Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers

Krishna Chaitanya Sunkara

cs.DC cs.PFeess.SY ·submitted 2026-09-25 04:06 UTC · v1

Abstract

GPU-dense AI data centers need to run on liquid cooling as air simply cannot shed the heat at these power densities. Yet the cooling loops themselves are blind to what workloads are about to run; they crank up flow only after a sensor catches a temperature climb, which can take 30 to 50 seconds. We built Job-Class Thermal Intent (JCTI) to close that window. The scheduler already knows a job is coming and what class it belongs to; JCTI feeds that information straight to the cooling controller so it can stage coolant before the heat shows up. We pulled the thermal signatures for each job class out of MLPerf GPU power traces and tuned arrival patterns against Alibaba cluster data. Over 120 paired Monte Carlo trials the numbers come out to 56.4% fewer thermal violations and 60.2% less cumulative overshoot than a straight PI loop. As AI data centers evolving towards gigawatt grid loads with highly fluctuating power swings, thermally-aware scheduling reduces sudden demand and improves load prediction in grid side. Cooling and scheduling have been running as two separate systems for years despite each one knowing something the other needs, JCTI wires them together.

Comment
6 pages, 5 figures, IEEE conference paper, first submitted to IEEE ICCSP 2026 02/02/2026

Closest papers

Nearest neighbours by meaning across the whole index.

ETCInfer: An Energy-efficient Thermal-aware Cooling-joint Scheduler for LLM Inference in AI Datacenters

cs.DC cs.PFeess.SY ·2026-09-14 ·Rui Lu, Rui Ge, Huanghuang Liang, Xiaobo Zhou, Dan Wang
similarity 0.78
Abstract · 16 pages

Large language model (LLM) inference in AI datacenters creates a coupled control problem between GPU serving and facility cooling. Raising ambient temperature setpoints can reduce cooling energy and carbon, but also shrinks thermal headroom, induces GPU throttling, and leads to Service-Level-Objective (SLO) violations. In this paper, we study joint cooling--computing control for LLM inference: minimizing per-job GPU-plus-cooling energy while satisfying thermal safety and latency SLO constraints. We present ETCInfer, an energy-efficient, thermal-aware scheduler that selects a pre-job Computer Room Air Conditioner (CRAC) setpoint and adapts per-GPU frequency and micro-batch size during execution. ETCInfer builds compact physics-informed control models by calibrating GPU heat generation, chassis heat dissipation, CRAC power, and prefill/decode latency relations from telemetry. These models estimate hidden thermal states and time-to-throttle, enabling the scheduler to evaluate energy, temperature, and latency before applying an action. We formulate this joint setpoint--frequency--micro-batch control problem as a partially observable Markov decision process and design ETCAdapter, a learning-based controller that minimizes per-job energy under thermal safety and SLO constraints. We implement ETCInfer as a coordination layer over typical inference and cluster management stacks. Evaluation across real-trace simulation and validation experiments shows that ETCInfer reduces total job energy by up to 33.1%, thermal throttle exposure by up to 92.9%, and keeps SLO violation rates below 0.7% even at ambient temperatures up to $48^{\circ}\mathrm{C}$.

0.17

HeatCache: Thermal-aware Energy-efficient LLM Inference Scheduling for Chassis-level Liquid Cooling in Sustainable Edge Server Rooms

cs.DC cs.PFeess.SY ·2026-09-11 ·Rui Lu, Huanghuang Liang, Kaiqi Guan, Dan Wang
similarity 0.76
Abstract

LLM inference is increasingly deployed at institution-scale edges to meet service requirements. However, multi-GPU inference consumes a large amount of electricity and produces substantial heat. To improve sustainability, operators and regulations often demand raising the ambient setpoint to reduce cooling electricity. This can increase thermal throttling and hardware aging, leading to Service-Level Objective violations. In this paper, we present HeatCache, a thermal-aware, energy-efficient LLM inference scheduler for commercial chassis-level AIO liquid-cooled GPUs at sustainable ambient temperatures. HeatCache treats AIO loops as a temporary heat buffer, measured by heat budget and schedules requests to minimize energy subject to thermal safety and SLO constraints, based on an electrical-informed heat-demand estimation from HeatiTS. We implement HeatCache atop vLLM and show that it reduces computing energy by up to 18.0%, decreases thermal-throttle exposure by 81.7%, and maintains SLO violation rates below 0.9% even up to $48~^{\circ}\mathrm{C}$.

0.11

AI-driven Thermal-aware Data Center Capacity Planning

cs.LG ·2026-10-01 ·Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai +1 more
published similarity 0.73
Abstract · Presented at DesignCon 2026

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

0.13

Modeling Liquid-Cooled Data Centers in EnergyPlus

eess.SY cs.CEcs.DCcs.LG ·2026-10-23 ·Yun-Dam Ko, Dipashreya A. Sur, Cade Napier, Carlos D. Díaz-Marín, Rishee K. Jain
code/data similarity 0.66
Abstract · 14 pages, 7 figures, 6 tables. Code: https://github.com/Urban-Informatics-Lab/energyplus-liquid-cooling

As AI workloads accelerate data center transition toward high-density racks with direct-to-chip (DTC) liquid cooling, existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap, we develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled, that models DTC liquid cooling for chilled-water and warm-water architectures as plant-loop components. It couples facility-water loops, rack-side secondary loops, coolant distribution units, and chip-junction temperatures within a single solver. Validation against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution, yields loop-temperature RMSE at or below 0.021 K, well within the 0.1 K acceptance threshold. Our case study demonstrates that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use, and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic into EnergyPlus, our work provides whole-building, long-term energy modeling for high-density AI infrastructure within an open-source framework.

