CS Paper Radar

Grid-Mode-Aware Model Predictive Control of Hybrid Energy Storage Systems for AI Data Center Power Smoothing

Xin Chen

eess.SY ·submitted 2026-09-03 19:07 UTC · v1

Abstract

To facilitate the grid-friendly integration of highly variable AI data center loads, this paper proposes a grid-mode-aware model predictive control (G-MPC) framework for managing a hybrid energy storage system (HESS) to smooth grid-side power demand. The framework optimally coordinates a battery energy storage system (BESS) and a supercapacitor (SC) by solving a multi-step optimization problem in a receding-horizon manner. In particular, band-pass filter dynamics are directly embedded in the G-MPC formulation to extract and suppress grid-side power components associated with vulnerable grid oscillatory modes, thus mitigating load-induced grid oscillations. The resulting G-MPC optimization jointly minimizes violations of grid-side power-envelope, ramp-rate, and modal-power requirements and the degradation and power-ramping costs of the BESS and SC, while satisfying power limits, state-of-charge limits, and other operational constraints. To enable real-time implementation, a fix-and-re-optimize algorithm is developed to solve each G-MPC problem efficiently while preventing simultaneous charging and discharging. Extensive simulations demonstrate the effectiveness, flexibility, and computational efficiency of the proposed framework. The results also highlight the importance of explicitly suppressing power components associated with vulnerable grid modes, rather than merely reducing overall load variations, to effectively mitigate grid oscillations.

Closest papers

Nearest neighbours by meaning across the whole index.

Grid-Mode-Aware AI Data Center Power Smoothing via Bayesian-Optimized Hybrid Energy Storage System

eess.SY ·2026-11-02 ·Sina Mohammadi, Quang Manh Hoang, Marcus Chen I Wada, Van-Hai Bui, Wencong Su
similarity 0.84
Abstract · 6 pages, 5 figures, Submitted, 2027 IEEE Texas Power and Energy Conference (TPEC)

AI data centers exhibit highly stochastic, volatile power demands from intensive workloads and synchronized GPU training cycles, which can excite grid natural frequencies and threaten system stability. This paper proposes a real-time, forecasting-independent control framework utilizing a Hybrid Energy Storage System (HESS) that coordinates a Battery Energy Storage System (BESS) and a supercapacitor (SC). Employing a parameterized frequency-decoupling and active modal-damping policy, the framework mitigates critical oscillatory load components while smoothing overall power fluctuations. To bypass the heavy computational burden of online receding-horizon optimization, this work introduces an offline Bayesian Optimization (BO) approach to optimally tune real-time control parameters, minimizing a multi-objective cost function that balances grid compliance penalties and storage degradation. Numerical simulations demonstrate that the proposed method ensures grid stability and strong target envelope adherence. Specifically, it reshapes extreme 75-160 MW raw demand fluctuations to largely fit within a tight 10 MW target band, with only brief transient excursions, while attenuating the critical 20 MW oscillatory component below 1 MW to suppress resonant excitation.

0.20

Communication Delay Robust Control of BESS for AI Training Load Smoothing

eess.SY ·2026-09-18 ·Xue Lyu, Wei Du, Sheik Mohammad Mohiuddin, Brett A. Ross
hot direction similarity 0.74
Abstract · 10 pages, 17 figures

AI training loads can exhibit rapid power fluctuations because their power demand differs significantly between computational and communication phases, creating challenging ramp rates at the data center point of common coupling (PCC). Integrating battery energy storage systems (BESS) in data centers is a promising mitigation option. This paper proposes a hybrid BESS control strategy that combines droop-based grid-forming (GFM) control with instantaneous load current-based compensation to suppress high frequency load fluctuations. The GFM control loop regulates the long-term power exchange of the BESS, while the load-following control provides fast compensation for short-term AI workload fluctuations. Communication delay between the load current measurements and the BESS controller is explicitly modeled, and its impact on smoothing performance is analyzed. To mitigate delay-induced degradation, a predictor-based compensation method is incorporated into the BESS control structure. High-fidelity electromagnetic transient simulations are conducted to validate the proposed approach. Results demonstrate effective smoothing of AI training load fluctuations across different grid strength conditions and under time varying communication delays.

