Grid-Mode-Aware AI Data Center Power Smoothing via Bayesian-Optimized Hybrid Energy Storage System

Sina Mohammadi, Quang Manh Hoang, Marcus Chen I Wada, Van-Hai Bui, Wencong Su

eess.SY ·submitted 2026-11-02 16:53 UTC · v1

Abstract

AI data centers exhibit highly stochastic, volatile power demands from intensive workloads and synchronized GPU training cycles, which can excite grid natural frequencies and threaten system stability. This paper proposes a real-time, forecasting-independent control framework utilizing a Hybrid Energy Storage System (HESS) that coordinates a Battery Energy Storage System (BESS) and a supercapacitor (SC). Employing a parameterized frequency-decoupling and active modal-damping policy, the framework mitigates critical oscillatory load components while smoothing overall power fluctuations. To bypass the heavy computational burden of online receding-horizon optimization, this work introduces an offline Bayesian Optimization (BO) approach to optimally tune real-time control parameters, minimizing a multi-objective cost function that balances grid compliance penalties and storage degradation. Numerical simulations demonstrate that the proposed method ensures grid stability and strong target envelope adherence. Specifically, it reshapes extreme 75-160 MW raw demand fluctuations to largely fit within a tight 10 MW target band, with only brief transient excursions, while attenuating the critical 20 MW oscillatory component below 1 MW to suppress resonant excitation.

Comment
6 pages, 5 figures, Submitted, 2027 IEEE Texas Power and Energy Conference (TPEC)

Closest papers

Nearest neighbours by meaning across the whole index.

Grid-Mode-Aware Model Predictive Control of Hybrid Energy Storage Systems for AI Data Center Power Smoothing

eess.SY ·2026-09-03 ·Xin Chen
similarity 0.84
Abstract

To facilitate the grid-friendly integration of highly variable AI data center loads, this paper proposes a grid-mode-aware model predictive control (G-MPC) framework for managing a hybrid energy storage system (HESS) to smooth grid-side power demand. The framework optimally coordinates a battery energy storage system (BESS) and a supercapacitor (SC) by solving a multi-step optimization problem in a receding-horizon manner. In particular, band-pass filter dynamics are directly embedded in the G-MPC formulation to extract and suppress grid-side power components associated with vulnerable grid oscillatory modes, thus mitigating load-induced grid oscillations. The resulting G-MPC optimization jointly minimizes violations of grid-side power-envelope, ramp-rate, and modal-power requirements and the degradation and power-ramping costs of the BESS and SC, while satisfying power limits, state-of-charge limits, and other operational constraints. To enable real-time implementation, a fix-and-re-optimize algorithm is developed to solve each G-MPC problem efficiently while preventing simultaneous charging and discharging. Extensive simulations demonstrate the effectiveness, flexibility, and computational efficiency of the proposed framework. The results also highlight the importance of explicitly suppressing power components associated with vulnerable grid modes, rather than merely reducing overall load variations, to effectively mitigate grid oscillations.

0.40

Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation

eess.SY ·2026-11-04 ·Quang Manh Hoang, Sina Mohammadi, Phi Long Nguyen, Wencong Su, Van-Hai Bui
similarity 0.71
Abstract · Manuscript is submitted to PESGM2027

Oscillatory power components in AI data-center demand can produce large frequency deviations when they coincide with vulnerable grid modes. Mode-aware hybrid energy storage systems (HESSs) can selectively suppress these components, but their effectiveness degrades when the grid mode changes while the control target remains fixed. This paper proposes a closed-loop grid-mode-adaptive HESS control framework that integrates measurement-based modal identification with mode-selective control. A sliding-window N4SID estimator identifies the local grid dynamics from grid-side power and frequency measurements, and the resulting natural-frequency estimate is used to retune the modal suppression branch assigned to the supercapacitor. The framework is evaluated under a grid-mode shift from 0.50 to 1.35Hz while maintaining equal physical damping and approximately equal load excitation at both frequencies. Compared with the fixed-target controller, the adaptive method reduces the post-change grid-side modal power component from 8.78 to 2.02MW, corresponding to a 76.94% reduction, and substantially lowers the resulting frequency deviation.

