CS Paper Radar

Real-Time Control of Sustainable Data Centers: A Two-Layer Model Predictive Control Framework with Workload Flexibility and Heat Recovery

Wenyu Liu, Enea Figini, Mario Paolone

eess.SY ·submitted 2026-08-17 11:31 UTC · v1

Abstract

This paper proposes a two-layer model predictive control (MPC) framework for the real-time operation of data centers integrated with on-site photovoltaic generation, battery energy storage, waste heat recovery, and district heating. The upper layer employs scenario-based stochastic optimization to jointly optimize intraday market participation, workload scheduling, and energy management under uncertainty. The lower layer adopts an adaptive tube-based MPC strategy that compensates short-term disturbances while tracking the dispatch references given by the upper layer. The framework further integrates multi-horizon forecasting to support real-time decision making. Microservice-based simulation studies under representative clear-sky and overcast operating conditions demonstrate that the proposed framework accurately tracks dispatch plans despite fast photovoltaic and workload fluctuations. Compared with single-layer control strategies, the adaptive lower-layer controller substantially reduces real-time dispatch deviations and the associated imbalance costs. In addition, the proposed framework naturally adapts to seasonal operating conditions and responds to carbon-aware operating signals, offering a practical approach for economically efficient, sustainable, and grid-supportive operation of future data centers.

Comment
22 pages, 14 figures

Closest papers

Nearest neighbours by meaning across the whole index.

Building Seasonal Highways for Residential Energy Hubs: Sizing, planning and operating thermal energy storage

eess.SY math.OC ·2026-10-01 ·Dario Slaifstein, Mohammad Khosravi, Gautham Ram Chandra Mouli, Laura Ramirez-Elizondo, Pavol Bauer
similarity 0.67
Abstract

The operation of residential energy hubs with multiple energy carriers (electricity, heat, mobility) poses a significant challenge due to the energy storage differences in time-constants, round-trip efficiencies and self-discharge rates. Usually, thermal storage exhibits flexibility in yearly planning optimizations or long-term scenarios. However, as optimization horizons shrink (1-48hs) so does their supplied value due to the lower round-trip efficiencies. To avoid this early depletion during operation this paper proposes a data-driven highway to steer the short-term daily control towards long-term optimality. The proposed methodology also presents how to optimally size the thermal storage and avoid yearly simulations and how all of this is related to nonlinearities in the daily operation. The presented framework links seasonal and daily optimizations through dynamic terminal sets and value functions. The seasonally-aware nonlinear economic model predictive controller achieves the most balanced performance, with the second best mean grid cost of all MPCs at -\texteuro 209. It also achieves better battery degradation control than its linear counterparts (between 26-34%) and the best thermal comfort of the nonlinear benchmarks. Nevertheless, the data-driven seasonal highway restrains the ability to control battery degradation and slightly increases computational time.

0.14

Integrated Thermal and Power Management for Wave-Powered Subsea Data Centers via Nonlinear Model Predictive Control

eess.SY ·2026-09-28 ·Wanqun Yang, Jun Chen
similarity 0.66
Abstract · 14 figures and 11 tables

This paper develops an integrated modeling and nonlinear model predictive control (NMPC) framework for coordinating thermal management, flexible workload scheduling, wave-power utilization, and battery operation in a wave-powered subsea data center. Realistic data center workloads are constructed from job-level CPU, memory, and GPU measurements from the MIT Supercloud dataset and divided into interactive and delay-tolerant flexible jobs. Thermal behavior is represented by a three-node lumped model of the IT equipment, recirculating nitrogen, and pressure hull with surrounding seawater as the thermal boundary. The NMPC jointly optimizes the flexible workload power budget and cooling command subject to thermal, battery, and workload constraints. Closed-loop simulations under different workload, thermal, battery, and renewable-generation conditions demonstrate that the proposed framework maintains thermal safety while adapting cooling operation and flexible workload execution to wave-power availability and battery state-of-charge. The parametric studies show that battery capacity and wave-generation capacity strongly affect battery availability and flexible-workload queue accumulation, while excessive renewable generation capacity may lead to increased energy curtailment. Monte Carlo and distance-correlation analyses further show that flexible-job delay is relatively insensitive to the investigated system parameters, whereas terminal battery state-of-charge is primarily influenced by battery energy capacity and wave generation capacity.