0.28

Adaptive Grid-Mode-Aware Hybrid Energy Storage Control for AI Data Center Oscillation Mitigation

eess.SY ·2026-11-04 ·Quang Manh Hoang, Sina Mohammadi, Phi Long Nguyen, Wencong Su, Van-Hai Bui
similarity 0.73
Abstract · Manuscript is submitted to PESGM2027

Oscillatory power components in AI data-center demand can produce large frequency deviations when they coincide with vulnerable grid modes. Mode-aware hybrid energy storage systems (HESSs) can selectively suppress these components, but their effectiveness degrades when the grid mode changes while the control target remains fixed. This paper proposes a closed-loop grid-mode-adaptive HESS control framework that integrates measurement-based modal identification with mode-selective control. A sliding-window N4SID estimator identifies the local grid dynamics from grid-side power and frequency measurements, and the resulting natural-frequency estimate is used to retune the modal suppression branch assigned to the supercapacitor. The framework is evaluated under a grid-mode shift from 0.50 to 1.35Hz while maintaining equal physical damping and approximately equal load excitation at both frequencies. Compared with the fixed-target controller, the adaptive method reduces the post-change grid-side modal power component from 8.78 to 2.02MW, corresponding to a 76.94% reduction, and substantially lowers the resulting frequency deviation.

0.21

Supporting Data Center Grid Integration via Co-Optimized Battery Energy Storage Sizing and Capacity Allocation

eess.SY math.OC ·2026-11-06 ·Wei Wang, Himanshu Sharma, Thiagarajan Ramachandran
similarity 0.73
Abstract

Interconnecting large data centers can be delayed by grid requirements on demand flexibility, ramping limits, and ride-through performance. This paper proposes an optimization-based framework to size a Battery Energy Storage System (BESS) that accelerates data center grid integration by providing BESS capacity required to meet selected flexibility and grid-support requirements. The model co-optimizes BESS power rating and energy capacity while allocating capability across three services: (i) demand response over a specified duration, (ii) mitigation of high-magnitude, high-frequency load fluctuations through reserved active power with zero net state-of-charge change, and (iii) voltage support via reactive power capability at the point of common coupling. Minute-level operational scheduling enforces state-of-charge feasibility and load ramp constraints, and incorporates a controllable queue of delay-insensitive computing tasks to enhance flexibility. A case study using a real data center load profile demonstrates the proposed method and quantifies the BESS power-energy requirements and operational trade-offs needed to satisfy the multi-service constraints, providing practical guidance for interconnection planning and deployment.

0.05

Optimal Coordination of Heat Pump Demand Flexibility and Battery Energy Storage Considering the Operation of Distribution Networks

eess.SY ·2026-10-06 ·Gustavo L. Aschidamini, Guilherme S. Castiglio, Mariana Resener
similarity 0.71
Abstract

Electrifying space heating with heat pumps (HP) and backup electric-resistance heaters (ERH) is incentivized to support decarbonization but increases voltage and thermal issues in distribution networks. Direct load control (DLC) of smart thermostats (ST) provide grid support, yet, to the best of our knowledge, existing methods do not co-optimize this flexibility with grid-scale battery energy storage systems (BESS) and voltage-regulation devices, and do not use ERH for preheating, limiting peak demand reduction and undervoltage mitigation. We propose a mixed-integer linear programming (MILP)-based model predictive control (MPC) framework that coordinates ST setpoints for preheating and setback, grid-scale BESS, on-load tap changers, switched capacitor banks, and step voltage regulators. The framework is evaluated on 23-node and 733-node distribution networks, including a real-data-based feeder, across multiple realized days. On the 23-node feeder with 50% HP penetration and 50% DLC participation, the proposed framework reduces the feeder peak by 23.1%, and by 27.1% with the co-optimized BESS. Rolling-horizon setpoint optimization contributes 6.5 percentage points beyond a day-ahead ST schedule (16.6%), and dispatching the ERH for preheating adds 2.7 percentage points beyond backup-only operation (20.4%). On the 733-node feeder, where thermal congestion is the binding constraint, the framework reduces overloaded branches by 94% and overloaded transformers by 47%. These results demonstrate the potential of coordinated demand flexibility and voltage regulation to accommodate heating electrification.