0.31

Optimal Energy and LLM Task Scheduling for Multiple Cloud Data Centers

eess.SY ·2026-11-17 ·Zhongqi Zhao, Lei Fan, Zhu Han
similarity 0.66
Abstract

This paper studies coordinated Large Language Model (LLM) training-task scheduling and facility operation for geographically distributed cloud data centers (CDCs). The central question is how two scheduling flexibilities - cross-CDC task transfer and task reordering - affect service and economic outcomes when remote execution remains subject to compute, bandwidth, energy, and zone-temperature constraints. We formulate a mixed-integer optimization model that jointly determines task outcomes, heterogeneous-node assignment, execution timing, pre-execution data transfer, node activation, and facility operation. A deterministic 24-hour case study contains 3 CDCs, 15 heterogeneous graphics processing unit (GPU) nodes, 4 thermal zones per CDC, and 103 tasks. In this instance, enabling transfer increases net profit by 57.9% relative to the otherwise matched no-transfer variant and increases completed tasks from 76 to 103. The more restrictive no-transfer FIFO-prefix variant completes 14 tasks and yields negative profit. The proposed schedule transfers 39 tasks, achieves 70.3% node utilization, and maintains zone temperatures within 24°C-27°C. These fixed-instance results indicate that cross-CDC transfer and task-reordering flexibility can improve the modeled profit and task-completion outcomes under the studied conditions.

0.31

LLM-Powered Predictive Decision-Making for Sustainable Data Center Operations

cs.LG ·2026-08-19 ·Hanzhao Wang, Jingxuan Wu, Yumeng Li, Yu Pan, Guanting Chen
similarity 0.65
Abstract

The growing demand for AI-driven workloads, particularly from Large Language Models (LLMs), has raised concerns about the significant energy and resource consumption in data centers. This work introduces a novel LLM-based predictive scheduling system designed to enhance operational efficiency while reducing the environmental impact of data centers. Our system utilizes an LLM to predict key metrics such as execution time and energy consumption from source code, and it has the potential to extend to other sustainability-focused metrics like water usage for cooling and carbon emissions, provided the data center can track such data. The predictive model is followed by a real-time scheduling algorithm that allocates GPU resources, aiming to improve sustainability by optimizing both energy consumption and queuing delays. With fast inference times, the ability to generalize across diverse task types, and minimal data requirements for training, our approach offers a practical solution for data center scheduling. This framework demonstrates strong potential for advancing sustainability objectives in AI-driven infrastructure. Through our collaboration with a data center, we achieved a 32% reduction in energy consumption and a 30% decrease in waiting time.

0.08

ThermE: Predictive Management of Shared Thermal Headroom for Sustained LLM Inference on Thermally Constrained Edge SoCs

eess.SY ·2026-09-24 ·Rui Lu, Yuheng Wang, Bozheng Liu
similarity 0.65
Abstract · 13 pages, 16 figures

Compact edge system-on-chip (SoC) platforms increasingly run sustained LLM inference under thermal constraints, while their CPU, GPU, and RAM share a cooling path. Prefill and decode therefore consume shared, time-varying thermal headroom, yet vendor governors react only near hardware throttling thresholds without knowledge of request state or upcoming work. A control decision that improves current performance can thus consume headroom too quickly and degrade subsequent service. In this paper, we present ThermE, a runtime system that predicts and jointly manages shared thermal headroom for sustained LLM inference on edge SoCs. Its Fast LLM-to-Heat Compiler maps the model, requests, runtime state, and candidate actions to domain heats without executing LLMs. A partial differential equation (PDE)-constrained Headroom Predictor uses ThermPINN for offline thermal identification and a Reduced Headroom Predictor (RHP) for low-overhead online uncertainty-calibrated headroom forecasts. An Uncertainty-Aware Action Scheduler then selects actions that balance serving quality and future headroom. We implement ThermE atop vLLM and evaluate it across four LLM inference workloads. The results show that ThermE reduces TTFT and TPOT by 40.55% and 12.17%, respectively, relative to vLLM. It achieves a 5.70% SLO violation rate, compared with 12.30% for the strongest baseline, while its predictor obtains a 1.94 $^\circ$C MAE with 11.50 ms overhead.

0.09

AI Surge Accelerates the Transition to Liquid Cooling: Rethinking Energy and Water Use in Data Center Cooling

cs.CY ·2026-11-18 ·Yingbo Zhang, Eric Masanet, Shengwei Wang
similarity 0.64
Abstract

The power density of AI workloads is rapidly driving shifts to liquid cooling. This study rethinks and assesses the global impact on energy and water demand of this cooling transformation. Results suggest that liquid cooling can reduce cooling energy use by 25-56% relative to air cooling, offering substantial energy savings for GW-scale AI data centers. Best-practice PUE values could be as low as 1.07-1.08 for today's systems and 1.03-1.04 for emerging designs, and WUE values range from 0.38 to 2.63 L/kWh, depending on temperature conditions. We identify global free-cooling rack inlet temperature thresholds of 33 $^\circ$C for evaporative systems and 49 $^\circ$C for dry systems, demonstrating the practicality of 100% free cooling in many locations. The model finds that minimum PUEs do not necessarily coincide with minimum total energy use, because warmer coolant raises server power. Results quantify the large sustainability potential of liquid cooling and provide actionable targets for data center design and policies.

0.20