Integrated Thermal and Power Management for Wave-Powered Subsea Data Centers via Nonlinear Model Predictive Control

Wanqun Yang, Jun Chen

eess.SY ·submitted 2026-09-28 01:45 UTC · v1

Abstract

This paper develops an integrated modeling and nonlinear model predictive control (NMPC) framework for coordinating thermal management, flexible workload scheduling, wave-power utilization, and battery operation in a wave-powered subsea data center. Realistic data center workloads are constructed from job-level CPU, memory, and GPU measurements from the MIT Supercloud dataset and divided into interactive and delay-tolerant flexible jobs. Thermal behavior is represented by a three-node lumped model of the IT equipment, recirculating nitrogen, and pressure hull with surrounding seawater as the thermal boundary. The NMPC jointly optimizes the flexible workload power budget and cooling command subject to thermal, battery, and workload constraints. Closed-loop simulations under different workload, thermal, battery, and renewable-generation conditions demonstrate that the proposed framework maintains thermal safety while adapting cooling operation and flexible workload execution to wave-power availability and battery state-of-charge. The parametric studies show that battery capacity and wave-generation capacity strongly affect battery availability and flexible-workload queue accumulation, while excessive renewable generation capacity may lead to increased energy curtailment. Monte Carlo and distance-correlation analyses further show that flexible-job delay is relatively insensitive to the investigated system parameters, whereas terminal battery state-of-charge is primarily influenced by battery energy capacity and wave generation capacity.

Comment
14 figures and 11 tables

Closest papers

Nearest neighbours by meaning across the whole index.

Real-Time Control of Sustainable Data Centers: A Two-Layer Model Predictive Control Framework with Workload Flexibility and Heat Recovery

eess.SY ·2026-08-17 ·Wenyu Liu, Enea Figini, Mario Paolone
similarity 0.66
Abstract · 22 pages, 14 figures

This paper proposes a two-layer model predictive control (MPC) framework for the real-time operation of data centers integrated with on-site photovoltaic generation, battery energy storage, waste heat recovery, and district heating. The upper layer employs scenario-based stochastic optimization to jointly optimize intraday market participation, workload scheduling, and energy management under uncertainty. The lower layer adopts an adaptive tube-based MPC strategy that compensates short-term disturbances while tracking the dispatch references given by the upper layer. The framework further integrates multi-horizon forecasting to support real-time decision making. Microservice-based simulation studies under representative clear-sky and overcast operating conditions demonstrate that the proposed framework accurately tracks dispatch plans despite fast photovoltaic and workload fluctuations. Compared with single-layer control strategies, the adaptive lower-layer controller substantially reduces real-time dispatch deviations and the associated imbalance costs. In addition, the proposed framework naturally adapts to seasonal operating conditions and responds to carbon-aware operating signals, offering a practical approach for economically efficient, sustainable, and grid-supportive operation of future data centers.

0.29

Data center cooling choices shift water impacts across the grid: An integrated water-energy model for sustainable data center development

eess.SY cs.CYcs.DC ·2026-09-21 ·Garrett Alston, Nancy Love, Rabab Haider
code/data similarity 0.65
Abstract · 12 pages; 8 figures; 6 tables; appendix

Data centers are being developed at an unprecedented pace, yet their energy and water impacts, and the spatial and temporal distribution of these impacts, remain poorly characterized. Data centers consume water for cooling (direct) and through electricity generation (indirect). Decisions on siting and cooling technology result in water-energy trade-offs that extend impacts beyond the facility's location. Existing assessment frameworks rely on facility efficiency metrics and average grid water intensity factors, suppressing the temporal impacts of data center load and generation availability. They also attribute indirect consumption to the facility's location rather than to the generators (and corresponding hydrologic regions) that respond to the added load, misattributing spatial impacts. To close this gap, we develop a computational model of the data center-energy-water nexus that links facility cooling and electricity demand with hourly economic dispatch, generator-level water consumption, and monthly subbasin depletion. Built on open-source data, the model resolves where and when water is consumed, and where this consumption compounds existing water risk or creates new risk. Using the model, we study different cooling configurations and proposed developments in the state of Michigan. Air-cooled data centers halve total water consumption relative to evaporative cooling, but increase electricity demand and raise indirect water consumption by one-third, shifting the water footprint from the facility to generators. Mapping these changes to subbasins reveals depletion increases beyond the data center sites, in regions that facility-level reporting may overlook. These results show that data center water and energy impacts cannot be assessed in isolation, motivating the need for integrated modeling to inform siting, design, and reporting practices.

0.22

Grid-Mode-Aware AI Data Center Power Smoothing via Bayesian-Optimized Hybrid Energy Storage System

eess.SY ·2026-11-02 ·Sina Mohammadi, Quang Manh Hoang, Marcus Chen I Wada, Van-Hai Bui, Wencong Su
similarity 0.65
Abstract · 6 pages, 5 figures, Submitted, 2027 IEEE Texas Power and Energy Conference (TPEC)

AI data centers exhibit highly stochastic, volatile power demands from intensive workloads and synchronized GPU training cycles, which can excite grid natural frequencies and threaten system stability. This paper proposes a real-time, forecasting-independent control framework utilizing a Hybrid Energy Storage System (HESS) that coordinates a Battery Energy Storage System (BESS) and a supercapacitor (SC). Employing a parameterized frequency-decoupling and active modal-damping policy, the framework mitigates critical oscillatory load components while smoothing overall power fluctuations. To bypass the heavy computational burden of online receding-horizon optimization, this work introduces an offline Bayesian Optimization (BO) approach to optimally tune real-time control parameters, minimizing a multi-objective cost function that balances grid compliance penalties and storage degradation. Numerical simulations demonstrate that the proposed method ensures grid stability and strong target envelope adherence. Specifically, it reshapes extreme 75-160 MW raw demand fluctuations to largely fit within a tight 10 MW target band, with only brief transient excursions, while attenuating the critical 20 MW oscillatory component below 1 MW to suppress resonant excitation.