0.12

Battery Energy Storage Sizing in PV Ramp-Rate Smoothing using Constraint-Aware Reinforcement Learning-Based Controller

eess.SY ·2026-11-13 ·Arash Omidi, Tanmay Mishra, Mads R. Almassalkhi
benchmark similarity 0.69
Abstract

This paper presents a constraint-aware reinforcement learning (CARL) controller for battery energy storage system (BESS) sizing and photovoltaic (PV) ramp-rate smoothing. Rapid PV power fluctuations caused by cloud transitions can introduce operational and stability challenges in power systems. To mitigate these impacts, grid codes impose ramp-rate limits (RRL) on PV power injected to the grid. BESSs can support such grid codes by absorbing or supplying power during rapid variations. However, the extent to which BESSs can reduce PV-induced variability depends on (i) the BESS power and energy capacities; and (ii) the adopted controller. Thus, BESS sizing and controller design are coupled. Conventional moving-average control can increase battery usage due to filter-induced lag, while ramp-rate control is reactive and does not account for the long-term impact of actions on battery state of charge and future ramp events. Optimization-based methods can reduce BESS requirements by anticipating future PV variations, but their performance depends on accurate PV forecasts. To address these limitations, the CARL controller learns a causal state-feedback policy from historical PV data without requiring forecasts during deployment. Ramp-rate, converter-power, and state-of-charge constraints are incorporated into a causal feasibility interval that guarantees feasible actions by definition. A full-horizon input-convex neural network (ICNN)-based optimization is developed as a noncausal benchmark for the minimum achievable BESS requirements. Evaluation using three real-world PV datasets shows that, at a 10\%/min ramp-rate limit, CARL reduces peak BESS power by 8.7--10.4\% and energy capacity by 47.5--62.6\% relative to conventional ramp-rate control while maintaining the grid-codes compliance.

0.20

Hierarchical Control via MPC-RL for Multi-Timescale Battery Systems

eess.SY ·2026-10-02 ·Rasa Pourjam, Ehecatl Antonio del Río Chanona, Paulina Quintanilla
similarity 0.69
Abstract

Multi-timescale systems present a fundamental challenge, where fast operational decisions must coexist with long-horizon sustainability targets. In this work, we propose a new hierarchical control framework via Model Predictive Control (MPC) and Reinforcement Learning (RL) to separate decision-making on two distinct timescales. The high-level MPC optimizes long-horizon setpoints at the slow dynamic and on a fast timescale, a low-level pretrained RL agent tracks these setpoints in real time to maximize short-term objectives. RL is introduced to learn nonlinear control policies, without relying on model linearizations or requiring the heavy online computation from solving repeated optimal control problems. The framework is applied to a Battery Energy Storage System (BESS) operating in frequency regulation markets to balance fast profit opportunities (seconds) and slow battery degradation (weeks to months). The design employs a degradation-aware RL agent trained offline to generate safe long-horizon setpoints, and a degradation-unaware agent fine-tuned from it for fast runtime setpoint tracking. Compared to MPC baselines, the proposed approach successfully extends battery lifetime by 84% and increases operational profit by 34%.

0.17

Robust Scenario-Based Data-Enabled Predictive Control of a Battery Energy Storage System: An Experimental Study

eess.SY math.OC ·2026-10-06 ·Sebastian Zieglmeier, Nikolas Recke, Mathias Hudoba de Badyn
similarity 0.69
Abstract · 8 pages, 5 figures

Battery energy storage systems must respect strict state-of-charge (SOC) limits to prevent overcharge and deep discharge, a task complicated by measurement noise and costly-to-model nonlinear dynamics. Data-enabled predictive control (DeePC) resolves the costly modeling issue by predicting future behavior directly from data. However, its regularization robustifies only the prediction and not the constraints. Scenario-based DeePC (Scenario-DeePC) extends DeePC with the scenario approach, building constraint robustness fully data-driven from observed prediction errors rather than an assumed disturbance distribution. This paper presents the first real-world deployment of Scenario-DeePC, on a grid-connected battery system at the NEST research facility, whose SOC estimate exhibits abrupt, irregular recalibration jumps in addition to ordinary noise. Compared to standard DeePC, Scenario-DeePC achieves comparable tracking performance with substantially fewer constraint violations. Its adaptive scenario buffer further tightens constraint handling automatically, improving robustness to unpredictable recalibration events.

0.17