0.17

Aging-Aware Online Distributed Scheduling for Lifecycle Carbon Reduction in Geo-Distributed Data Centers

eess.SY ·2026-09-30 ·Junyu Lin, Wenjie Liu, Shunbo Lei, Wentian Lu, Jianhui Wang +1 more
similarity 0.65
Abstract

The rapid proliferation of data centers (DCs), driven by cloud computing and artificial intelligence (AI), has led to massive energy demand and carbon emissions, posing significant sustainability challenges. Carbon-aware optimization in geographically distributed data centers has been widely studied. Most existing approaches mainly focus on operational carbon emissions from server usage. However, existing literature often ignores workload-induced thermal stress, which accelerates nonlinear hardware degradation. This leads to more frequent server replacements and ultimately increases embodied carbon emissions. To address these limitations, we propose a comprehensive carbon life-cycle modeling framework for distributed data centers. Apart from operational carbon emissions, this work combines workload scheduling with a utilization-dependent exponential aging model to evaluate long-term carbon costs from server degradation. In order to solve the proposed optimization model in an online and privacy-preserving manner, an enhanced Lyapunov framework with time-varying queue shifting (TVQS) is first introduced to handle system uncertainties. Then, a zero-sum perturbation-based alternating direction method of multipliers (ZSP-ADMM) framework is developed to enable distributed coordination across geographically separated data centers while protecting locally exchanged workload information. Simulation results demonstrate that the proposed approach achieves up to 13.0% lower carbon emissions and 12.6% lower operational costs compared with benchmarks.

0.14

Comparative Evaluation of MILP, MPC, and Reinforcement Learning for Commercial Battery Dispatch Under Time-of-Use Tariffs

eess.SY ·2026-09-13 ·Hafiz Majid Hussain, Wajiha Samar, Lurian Klein, Pedro Nardelli
benchmark similarity 0.64
Abstract

Battery energy storage systems (BESS) paired with rooftop photovoltaics (PVs) can deliver measurable cost savings under time-of-use (TOU) electricity tariffs; however, the relative performance of model-based and model-free dispatch strategies remains insufficiently benchmarked on full-year, real-world commercial datasets. This paper presents a full-year (2023) comparative evaluation of three BESS dispatch approaches using data from a commercial PV installation operating under a TOU tariff. The examined strategies include: (i) a mixed-integer linear programming (MILP) formulation with perfect foresight, providing an oracle performance benchmark under the assumed model; (ii) a model predictive control (MPC) scheme based on a day-ahead persistence forecast, representing a low-complexity deployable approach; and (iii) a soft actor-critic (SAC) deep reinforcement learning agent trained under causal information constraints. The MILP benchmark achieves an annual cost reduction of 24.6\% relative to a no-storage baseline. The persistence-based MPC approach recovers 99.2\% of this benchmark using only prior-day data. In contrast, the evaluated SAC agent yields an annual cost higher than the no-storage baseline. This outcome is analyzed in the context of known challenges in reinforcement learning for energy systems, including limited observability and reward design. Overall, the results indicate that, for the studied dataset and tariff structure, persistence-based MPC captures nearly all achievable economic benefits under practical deployment constraints, whereas the considered RL configuration does not yield competitive performance under the same information limitations.

0.21

Decision-Focused Learning for Optimal Battery Scheduling Under Load and Photovoltaic Power Uncertainty in Microgrids

eess.SY ·2026-10-10 ·Marios Saleptsis, Antoine Lesage-Landry, Marco Mussetta, Sonia Leva
similarity 0.64
Abstract · 20 pages, 13 figures, submitted to Sustainable Energy, Grids and Networks

The increasing penetration of renewable energy sources in microgrids demands accurate day-ahead forecasting to support optimal battery energy storage system (BESS) scheduling. Yet the conventional predict-then-optimize paradigm trains forecasters on statistical accuracy metrics that are agnostic to the asymmetric and time-varying cost impacts of forecast errors. This work proposes a decision-focused learning (DFL) framework that trains gated recurrent unit forecasters for both load demand and photovoltaic generation directly on the downstream operational cost of a two-stage energy management system, where day-ahead BESS commitments are fixed prior to real-time balancing. Gradients are backpropagated from the real-time operational cost through both optimization stages to the forecaster weights via implicit differentiation, enabling the forecasters to internalize the penalty structure of the scheduling problem. The framework is validated on the MG2Lab experimental microgrid testbed at Politecnico di Milano across two operational scenarios of increasing grid constraint and eight forecasting configurations comprising single-source and combined-forecaster settings. Results illustrate that the DFL-trained pipeline reduces operational cost by 3.78% under normal grid conditions and by 30.60% under grid-constrained conditions relative to the accuracy- optimized baseline, while nearly eliminating load shedding events. Notably, the DFL forecasters exhibit higher statistical errors than their accuracy-trained counterparts yet achieve consistently lower operational costs, confirming that forecast accuracy and decision quality do not share a monotonic relationship in constrained microgrid scheduling.