0.20

AI-driven Thermal-aware Data Center Capacity Planning

cs.LG ·2026-10-01 ·Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai +1 more
published similarity 0.64
Abstract · Presented at DesignCon 2026

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

0.13

Supporting Data Center Grid Integration via Co-Optimized Battery Energy Storage Sizing and Capacity Allocation

eess.SY math.OC ·2026-11-06 ·Wei Wang, Himanshu Sharma, Thiagarajan Ramachandran
similarity 0.64
Abstract

Interconnecting large data centers can be delayed by grid requirements on demand flexibility, ramping limits, and ride-through performance. This paper proposes an optimization-based framework to size a Battery Energy Storage System (BESS) that accelerates data center grid integration by providing BESS capacity required to meet selected flexibility and grid-support requirements. The model co-optimizes BESS power rating and energy capacity while allocating capability across three services: (i) demand response over a specified duration, (ii) mitigation of high-magnitude, high-frequency load fluctuations through reserved active power with zero net state-of-charge change, and (iii) voltage support via reactive power capability at the point of common coupling. Minute-level operational scheduling enforces state-of-charge feasibility and load ramp constraints, and incorporates a controllable queue of delay-insensitive computing tasks to enhance flexibility. A case study using a real data center load profile demonstrates the proposed method and quantifies the BESS power-energy requirements and operational trade-offs needed to satisfy the multi-service constraints, providing practical guidance for interconnection planning and deployment.

0.05

Grid-Mode-Aware Model Predictive Control of Hybrid Energy Storage Systems for AI Data Center Power Smoothing

eess.SY ·2026-09-03 ·Xin Chen
similarity 0.63
Abstract

To facilitate the grid-friendly integration of highly variable AI data center loads, this paper proposes a grid-mode-aware model predictive control (G-MPC) framework for managing a hybrid energy storage system (HESS) to smooth grid-side power demand. The framework optimally coordinates a battery energy storage system (BESS) and a supercapacitor (SC) by solving a multi-step optimization problem in a receding-horizon manner. In particular, band-pass filter dynamics are directly embedded in the G-MPC formulation to extract and suppress grid-side power components associated with vulnerable grid oscillatory modes, thus mitigating load-induced grid oscillations. The resulting G-MPC optimization jointly minimizes violations of grid-side power-envelope, ramp-rate, and modal-power requirements and the degradation and power-ramping costs of the BESS and SC, while satisfying power limits, state-of-charge limits, and other operational constraints. To enable real-time implementation, a fix-and-re-optimize algorithm is developed to solve each G-MPC problem efficiently while preventing simultaneous charging and discharging. Extensive simulations demonstrate the effectiveness, flexibility, and computational efficiency of the proposed framework. The results also highlight the importance of explicitly suppressing power components associated with vulnerable grid modes, rather than merely reducing overall load variations, to effectively mitigate grid oscillations.

0.40

LLM-Powered Predictive Decision-Making for Sustainable Data Center Operations

cs.LG ·2026-08-19 ·Hanzhao Wang, Jingxuan Wu, Yumeng Li, Yu Pan, Guanting Chen
similarity 0.62
Abstract

The growing demand for AI-driven workloads, particularly from Large Language Models (LLMs), has raised concerns about the significant energy and resource consumption in data centers. This work introduces a novel LLM-based predictive scheduling system designed to enhance operational efficiency while reducing the environmental impact of data centers. Our system utilizes an LLM to predict key metrics such as execution time and energy consumption from source code, and it has the potential to extend to other sustainability-focused metrics like water usage for cooling and carbon emissions, provided the data center can track such data. The predictive model is followed by a real-time scheduling algorithm that allocates GPU resources, aiming to improve sustainability by optimizing both energy consumption and queuing delays. With fast inference times, the ability to generalize across diverse task types, and minimal data requirements for training, our approach offers a practical solution for data center scheduling. This framework demonstrates strong potential for advancing sustainability objectives in AI-driven infrastructure. Through our collaboration with a data center, we achieved a 32% reduction in energy consumption and a 30% decrease in waiting time.

0.08

Grid Demand Flexibility Assessment of AI Data Centers via Batch Workload Temporal Shifting

eess.SY ·2026-09-29 ·Suntao Su, Liang Du, Shengyi Wang
similarity 0.62
Abstract · 5 pages, 5 figures, conference

The rapid growth of artificial intelligence (AI) data centers has introduced new challenges to power system operation. As their power demand becomes larger and more variable, quantitatively characterizing their demand flexibility is increasingly important for effective power system coordination. However, heterogeneous workload characteristics and resource requirements make this flexibility difficult to characterize directly. This paper proposes a framework for assessing the grid-compatible demand flexibility of AI data centers via batch workload temporal shifting. An averaging-based resource usage processing method is developed to map fine-resolution CPU, GPU and memory usage into unified time intervals compatible with power system operation. A workload temporal scheduling model is then formulated to shift batch workloads while preserving execution continuity, delay constraints, and server resource capacities, and is coupled with a utilization-dependent server power model to translate workload scheduling decisions into server power demand. Two complementary flexibility metrics are evaluated: short-term peak demand shaving and the maximum duration of sustained power reduction. Numerical results based on real GPU cluster traces demonstrate that workload temporal shifting can provide quantifiable and grid-compatible demand flexibility for AI data centers with limited disruption to computing workloads.

0.13