Creating Power Flexibility in Datacenters via Query Routing

Shivam Patel, Bingqing Chen, Jared Fernandez, Guannan Qu, Gauri Joshi

cs.AI ·submitted 2026-11-03 16:22 UTC · v1

Abstract

The growing energy requirements of large language model inference highlight the need for datacenters to support safe grid operation by providing power demand flexibility, while maintaining service for interactive workloads. This work investigates query routing as a mechanism to enable such capability by dynamically allocating queries across different language model instances without deferring requests. We develop a general analytical framework that connects query arrival rates and sequence length distributions to token iteration time, request residence time, serving capacity, and power consumption of model instances. Leveraging this framework, we characterize the feasible query routing allocations and the corresponding power demand flexibilities, enabling the selection of routing strategies to achieve desired power consumption behavior. We validate our framework across four GPU platforms on language models ranging from 1B to 70B parameters, obtaining 2.8% mean absolute percentage error in estimating achievable power flexibility. We evaluate our approach on a real trace-driven simulation of a 10,000 H100 GPUs datacenter, exhibiting flexibility up to 16% of total power consumption, with 90% of the desired power reduction achieved within approximately 10 seconds. These results establish query routing as an effective mechanism for datacenter power demand flexibility and demonstrate the broader applicability of our proposed framework to datacenter level planning and orchestration.

Closest papers

Nearest neighbours by meaning across the whole index.

Grid Demand Flexibility Assessment of AI Data Centers via Batch Workload Temporal Shifting

eess.SY ·2026-09-29 ·Suntao Su, Liang Du, Shengyi Wang
similarity 0.71
Abstract · 5 pages, 5 figures, conference

The rapid growth of artificial intelligence (AI) data centers has introduced new challenges to power system operation. As their power demand becomes larger and more variable, quantitatively characterizing their demand flexibility is increasingly important for effective power system coordination. However, heterogeneous workload characteristics and resource requirements make this flexibility difficult to characterize directly. This paper proposes a framework for assessing the grid-compatible demand flexibility of AI data centers via batch workload temporal shifting. An averaging-based resource usage processing method is developed to map fine-resolution CPU, GPU and memory usage into unified time intervals compatible with power system operation. A workload temporal scheduling model is then formulated to shift batch workloads while preserving execution continuity, delay constraints, and server resource capacities, and is coupled with a utilization-dependent server power model to translate workload scheduling decisions into server power demand. Two complementary flexibility metrics are evaluated: short-term peak demand shaving and the maximum duration of sustained power reduction. Numerical results based on real GPU cluster traces demonstrate that workload temporal shifting can provide quantifiable and grid-compatible demand flexibility for AI data centers with limited disruption to computing workloads.

0.13

Scaling Shapley Energy Attribution to Large LLM Batches

cs.DC cs.ARcs.PF ·2026-11-10 ·Qi Luo, Ziwen Wang, Kunlin Li, Changxi Liu, Yun Chen
similarity 0.70
Abstract · 13 pages, 11 figures

LLM services have become essential infrastructure for applications such as chat assistants and coding agents. Service providers need to attribute resource consumption to individual requests for purposes such as billing. Among these resources, energy is a key metric for assessing the cost of serving each request. However, serving engines batch requests together, and GPUs report only aggregate energy consumption. Providers typically estimate each request's share in proportion to its token consumption, but this approach can produce substantially unfair estimates. The Shapley value provides a principled solution to fair energy allocation, but computing it directly requires $2^N-1$ GPU runs for $N$ requests, which is infeasible for large batches. To address this problem, we propose StepSplit. Across GPU generations, we observe that the energy consumed by each inference step, a forward pass over a batch, consists of a shared energy, largely due to reading model weights, and a request-specific energy. We derive a closed-form Shapley value: each request is charged its own energy plus an equal part of the shared energy of every step in which it participates. A microbenchmark of 2.5-17.8 minutes calibrates both parts of the step energy once per model and GPU configuration. Under static batching, StepSplit uses this closed form in a single pass over the scheduler log. Under continuous batching, removing a request can change how the remaining requests are batched, so StepSplit adds a correction to the closed form, computed by replaying the scheduler on a CPU. We evaluate StepSplit against Shapley values measured using 529,513 GPU runs. Under static batching with batch sizes of 8-256, StepSplit achieves an $L_1$ error of 0.4-4.3%, compared with 13.4-61.3% for token-proportional allocation. Under continuous batching with 8-128 requests, the corresponding errors are 0.5-6.4% and 20.6-71.7%.