0.12

Energy system device sizing under closed-loop operation with imperfect forecasts

eess.SY ·2026-11-12 ·Cara Koepele, Kevin Wallington, Georgios Mavromatidis, John Lygeros
similarity 0.63
Abstract · 8 pages, 7 figures, 2 tables. Submitted to the 2027 European Control Conference (ECC)

The value of renewable energy devices depends on their operation, which must adapt to weather and demand using limited, imperfect forecasts that update over time. Conventional energy systems planning practices assume unlimited foresight in a single-level formulation, potentially leading to long-term investment in suboptimal device sizes. Accounting for realistic operation corresponds to a bi-level problem: the upper level selects device sizes, while the lower level contains closed-loop operation under evolving forecasts. We solve this problem using backpropagation MPC (BP-MPC), a gradient-based method, with a deterministic MPC as the lower-level controller. Using forecast errors generated by a parameterized martingale model of forecast evolution, we investigate how forecast accuracy affects the benefits of operation-aware energy systems planning and the resulting device sizes. In a case study of an energy system comprising photovoltaics, a battery, a heat pump, and thermal storage with uncertain weather and energy demands, accounting for closed-loop operation yields higher average cost savings as forecast error increases. The resulting designs achieve these savings by progressively shifting investment from battery storage to solar generation and thermal storage, which buffers forecast mismatches.

0.29

Scarcity Pricing for State-of-Charge Management in Real-Time Markets Under Intra-Day Uncertainty

eess.SY ·2026-11-09 ·Shailesh Wasti, Aravind Retna Kumar, Sushant Varghese, Anthony Giacomoni, Parviz Alivand +2 more
similarity 0.63
Abstract

The growth in renewable resources will increase net load variability and forecast error. Energy storage resources can provide flexibility when ramp capability is limited and contribute to load leveling over the day. The challenge for system operators is how to balance these two functions in real time, when updated net load forecasts are available for a limited lookahead horizon. U.S. electricity markets are seeking ways to manage state-of-charge (SoC) within their energy markets to more efficiently utilize these resources. We propose a method to manage energy storage SoC in a real-time market by extending Hogan's (2013) scarcity pricing framework. A day-ahead SoC schedule is modified using existing multi-interval real-time unit commitment engines as net load forecasts change. To address 30-minute-ahead forecast errors, an updated 5-minute SoC target and a dynamically updated shortage price for violating the constraint are provided to each economic dispatch. We simulate PJM's energy markets for 365 days and demonstrate reliability improvements relative to a strategy that enforces the day-ahead schedule. We show cost reductions and improved price formation relative to a strategy that updates target quantities but uses an administratively chosen shortage penalty.

0.24

LLM-Powered Predictive Decision-Making for Sustainable Data Center Operations

cs.LG ·2026-08-19 ·Hanzhao Wang, Jingxuan Wu, Yumeng Li, Yu Pan, Guanting Chen
similarity 0.63
Abstract

The growing demand for AI-driven workloads, particularly from Large Language Models (LLMs), has raised concerns about the significant energy and resource consumption in data centers. This work introduces a novel LLM-based predictive scheduling system designed to enhance operational efficiency while reducing the environmental impact of data centers. Our system utilizes an LLM to predict key metrics such as execution time and energy consumption from source code, and it has the potential to extend to other sustainability-focused metrics like water usage for cooling and carbon emissions, provided the data center can track such data. The predictive model is followed by a real-time scheduling algorithm that allocates GPU resources, aiming to improve sustainability by optimizing both energy consumption and queuing delays. With fast inference times, the ability to generalize across diverse task types, and minimal data requirements for training, our approach offers a practical solution for data center scheduling. This framework demonstrates strong potential for advancing sustainability objectives in AI-driven infrastructure. Through our collaboration with a data center, we achieved a 32% reduction in energy consumption and a 30% decrease in waiting time.

0.08