear power flow, separable convex network optimization, and direct energy methods---into a single cycle-space certificate framework for the lossless fixed-voltage model. The static layer gives an exact strict-cohesion test within a prescribed winding cell and reveals the widely used Dörfler--Chertkov--Bullo test as a quadratic surrogate of the same convex problem. The dynamic layer converts the critical-energy calculation into a finite family of convex boundary problems. Standard MATPOWER benchmarks illustrate both what the stronger static test gains and where it gains nothing: the 118-bus case admits $16.2\%$ more loading than the sufficient screen, while the 39-bus case is bridge-limited and the thresholds coincide. A stylized $2.7$-GW 39-bus event further shows that transient margin can change by about a factor of two depending on where balancing power is supplied, even when every final balanced operating point remains statically feasible. The result is a tutorial synthesis and an extensible deterministic certificate for emerging gigawatt-scale computational-load contingencies.

0.53

Source--Grid Coupling in Power System Oscillations: Observational Equivalence, Feedback Detectability, and Modal Interaction

eess.SY eess.SP ·2026-09-17 ·Kai Sun, Bin Wang
similarity 0.58
Abstract · Submitted to IEEE Transactions on Power Systems

The conventional distinction between forced and natural oscillations treats the oscillation source as external to a fixed power-system boundary. This paper develops a coupling-aware dynamical interpretation by explicitly accounting for the directionality of source-grid coupling. It examines when prescribed forcing and a one-way autonomous source are observationally equivalent, and when grid measurements can distinguish the presence of grid-to-source feedback. Matched interface signals yield exact equivalence under the same deterministic grid initial-value problem and measurement map. Bidirectional feedback enables source-grid eigenvalue interaction in the augmented autonomous model, while a reduced two-mode model shows that the interaction depends jointly on loop coupling and complex modal separation. The resulting framework establishes source-grid coupling directionality as a feedback-based dynamical boundary and clarifies when feedback can be inferred from grid-side measurements and why weak feedback may remain unresolved. Simulation studies on a two-area system demonstrate feedback detection within a calibrated source family, while source-model mismatch can be confounded with feedback. A WECC 243-bus system study demonstrates feasibility on a large system and shows that feedback detection need not require exact candidate selection.

0.24