0.24

Slasher: Power Flexibility for Cloud Datacenters

cs.DC cs.OSeess.SY ·2026-08-26 ·Liuzixuan Lin, Fiodar Kazhamiaka, Alok Gautam Kumbhare, Chaojie Zhang, Jaylen Wang +8 more
similarity 0.68
Abstract · 18 pages, 15 figures

Datacenters consume many megawatts of power, and regularly encounter scenarios that require modulating their power draw. These scenarios include datacenter infrastructure failures, power grid failures, grid services, and more, spanning a diverse range of requirements in terms of the power magnitude, the scope of the reduction, the notice time, and other dimensions. To address these scenarios, we have built Slasher, a general system for modulating the power of \azure datacenters to handle scenarios ranging from individual racks to regional multi-datacenter grid events. Slasher coordinates datacenter resources with the goal of meeting power targets while minimizing negative impact on hosted workloads. In this paper, we review the main power modulation scenarios, characterize the power reduction levers using data from production cloud datacenters, describe Slasher's system architecture, and formulate the cloud datacenter power modulation control problem. We also develop a high-fidelity datacenter simulator and propose a workload impact model, using them to design and evaluate power control algorithms.

0.31

AI-driven Thermal-aware Data Center Capacity Planning

cs.LG ·2026-10-01 ·Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai +1 more
published similarity 0.67
Abstract · Presented at DesignCon 2026

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

0.13

eFAIR: Fair LLM Serving under Hourly Electricity Commitments

cs.DC ·2026-11-18 ·You Peng, Youhe Jiang, Chen Wang, Binhang Yuan
hot direction similarity 0.67
Abstract

Datacenters can procure electricity in day-ahead markets by committing to energy purchases for individual hours. For LLM services operating within these hourly budgets, maximizing aggregate throughput alone may still leave individual requests waiting or receiving much slower service than desired. Fair serving therefore requires improving service for poorly served requests while reserving electricity for later arrivals whose timing and demand are unknown. To compare service across requests, we define normalized throughput as each request's actual output rate divided by the product of its standalone throughput and its service entitlement, a positive weight representing its desired service level. Using this measure, we formulate fair serving as leximin optimization under an hourly electricity constraint, prioritizing requests with the lowest normalized throughput. To address this problem, we present eFAIR, an online scheduler that coordinates request dispatching, electricity budget allocation, and GPU frequency selection through a common normalized-throughput target. Specifically, request dispatching prioritizes requests by desired service level and progress; electricity budget allocation reserves electricity for current and expected future work; and frequency selection uses electricity savings to raise GPU frequencies for requests with higher desired service levels. Evaluations on H20 and H200 configurations, each with 32 replicas, show that eFAIR improves the tenth percentile of normalized throughput by 28.0%-31.0% over the best budget-feasible baseline, while keeping absolute deviations from the hourly electricity commitment below 0.26%. eFAIR also improves throughput balance among concurrent requests and aligns electricity allocation more closely with service demand over time. Together, these results demonstrate how eFAIR improves request-level fairness within an hourly commitment.

