AI-driven Thermal-aware Data Center Capacity Planning

Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai, Zhiyu Zeng

cs.LG ·submitted 2026-10-01 20:09 UTC · v1
published

Abstract

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

Comment
Presented at DesignCon 2026

Closest papers

Nearest neighbours by meaning across the whole index.

ETCInfer: An Energy-efficient Thermal-aware Cooling-joint Scheduler for LLM Inference in AI Datacenters

cs.DC cs.PFeess.SY ·2026-09-14 ·Rui Lu, Rui Ge, Huanghuang Liang, Xiaobo Zhou, Dan Wang
similarity 0.78
Abstract · 16 pages

Large language model (LLM) inference in AI datacenters creates a coupled control problem between GPU serving and facility cooling. Raising ambient temperature setpoints can reduce cooling energy and carbon, but also shrinks thermal headroom, induces GPU throttling, and leads to Service-Level-Objective (SLO) violations. In this paper, we study joint cooling--computing control for LLM inference: minimizing per-job GPU-plus-cooling energy while satisfying thermal safety and latency SLO constraints. We present ETCInfer, an energy-efficient, thermal-aware scheduler that selects a pre-job Computer Room Air Conditioner (CRAC) setpoint and adapts per-GPU frequency and micro-batch size during execution. ETCInfer builds compact physics-informed control models by calibrating GPU heat generation, chassis heat dissipation, CRAC power, and prefill/decode latency relations from telemetry. These models estimate hidden thermal states and time-to-throttle, enabling the scheduler to evaluate energy, temperature, and latency before applying an action. We formulate this joint setpoint--frequency--micro-batch control problem as a partially observable Markov decision process and design ETCAdapter, a learning-based controller that minimizes per-job energy under thermal safety and SLO constraints. We implement ETCInfer as a coordination layer over typical inference and cluster management stacks. Evaluation across real-trace simulation and validation experiments shows that ETCInfer reduces total job energy by up to 33.1%, thermal throttle exposure by up to 92.9%, and keeps SLO violation rates below 0.7% even at ambient temperatures up to $48^{\circ}\mathrm{C}$.

0.17

LLM-Powered Predictive Decision-Making for Sustainable Data Center Operations

cs.LG ·2026-08-19 ·Hanzhao Wang, Jingxuan Wu, Yumeng Li, Yu Pan, Guanting Chen
similarity 0.76
Abstract

The growing demand for AI-driven workloads, particularly from Large Language Models (LLMs), has raised concerns about the significant energy and resource consumption in data centers. This work introduces a novel LLM-based predictive scheduling system designed to enhance operational efficiency while reducing the environmental impact of data centers. Our system utilizes an LLM to predict key metrics such as execution time and energy consumption from source code, and it has the potential to extend to other sustainability-focused metrics like water usage for cooling and carbon emissions, provided the data center can track such data. The predictive model is followed by a real-time scheduling algorithm that allocates GPU resources, aiming to improve sustainability by optimizing both energy consumption and queuing delays. With fast inference times, the ability to generalize across diverse task types, and minimal data requirements for training, our approach offers a practical solution for data center scheduling. This framework demonstrates strong potential for advancing sustainability objectives in AI-driven infrastructure. Through our collaboration with a data center, we achieved a 32% reduction in energy consumption and a 30% decrease in waiting time.

0.08

Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers

cs.DC cs.PFeess.SY ·2026-09-25 ·Krishna Chaitanya Sunkara
similarity 0.73
Abstract · 6 pages, 5 figures, IEEE conference paper, first submitted to IEEE ICCSP 2026 02/02/2026

GPU-dense AI data centers need to run on liquid cooling as air simply cannot shed the heat at these power densities. Yet the cooling loops themselves are blind to what workloads are about to run; they crank up flow only after a sensor catches a temperature climb, which can take 30 to 50 seconds. We built Job-Class Thermal Intent (JCTI) to close that window. The scheduler already knows a job is coming and what class it belongs to; JCTI feeds that information straight to the cooling controller so it can stage coolant before the heat shows up. We pulled the thermal signatures for each job class out of MLPerf GPU power traces and tuned arrival patterns against Alibaba cluster data. Over 120 paired Monte Carlo trials the numbers come out to 56.4% fewer thermal violations and 60.2% less cumulative overshoot than a straight PI loop. As AI data centers evolving towards gigawatt grid loads with highly fluctuating power swings, thermally-aware scheduling reduces sudden demand and improves load prediction in grid side. Cooling and scheduling have been running as two separate systems for years despite each one knowing something the other needs, JCTI wires them together.

0.22

HeatCache: Thermal-aware Energy-efficient LLM Inference Scheduling for Chassis-level Liquid Cooling in Sustainable Edge Server Rooms

cs.DC cs.PFeess.SY ·2026-09-11 ·Rui Lu, Huanghuang Liang, Kaiqi Guan, Dan Wang
similarity 0.71
Abstract

LLM inference is increasingly deployed at institution-scale edges to meet service requirements. However, multi-GPU inference consumes a large amount of electricity and produces substantial heat. To improve sustainability, operators and regulations often demand raising the ambient setpoint to reduce cooling electricity. This can increase thermal throttling and hardware aging, leading to Service-Level Objective violations. In this paper, we present HeatCache, a thermal-aware, energy-efficient LLM inference scheduler for commercial chassis-level AIO liquid-cooled GPUs at sustainable ambient temperatures. HeatCache treats AIO loops as a temporary heat buffer, measured by heat budget and schedules requests to minimize energy subject to thermal safety and SLO constraints, based on an electrical-informed heat-demand estimation from HeatiTS. We implement HeatCache atop vLLM and show that it reduces computing energy by up to 18.0%, decreases thermal-throttle exposure by 81.7%, and maintains SLO violation rates below 0.9% even up to $48~^{\circ}\mathrm{C}$.

