Modeling Liquid-Cooled Data Centers in EnergyPlus

Yun-Dam Ko, Dipashreya A. Sur, Cade Napier, Carlos D. Díaz-Marín, Rishee K. Jain

eess.SY cs.CEcs.DCcs.LG ·submitted 2026-10-23 17:24 UTC · v1
code/data

Abstract

As AI workloads accelerate data center transition toward high-density racks with direct-to-chip (DTC) liquid cooling, existing simulation tools remain limited in evaluating whole-building and multi-year efficiency. To bridge this gap, we develop a native EnergyPlus object, ElectricEquipment:ITE:LiquidCooled, that models DTC liquid cooling for chilled-water and warm-water architectures as plant-loop components. It couples facility-water loops, rack-side secondary loops, coolant distribution units, and chip-junction temperatures within a single solver. Validation against an independent Modelica implementation across 21 operating conditions, including two full-year runs compared at one-minute resolution, yields loop-temperature RMSE at or below 0.021 K, well within the 0.1 K acceptance threshold. Our case study demonstrates that warm-water liquid cooling reduces annual PUE from 1.43 to 1.25, eliminates on-site water use, and cuts total facility energy by 37.9% relative to an air-cooled baseline. By embedding liquid-cooling logic into EnergyPlus, our work provides whole-building, long-term energy modeling for high-density AI infrastructure within an open-source framework.

Comment
14 pages, 7 figures, 6 tables. Code: https://github.com/Urban-Informatics-Lab/energyplus-liquid-cooling

Closest papers

Nearest neighbours by meaning across the whole index.

HeatCache: Thermal-aware Energy-efficient LLM Inference Scheduling for Chassis-level Liquid Cooling in Sustainable Edge Server Rooms

cs.DC cs.PFeess.SY ·2026-09-11 ·Rui Lu, Huanghuang Liang, Kaiqi Guan, Dan Wang
similarity 0.68
Abstract

LLM inference is increasingly deployed at institution-scale edges to meet service requirements. However, multi-GPU inference consumes a large amount of electricity and produces substantial heat. To improve sustainability, operators and regulations often demand raising the ambient setpoint to reduce cooling electricity. This can increase thermal throttling and hardware aging, leading to Service-Level Objective violations. In this paper, we present HeatCache, a thermal-aware, energy-efficient LLM inference scheduler for commercial chassis-level AIO liquid-cooled GPUs at sustainable ambient temperatures. HeatCache treats AIO loops as a temporary heat buffer, measured by heat budget and schedules requests to minimize energy subject to thermal safety and SLO constraints, based on an electrical-informed heat-demand estimation from HeatiTS. We implement HeatCache atop vLLM and show that it reduces computing energy by up to 18.0%, decreases thermal-throttle exposure by 81.7%, and maintains SLO violation rates below 0.9% even up to $48~^{\circ}\mathrm{C}$.

0.11

Data center cooling choices shift water impacts across the grid: An integrated water-energy model for sustainable data center development

eess.SY cs.CYcs.DC ·2026-09-21 ·Garrett Alston, Nancy Love, Rabab Haider
code/data similarity 0.68
Abstract · 12 pages; 8 figures; 6 tables; appendix

Data centers are being developed at an unprecedented pace, yet their energy and water impacts, and the spatial and temporal distribution of these impacts, remain poorly characterized. Data centers consume water for cooling (direct) and through electricity generation (indirect). Decisions on siting and cooling technology result in water-energy trade-offs that extend impacts beyond the facility's location. Existing assessment frameworks rely on facility efficiency metrics and average grid water intensity factors, suppressing the temporal impacts of data center load and generation availability. They also attribute indirect consumption to the facility's location rather than to the generators (and corresponding hydrologic regions) that respond to the added load, misattributing spatial impacts. To close this gap, we develop a computational model of the data center-energy-water nexus that links facility cooling and electricity demand with hourly economic dispatch, generator-level water consumption, and monthly subbasin depletion. Built on open-source data, the model resolves where and when water is consumed, and where this consumption compounds existing water risk or creates new risk. Using the model, we study different cooling configurations and proposed developments in the state of Michigan. Air-cooled data centers halve total water consumption relative to evaporative cooling, but increase electricity demand and raise indirect water consumption by one-third, shifting the water footprint from the facility to generators. Mapping these changes to subbasins reveals depletion increases beyond the data center sites, in regions that facility-level reporting may overlook. These results show that data center water and energy impacts cannot be assessed in isolation, motivating the need for integrated modeling to inform siting, design, and reporting practices.