0.21

Supporting Data Center Grid Integration via Co-Optimized Battery Energy Storage Sizing and Capacity Allocation

eess.SY math.OC ·2026-11-06 ·Wei Wang, Himanshu Sharma, Thiagarajan Ramachandran
similarity 0.70
Abstract

Interconnecting large data centers can be delayed by grid requirements on demand flexibility, ramping limits, and ride-through performance. This paper proposes an optimization-based framework to size a Battery Energy Storage System (BESS) that accelerates data center grid integration by providing BESS capacity required to meet selected flexibility and grid-support requirements. The model co-optimizes BESS power rating and energy capacity while allocating capability across three services: (i) demand response over a specified duration, (ii) mitigation of high-magnitude, high-frequency load fluctuations through reserved active power with zero net state-of-charge change, and (iii) voltage support via reactive power capability at the point of common coupling. Minute-level operational scheduling enforces state-of-charge feasibility and load ramp constraints, and incorporates a controllable queue of delay-insensitive computing tasks to enhance flexibility. A case study using a real data center load profile demonstrates the proposed method and quantifies the BESS power-energy requirements and operational trade-offs needed to satisfy the multi-service constraints, providing practical guidance for interconnection planning and deployment.

0.05

Communication Delay Robust Control of BESS for AI Training Load Smoothing

eess.SY ·2026-09-18 ·Xue Lyu, Wei Du, Sheik Mohammad Mohiuddin, Brett A. Ross
hot direction similarity 0.70
Abstract · 10 pages, 17 figures

AI training loads can exhibit rapid power fluctuations because their power demand differs significantly between computational and communication phases, creating challenging ramp rates at the data center point of common coupling (PCC). Integrating battery energy storage systems (BESS) in data centers is a promising mitigation option. This paper proposes a hybrid BESS control strategy that combines droop-based grid-forming (GFM) control with instantaneous load current-based compensation to suppress high frequency load fluctuations. The GFM control loop regulates the long-term power exchange of the BESS, while the load-following control provides fast compensation for short-term AI workload fluctuations. Communication delay between the load current measurements and the BESS controller is explicitly modeled, and its impact on smoothing performance is analyzed. To mitigate delay-induced degradation, a predictor-based compensation method is incorporated into the BESS control structure. High-fidelity electromagnetic transient simulations are conducted to validate the proposed approach. Results demonstrate effective smoothing of AI training load fluctuations across different grid strength conditions and under time varying communication delays.

0.28

Decision-Focused Learning via Neural Optimization Layers for Battery-Assisted Grid-Import Smoothing in AI Data Centers

eess.SY cs.LGmath.OC ·2026-11-10 ·Xinda Zheng, Canchen Jiang, Frits de Nijs, Edward Lam, Markus Wagner
similarity 0.66
Abstract

Rapid AI data-center power fluctuations challenge grid integration. Sustained grid-import smoothing requires allocating limited battery power and energy under uncertain demand. We formulate risk-aware BESS scheduling that coordinates advance reserve commitments and demand-responsive dispatch, accounting for operating costs, grid-ramp penalties, and their conditional value-at-risk. We develop battery scheduling decision-focused learning (BS-DFL) with a constraint-aware neural optimization layer trained directly from this objective without optimal-solution labels. The trained layer is then frozen to guide demand-predictor learning through scheduling costs and ramping risk, enabling solver-free rolling-horizon scheduling. In a 10,000-minute simulation using loads derived from measured AI workloads, BS-DFL reduces mean absolute minute-to-minute grid-import changes by 71.70% and total scheduling cost by 18.01% relative to an MSE-trained predictor coupled with a mixed-integer linear programming solver, with an average decision time of 18.77 ms.