0.11

ThermE: Predictive Management of Shared Thermal Headroom for Sustained LLM Inference on Thermally Constrained Edge SoCs

eess.SY ·2026-09-24 ·Rui Lu, Yuheng Wang, Bozheng Liu
similarity 0.68
Abstract · 13 pages, 16 figures

Compact edge system-on-chip (SoC) platforms increasingly run sustained LLM inference under thermal constraints, while their CPU, GPU, and RAM share a cooling path. Prefill and decode therefore consume shared, time-varying thermal headroom, yet vendor governors react only near hardware throttling thresholds without knowledge of request state or upcoming work. A control decision that improves current performance can thus consume headroom too quickly and degrade subsequent service. In this paper, we present ThermE, a runtime system that predicts and jointly manages shared thermal headroom for sustained LLM inference on edge SoCs. Its Fast LLM-to-Heat Compiler maps the model, requests, runtime state, and candidate actions to domain heats without executing LLMs. A partial differential equation (PDE)-constrained Headroom Predictor uses ThermPINN for offline thermal identification and a Reduced Headroom Predictor (RHP) for low-overhead online uncertainty-calibrated headroom forecasts. An Uncertainty-Aware Action Scheduler then selects actions that balance serving quality and future headroom. We implement ThermE atop vLLM and evaluate it across four LLM inference workloads. The results show that ThermE reduces TTFT and TPOT by 40.55% and 12.17%, respectively, relative to vLLM. It achieves a 5.70% SLO violation rate, compared with 12.30% for the strongest baseline, while its predictor obtains a 1.94 $^\circ$C MAE with 11.50 ms overhead.

0.09

Modeling Liquid-Cooled Data Centers in EnergyPlus

eess.SY cs.CEcs.DCcs.LG ·2026-10-23 ·Yun-Dam Ko, Dipashreya A. Sur, Cade Napier, Carlos D. Díaz-Marín, Rishee K. Jain
code/data similarity 0.68
Abstract · 14 pages, 7 figures, 6 tables. Code: https://github.com/Urban-Informatics-Lab/energyplus-liquid-cooling

As AI workloads accelerate data center transition toward high-density racks with direct-to-chip (DTC) liquid cooling, existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap, we develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled, that models DTC liquid cooling for chilled-water and warm-water architectures as plant-loop components. It couples facility-water loops, rack-side secondary loops, coolant distribution units, and chip-junction temperatures within a single solver. Validation against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution, yields loop-temperature RMSE at or below 0.021 K, well within the 0.1 K acceptance threshold. Our case study demonstrates that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use, and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic into EnergyPlus, our work provides whole-building, long-term energy modeling for high-density AI infrastructure within an open-source framework.

0.31

Creating Power Flexibility in Datacenters via Query Routing

cs.AI ·2026-11-03 ·Shivam Patel, Bingqing Chen, Jared Fernandez, Guannan Qu, Gauri Joshi
similarity 0.67
Abstract

The growing energy requirements of large language model inference highlight the need for datacenters to support safe grid operation by providing power demand flexibility, while maintaining service for interactive workloads. This work investigates query routing as a mechanism to enable such capability by dynamically allocating queries across different language model instances without deferring requests. We develop a general analytical framework that connects query arrival rates and sequence length distributions to token iteration time, request residence time, serving capacity, and power consumption of model instances. Leveraging this framework, we characterize the feasible query routing allocations and the corresponding power demand flexibilities, enabling the selection of routing strategies to achieve desired power consumption behavior. We validate our framework across four GPU platforms on language models ranging from 1B to 70B parameters, obtaining 2.8% mean absolute percentage error in estimating achievable power flexibility. We evaluate our approach on a real trace-driven simulation of a 10,000 H100 GPUs datacenter, exhibiting flexibility up to 16% of total power consumption, with 90% of the desired power reduction achieved within approximately 10 seconds. These results establish query routing as an effective mechanism for datacenter power demand flexibility and demonstrate the broader applicability of our proposed framework to datacenter level planning and orchestration.

0.12

Large Language Models for AI Infrastructure

cs.AI cs.CL ·2026-11-14 ·Bolin Shen, Shaoyi Huang, Yushun Dong
survey similarity 0.65
Abstract

Large language models (LLMs) are increasingly used to design, optimize, and operate the infrastructure behind AI training and serving, yet the literature remains fragmented across hardware design, machine learning systems, electronic design automation, and high-performance computing. We present a comprehensive survey of LLM-assisted AI infrastructure across its lifecycle, from accelerator design and kernel engineering to compilation, deployment, operations, data management, and energy optimization. We organize the literature by the primary resource the LLM manages: artifact-centric methods for computational artifacts, operational-centric methods for deployment context and system state, and resource-centric methods for data and energy. These categories span the lifecycle and cover AI-specific concerns such as distributed-training configuration, inference serving, GPU-cluster scheduling, and data loading. Building on this taxonomy, we conduct a cross-study quantitative synthesis of reported results. Because studies adopt heterogeneous benchmarks, baselines, hardware, and metrics, we compare methods only where evaluation conditions permit and align results along common dimensions: functional correctness, execution performance, throughput, resource and energy consumption, operational outcomes, and optimization cost, keeping each result's native metric, baseline, and setting rather than collapsing them into a single score. This comparison reveals where LLM-driven methods yield consistent gains, how reported gains in workload orchestration depend on the evaluation environment, from simulators to real clusters and production, and where evidence is still lacking. Together, the taxonomy, lifecycle perspective, and quantitative evaluation provide an evidence-grounded reference for LLM-driven engineering of AI infrastructure.

0.19