0.22

AI-driven Thermal-aware Data Center Capacity Planning

cs.LG ·2026-10-01 ·Yixing Li, Mark Fenton, Matthew Kaufeler, Ka Ming Leung, Xin Ai +1 more
published similarity 0.68
Abstract · Presented at DesignCon 2026

The emerging of large language models (LLMs) has posed significant challenges to the thermal management of data center. Intense GPU computation for LLMs results in localized hotspots. Moreover, spiking thermal loads during training and inference bursts make real-time cooling response more difficult to predict and control. Thermal-aware capacity planning of data center requires massive expensive high-fidelity CFD simulations. AI models can perform real-time prediction for unseen designs. However, existing works either have large prediction error, or have over-simplified assumptions for data center operations. This work presents an AI-driven framework that can perform thermal-aware capacity planning for a real-world data center in seconds. The embedded AI model learns from numerous key parameters (rack power, server power, server placement, HVAC settings etc.), and provides temperature prediction within milliseconds. This AI model is tested against high-fidelity CFD simulations, and results show that for unseen data center designs, model can achieve high accuracy with 10000X speedup. Driven by the AI model, the authors design the thermal-aware capacity planning framework. This framework can help data center designers and operators instantaneously optimize both workload distribution and HVAC cooling efficiency.

0.13

Job Class Thermal Intent Aware Liquid Cooling Allocation for AI Data Centers

cs.DC cs.PFeess.SY ·2026-09-25 ·Krishna Chaitanya Sunkara
similarity 0.66
Abstract · 6 pages, 5 figures, IEEE conference paper, first submitted to IEEE ICCSP 2026 02/02/2026

GPU-dense AI data centers need to run on liquid cooling as air simply cannot shed the heat at these power densities. Yet the cooling loops themselves are blind to what workloads are about to run; they crank up flow only after a sensor catches a temperature climb, which can take 30 to 50 seconds. We built Job-Class Thermal Intent (JCTI) to close that window. The scheduler already knows a job is coming and what class it belongs to; JCTI feeds that information straight to the cooling controller so it can stage coolant before the heat shows up. We pulled the thermal signatures for each job class out of MLPerf GPU power traces and tuned arrival patterns against Alibaba cluster data. Over 120 paired Monte Carlo trials the numbers come out to 56.4% fewer thermal violations and 60.2% less cumulative overshoot than a straight PI loop. As AI data centers evolving towards gigawatt grid loads with highly fluctuating power swings, thermally-aware scheduling reduces sudden demand and improves load prediction in grid side. Cooling and scheduling have been running as two separate systems for years despite each one knowing something the other needs, JCTI wires them together.

0.22

ETCInfer: An Energy-efficient Thermal-aware Cooling-joint Scheduler for LLM Inference in AI Datacenters

cs.DC cs.PFeess.SY ·2026-09-14 ·Rui Lu, Rui Ge, Huanghuang Liang, Xiaobo Zhou, Dan Wang
similarity 0.62
Abstract · 16 pages

Large language model (LLM) inference in AI datacenters creates a coupled control problem between GPU serving and facility cooling. Raising ambient temperature setpoints can reduce cooling energy and carbon, but also shrinks thermal headroom, induces GPU throttling, and leads to Service-Level-Objective (SLO) violations. In this paper, we study joint cooling--computing control for LLM inference: minimizing per-job GPU-plus-cooling energy while satisfying thermal safety and latency SLO constraints. We present ETCInfer, an energy-efficient, thermal-aware scheduler that selects a pre-job Computer Room Air Conditioner (CRAC) setpoint and adapts per-GPU frequency and micro-batch size during execution. ETCInfer builds compact physics-informed control models by calibrating GPU heat generation, chassis heat dissipation, CRAC power, and prefill/decode latency relations from telemetry. These models estimate hidden thermal states and time-to-throttle, enabling the scheduler to evaluate energy, temperature, and latency before applying an action. We formulate this joint setpoint--frequency--micro-batch control problem as a partially observable Markov decision process and design ETCAdapter, a learning-based controller that minimizes per-job energy under thermal safety and SLO constraints. We implement ETCInfer as a coordination layer over typical inference and cluster management stacks. Evaluation across real-trace simulation and validation experiments shows that ETCInfer reduces total job energy by up to 33.1%, thermal throttle exposure by up to 92.9%, and keeps SLO violation rates below 0.7% even at ambient temperatures up to $48^{\circ}\mathrm{C}$.