0.26

Building Seasonal Highways for Residential Energy Hubs: Sizing, planning and operating thermal energy storage

eess.SY math.OC ·2026-10-01 ·Dario Slaifstein, Mohammad Khosravi, Gautham Ram Chandra Mouli, Laura Ramirez-Elizondo, Pavol Bauer
similarity 0.66
Abstract

The operation of residential energy hubs with multiple energy carriers (electricity, heat, mobility) poses a significant challenge due to the energy storage differences in time-constants, round-trip efficiencies and self-discharge rates. Usually, thermal storage exhibits flexibility in yearly planning optimizations or long-term scenarios. However, as optimization horizons shrink (1-48hs) so does their supplied value due to the lower round-trip efficiencies. To avoid this early depletion during operation this paper proposes a data-driven highway to steer the short-term daily control towards long-term optimality. The proposed methodology also presents how to optimally size the thermal storage and avoid yearly simulations and how all of this is related to nonlinearities in the daily operation. The presented framework links seasonal and daily optimizations through dynamic terminal sets and value functions. The seasonally-aware nonlinear economic model predictive controller achieves the most balanced performance, with the second best mean grid cost of all MPCs at -\texteuro 209. It also achieves better battery degradation control than its linear counterparts (between 26-34%) and the best thermal comfort of the nonlinear benchmarks. Nevertheless, the data-driven seasonal highway restrains the ability to control battery degradation and slightly increases computational time.

0.14

Integrated Thermal and Power Management for Wave-Powered Subsea Data Centers via Nonlinear Model Predictive Control

eess.SY ·2026-09-28 ·Wanqun Yang, Jun Chen
similarity 0.65
Abstract · 14 figures and 11 tables

This paper develops an integrated modeling and nonlinear model predictive control (NMPC) framework for coordinating thermal management, flexible workload scheduling, wave-power utilization, and battery operation in a wave-powered subsea data center. Realistic data center workloads are constructed from job-level CPU, memory, and GPU measurements from the MIT Supercloud dataset and divided into interactive and delay-tolerant flexible jobs. Thermal behavior is represented by a three-node lumped model of the IT equipment, recirculating nitrogen, and pressure hull with surrounding seawater as the thermal boundary. The NMPC jointly optimizes the flexible workload power budget and cooling command subject to thermal, battery, and workload constraints. Closed-loop simulations under different workload, thermal, battery, and renewable-generation conditions demonstrate that the proposed framework maintains thermal safety while adapting cooling operation and flexible workload execution to wave-power availability and battery state-of-charge. The parametric studies show that battery capacity and wave-generation capacity strongly affect battery availability and flexible-workload queue accumulation, while excessive renewable generation capacity may lead to increased energy curtailment. Monte Carlo and distance-correlation analyses further show that flexible-job delay is relatively insensitive to the investigated system parameters, whereas terminal battery state-of-charge is primarily influenced by battery energy capacity and wave generation capacity.

0.17

Scarcity Pricing for State-of-Charge Management in Real-Time Markets Under Intra-Day Uncertainty

eess.SY ·2026-11-09 ·Shailesh Wasti, Aravind Retna Kumar, Sushant Varghese, Anthony Giacomoni, Parviz Alivand +2 more
similarity 0.65
Abstract

The growth in renewable resources will increase net load variability and forecast error. Energy storage resources can provide flexibility when ramp capability is limited and contribute to load leveling over the day. The challenge for system operators is how to balance these two functions in real time, when updated net load forecasts are available for a limited lookahead horizon. U.S. electricity markets are seeking ways to manage state-of-charge (SoC) within their energy markets to more efficiently utilize these resources. We propose a method to manage energy storage SoC in a real-time market by extending Hogan's (2013) scarcity pricing framework. A day-ahead SoC schedule is modified using existing multi-interval real-time unit commitment engines as net load forecasts change. To address 30-minute-ahead forecast errors, an updated 5-minute SoC target and a dynamically updated shortage price for violating the constraint are provided to each economic dispatch. We simulate PJM's energy markets for 365 days and demonstrate reliability improvements relative to a strategy that enforces the day-ahead schedule. We show cost reductions and improved price formation relative to a strategy that updates target quantities but uses an administratively chosen shortage penalty.

0.30