0.22

LLM-PowerTrace: A Dataset of Time-Resolved GPU Power Traces for AI Compute

eess.SY cs.AIcs.OS ·2026-10-28 ·Jiansheng Wang, Jaskeerat Singh, Haochen Xu, Xinyi Li, Mingyuan Yan +4 more
datasetcode/data similarity 0.67
Abstract · In Submission; Code and dataset are available at https://systems-power-review.github.io/training-power-trace-explorer/

AI compute is becoming large and fast-changing electrical loads. Its impacts on data center infrastructure and power grids depend not only on total energy consumption, but also on how their power draw moves over sub-second to minute timescales, including peaks, ramps, and synchronized fluctuations across accelerators. Existing energy benchmarks for large language models (LLMs) report aggregate quantities such as joules per token and rarely release the underlying time-series measurements, leaving these power dynamics poorly characterized and difficult to model. We introduce LLM-PowerTrace, an open dataset of time-resolved, per-GPU power traces for LLM fine-tuning and inference, sampled every 100\,ms on varying NVIDIA platforms paired with complete workload and system metadata. For fine-tuning, LLM-PowerTrace profiles open model families spanning a wide range of model sizes and fine-tuning methods, together with controlled sweeps over batch size, sequence length, precision, parallelism, and checkpointing. For inference, it covers variations in concurrency, GPU frequency, KV-cache and weight quantization, prompt and output lengths, and request-arrival patterns. LLM-PowerTrace profiles a set of open model families across a wide range of model sizes, and controlled sweeps over batch size, sequence length, precision, parallelism, and checkpointing for fine-tuning, and it sweeps concurrency, GPU frequency, KV cache and weight quantization, prompt and output lengths, and request arrival patterns for inference. Built upon power traces, we define power-grid-facing metrics as well as AI-compute power\&energy scaling law for extrapolating beyond the measured settings. Together, LLM-PowerTrace provides a dataset foundation for modeling, forecasting, and managing the fast-changing electrical behavior of AI compute.

0.37

OpScale: Operator-level Provisioning and Autoscaling for LLM Serving

cs.DC ·2026-08-13 ·Xingqi Cui, Chieh-Jan Mike Liang, Ziang Tang, Jiarong Xing, Haoran Qiu
similarity 0.67
Abstract · 22 pages, 29 figures

Achieving cost efficiency while meeting strict user-facing SLOs (e.g., time-to-first-token) remains a fundamental challenge for cloud GPU clusters serving large language models (LLMs). Autoscaling is the key mechanism for cluster resource management, yet a basic system design question is open for serving LLMs: what should be the unit of scaling? Existing approaches primarily treat the entire model as a monolithic scaling unit--simple but unable to capture the fine-grained dynamics of inference workloads. As a result, such coarse-grained scaling often leads to either SLO violations under bursty demand or significant GPU under-utilization. Our characterization reveals substantial operator heterogeneity, exposing operator-level elasticity as a viable scaling primitive. We present OpScale, a practical operator-level orchestration framework of profiling, provisioning, placement, and runtime serving. OpScale is designed to tackle the high complexity and the space explosion problem, arising from operating at this finer granularity. Evaluated with production traces on up to 40 A100s and 24 GB200s, OpScale attains SLOs with up to 36.3% fewer GPUs and 28% less power, or achieves 44% higher throughput under fixed cost budgets.

0.10

AI Inference-Aware Optimal Power Flow: Converting Token Requirements into Grid Flexibility

eess.SY ·2026-11-14 ·Qianyi Ma, Dawei Qiu, Xiao Liu
similarity 0.67
Abstract

The rapid growth, temporal variability, and geographic concentration of electricity demand from artificial intelligence (AI) inference can aggravate transmission congestion near data centers (DCs). The spatial and temporal flexibility of inference workloads offers an opportunity to alleviate this congestion: requests can be routed across DCs or deferred within users' quality-of-service (QoS) requirements. However, inference routing primarily considers graphics processing unit (GPU) availability, leaving this flexibility underused in grid operation. Using GPU measurements, this paper models inference latency and DC power consumption to quantify the flexibility available under users' time-to-first-token (TTFT) and inter-token latency (ITL) requirements. These models are then incorporated into an AI inference-aware optimal power flow (OPF) that coordinates inference routing and power system operation among DC operators, the transmission system operator, and inference users. By linking user requests, token generation at DCs, and electricity delivery through the transmission network, the formulation schedules inference workloads subject to both users' QoS requirements and transmission constraints. Simulations on the PJM system show that, compared with computing-based routing and with electricity price-based routing, coordinating inference routing with network operation enables growing DC electricity demand deliverable to be met at lower cost.

0.20