0.17

Generative Design of Liquid-Cooling Channels for Thermal Management of 2.5D and 3D Integrated Advanced Packaging

eess.SY ·2026-08-24 ·Michael Acquah, Zheng Liu
similarity 0.62
Abstract · 29 pages, 5 figures

High-power multi-chip packages require increasingly effective cooling as intensive heat is generated within a limited package area. This work presents a physics-guided generative design framework for liquid-cooling channel topology optimization in a 2.7 kW multi-chip package containing two high-power graphics processing units (GPUs) and one central processing unit (CPU). A conditional diffusion model generates symmetric channel layouts using maximum GPU temperature, GPU temperature spread, and pressure drop as performance targets. Generated designs undergo connectivity and dead-end-branch screening and are evaluated using a calibrated reduced-order thermal-fluids model. Based on 5,000 generated layouts, the multi-objective analysis identified the optimal design for thermal properties, with estimated maximum GPU temperature of 70.30 degree Celsius, GPU temperature spread of 24.90 degree Celsius, and pressure drop of 89.72 kPa. Compared to a conventional reference topology, the optimal design reduced the maximum GPU temperature, temperature spread, and pressure drop by 33.6%, 52.5%, and 72.8%, respectively. High-fidelity three-dimensional conjugate heat-transfer simulation in OpenFOAM estimated a maximum GPU temperature of 66.70 degree Celsius and a pressure drop of 92.1 kPa, showing only differences of 8.6% in temperature rise and 2.6% in pressure drop. The results demonstrate that physics-guided generative design based on the reduced-order model can efficiently discover unconventional cooling channel architectures while reducing reliance on repeating computationally expensive simulation.

0.46

From Grid to Chip: Power Architecture, Stability, and Flexibility of AI Data Centers

cs.ET cs.AReess.SY ·2026-09-10 ·Yubo Song, Rui Kong, Takuro Umihara, Pooya Davari, Frede Blaabjerg +1 more
hot direction similarity 0.59
Abstract · The manuscript has been submitted for review to IEEE Open Journal of Power Electronics

The rapid growth of artificial intelligence (AI) computing is transforming data centers into large, dynamic electrical loads. Their deployment is primarily constrained by energy availability and grid-connection capacity, which is further aggravated by the ability of power-delivery architectures, control systems, and computing workloads to operate reliably during fast grid disturbances. This article presents a technological perspective on AI data centers as grid-interactive computing systems. First, it reviews grid-integration bottlenecks, evolving connection policies, grid-code requirements, which has fostered new technological trends via spatio-temporal flexibility available through workload orchestration, cooling systems, on-site resources, and energy storage. Second, it maps the evolution of power-delivery architectures from medium-voltage grid interfaces to chip-level, discussing higher-voltage DC distribution, solid-state transformers, wide-bandgap devices, advanced chip-level power delivery, and liquid cooling. Third, it establishes a three-level stability framework spanning rack-level DC-bus dynamics, facility-level converter interactions, and system-level grid-coupled behavior. The framework connects dominant instability mechanisms, including constant power load effects, impedance interactions, forced oscillations, and operating-mode transitions, with suitable modeling, assessment, and mitigation approaches. Synthesizing these topics, this article highlights grid-to-chip co-design as a central requirement for scalable AI infrastructure, linking computing workloads, power-delivery systems, energy buffers, and grid operation.

0.27

Integrated Thermal and Power Management for Wave-Powered Subsea Data Centers via Nonlinear Model Predictive Control

eess.SY ·2026-09-28 ·Wanqun Yang, Jun Chen
similarity 0.57
Abstract · 14 figures and 11 tables

This paper develops an integrated modeling and nonlinear model predictive control (NMPC) framework for coordinating thermal management, flexible workload scheduling, wave-power utilization, and battery operation in a wave-powered subsea data center. Realistic data center workloads are constructed from job-level CPU, memory, and GPU measurements from the MIT Supercloud dataset and divided into interactive and delay-tolerant flexible jobs. Thermal behavior is represented by a three-node lumped model of the IT equipment, recirculating nitrogen, and pressure hull with surrounding seawater as the thermal boundary. The NMPC jointly optimizes the flexible workload power budget and cooling command subject to thermal, battery, and workload constraints. Closed-loop simulations under different workload, thermal, battery, and renewable-generation conditions demonstrate that the proposed framework maintains thermal safety while adapting cooling operation and flexible workload execution to wave-power availability and battery state-of-charge. The parametric studies show that battery capacity and wave-generation capacity strongly affect battery availability and flexible-workload queue accumulation, while excessive renewable generation capacity may lead to increased energy curtailment. Monte Carlo and distance-correlation analyses further show that flexible-job delay is relatively insensitive to the investigated system parameters, whereas terminal battery state-of-charge is primarily influenced by battery energy capacity and wave generation capacity.

0.17